Jean Factory MV-BOQ

S.No. Description Qty. Unit Rate Amount

1 11 KV Wapda Metering Panel.

Supply, of fully metered MV. Panel as per the latest


Wapda requirements. Sheet metal clad indoor floor
mounting cubical type 15 KV H.T. Panel, 3 phase, 3 wire 50
Hz in free standing design all accessories with 3 phase
copper bus bar of rated capacity 630 Amps, inter-
connections fine wiring with cleats and ferrules, earthing
bar, connecting studs. Manual charging Handle, cable
sockets, designation labels, holding down bolts all
necessary material complete in all respects, equipped as
mentioned below Provision for XLPE 15 KV cable
complete with cleats clamps. The manufactured shall
certify that HT Panel as been manufactured as per Wapda
specification P-44:96 or any other latest publication and
stands responsible for any modification required by
Wapda without any extra claim. Bil 95 KV.

VCB MV ( Vacuum Circuit Breaker)

1:630 Amps 11 KV triple pole draw out type Vaccum


Circuit Breaker (VCB) make Areva , ABB ,Siemens (Made
in Germany) or Wapda Approved Breakerfitted with
manual operated spring charged mechanism indicator for
spring charged/discharged and VCB ON-OFF position 2
overload trip coil and 1-earth fault trip coil to work in
conjunction with protection relay (IDMT) breaking
capacity 350 MVA or 25 KA at 11 KV.

6: 630 Amps isolating plugs and sockets.

2: Sets of 3 phase shutters.

1: Set of indicating lamps Red and Green

6: Single-phase epoxy cast CTS Ratio 250/5 Amps having

suitable output and accuracy for metering and protection.

1: Moving iron spring controlled Ammeter scale 0-250


Amps with phase selector switch.

3: Single pole epoxy cast potential Transformer ratio


11000/110V. 100 VA.

1: Moving iron spring controlled voltmeter scale 0-15KV


selector switch 3 ways and off.

1:11 KV/110 V, 3 Phase 4 wire KWH meter combined with


30 minutes KW maximum demand indicator.

1: 11 KV/110, 3 Phase 3 wire KVARH meter.

Jean-Factory MV-BOQ
1 of 6
1: IDMT inverse time triple pole relay CDG-61 ( Areva) or
Digital relay or as approved by Wapda having over
current, short and 1 earth fault element suitable for
operation from 5 Amps CT secondary current.

2: Cable glands of 15 KV 3 core 150mm2 XLPE cable for


incoming and outgoing cables.

1: Anti Condensation heater with thermostat control and


ON-OFF switch. 1 No.

2 Incoming and Outgoing 11 KV MV Panels/Protection


Panel

Supply installation and commissioning of fully metered


MV Panel as per the latest Wapda requirements. Sheet
metal clad indoor floor mounting cubical type 15 KV H.T.
Panel, 3 phase, 3 wire 50 Hz in free standing design all
accessories with 3 phase copper bus bar of rated capacity
630 Amps, inter- connections fine wiring with cleats and
ferrules, earthing bar, connecting studs. Manual charging
Handle, cable sockets, designation labels, holding down
bolts all necessary material complete in all respects,
equipped as mentioned below and manufactured by any
one of the manufacturers PEL, Siemens, Areva Fico.
Provision for XLPE 15 KV cable complete with cleats
clamps. The manufactured shall certify that HT Panel as
been manufactured as per Wapda specification P-44:96 or
any other latest publication and stands responsible for
any modification required by Wapda without any extra
claim. Bil 95 KV.

1 No. 11 KV Incoming Panel

1:630 Amps 11 KV triple pole draw out type Vaccum


Circuit Breaker (VCB) make Areva , ABB ,Siemens (Made in
Germany) fitted with manual operated spring charged
mechanism indicator for spring charged/discharged and
VCB ON-OFF position 2 overload trip coil and 1-earth fault
trip coil to work in conjunction with protection relay
(IDMT) breaking capacity 350 MVA or 25 KA at 11 KV.

6: 630 Amps isolating plugs and sockets.

2: Sets of 3 phase shutters.

1: Set of indicating lamps Red and Green

6: Single-phase epoxy cast CTS Ratio 250/5 Amps having

suitable output and accuracy for metering and protection.

1: Moving iron spring controlled Ammeter scale 0-250


Amps with phase selector switch.

3: Single pole epoxy cast potential Transformer ratio


11000/110V. 100 VA.

Jean-Factory MV-BOQ
2 of 6
1: Moving iron spring controlled voltmeter scale 0-15KV
selector switch 3 ways and off.

1:11 KV/110 V, 3 Phase 4 wire KWH meter combined with


30 minutes KW maximum demand indicator.

1: 11 KV/110, 3 Phase 3 wire KVARH meter.

1: IDMT inverse time triple pole relay CDG-61 ( Areva) or


Digital relay or as approved by Wapda having over
current, short and 1 earth fault element suitable for
operation from 5 Amps CT secondary current.

2: Cable glands of 15 KV 3 core 150mm2 XLPE cable for


incoming and outgoing cables.

1: Anti Condensation heater with thermostat control and


ON-OFF switch.
2: Cable glands for incoming and outgoing cables.

1: Anti Condensation heater with thermostat control and


ON-OFF switch.

1- One Single phase socket outlet 1 No.

2 Nos. Outgoing Panels to be coupled with above


mentioned incoming Panel by Busbar

2-630 Amps 11 KV triple pole draw out type Vaccum


Circuit Breaker (VCB) make Areva (AEG), Siemens, ABB
(Made in Germany) fitted with manual operated spring
charged mechanism indicator for spring
charged/discharged and VCB ON-OFF position 2 overload
trip coil and 1-earth fault trip coil to work in conjunction
with protection relay (IDMT) breaking capacity 350 MVA
or 25 KA at 11 KV.

Each VCB having the following

a) 6: 630 Amps isolating plugs and sockets.

b) 2: Sets of 3 phase shutters.

c) 1: Set of indicating lamps Red and Green

d) 3: Single-phase epoxy cast CTs Ratio 150/5 Amps having


suitable output and accuracy for metering and protection.

e) 1: Moving iron spring controlled Ammeter scale 0-150


Amps with phase selector switch.

f) 3: Space for Single pole epoxy cast potential


Transformer ratio 11000/110V. 100 VA.

g) Space for 1:11 KV/110 V, 3 Phase KWH meter


combined with 30 minutes KW maximum demand
indicator.

Jean-Factory MV-BOQ
3 of 6
h) Space for 1: 11 KV/110, 3 Phase 3 wire KVARH meter.

i)1: IDMT inverse time triple pole relay MICOM P124


(make Areva) or SPAJ-140 C (Make ABB Germany) having
over current, short and 1 earth fault element suitable for
operation from 5 Amps CT secondary current.

j) 2: Cable glands for incoming and outgoing cables.

1:Anti Condensation heater with thermostat control and


ON-OFF switch.

1- One Single phase socket outlet 1 No.

3 11 KV MV Grid End Panel Board For Wapda Grid Station

Supply of fully metered MV Panel at WAPDA Grid Station


fabricated by Wapda's approved manufacturer and
conforming to Wapda's specification No. P:44:96 to be
installed in Wapdas Grid Station by WAPDA. Sheet metal
clad indoor floor mounting cubical type 11 KV HT. Panel, 3
phase, 3 wire 50 Hz in free standing design, including all
accessories with set of 3 phase insulated copper bus bar
of rated capacity 630 Amps, inter- connections fine wiring
with cleats and ferrules, earthing bar, connecting studs.
Manual/Motorized operated charging Handle, cable
sockets, designation labels, holding down bolts all
necessary material complete in all respects, equipped as
mentioned below. The panel after inspection by Cheif
Engineer Design (NTDC) shall be handed over to SE. GSO
LESCO Lahore. The supplier/manufacturer shall certify
that MV Panel has been manufactured as per Wapda
specification and stands responsible for any modification
required by Wapda without any extra claim and will
provide the Wapda test report if required.

VCB MV ( Vacuum Circuit Breaker)

1:630 Amps 11 KV triple pole fully enclosed Vacuum


Circuit Breaker (VCB) draw out type fitted with manual
operated mechanism having mechanical indicators for
spring charged/discharge position, visual ON-OFF
indicator, having 2 overload trip coil and 1-earth fault trip
coil to work in conjunction with protection relay (IDMT)
breaking capacity 350 MVA or 25 KA at 11 KV.

6: 630 Amps isolating plugs and sockets.

2: Sets of 3 phase shutters.

1: Set of indicating lamps Red and Green

6: Single-phase epoxy cast CTS Ratio 250/5 Amps having


suitable output and accuracy for metering and protection.

Jean-Factory MV-BOQ
4 of 6
1: Moving iron spring controlled Ammeter scaled 0-250
Amps with phase selector switch.

3: Single pole epoxy cast potential Transformer ratio


11000/110V, 100 VA.

1: Moving iron spring controlled voltmeter scaled 0-15KV


with phase selector switch ON-OFF.

1:11 KV/110 V, 3 Phase 4 wire KWH meter combined with


30 minutes KW maximum demand indicator.

1: 11 KV/110, 3 Phase 3 wire KVARH meter.

j)1: IDMT inverse time triple pole relay MICOM P124


(make Areva) or SPAJ-140 C (Make ABB Germany) having
over current, short and 1 earth fault element suitable for
operation from 5 Amps CT secondary current.

2: Cable glands for incoming and outgoing cables.

1: Anti Condensation heater with ON-OFF switch.

1-Trip circuit supervision relay.

1-Capacitor Trip unit.

1-Power Factor meter.

1-Test Block Plug.

3-Surge Arrestors. 1 No.

Notes

Manufacturer / Supplier will also provide any other


accessories/metering required by WAPDA at the Grid
Station without any extra claim.

4 Electro Mechanical Backup Meter KWH & MDI

Jean-Factory MV-BOQ
5 of 6
Supply and installation of Electro Mechanical Meter CT
operated 100/5 as backup Meter of Wapda Approved
Manufacturer with the consultation of M&T (West) of
Lesco. Contractor will be responsible for calibration of
meter from M&T also get approval from Lesco for
installation of this backup meter.

1 No.

Note

Client will buy the above two items no. 3 and 4 if


required by the Wapda

5 STEP DOWN TRANSFORMER 11000V/415V

Supply, installation and commissioning of transformers


completed with lifting hooks, temperature indicator, LT.
and H.T. bushings, double float Buchholz relay 220 V,
manual tap changer, oil gauge, breather, conservator, filled
with oil, filling plugs, cooling elements, drain cock,
earthing terminals, roller wheels, LT. bus properly
connected in steel box to cover total LT. side, all necessary
materials for connections on H.T and LT. side, rated voltage
11000/415/240V, impedance to be specified by the
manufacturer, system connection. D -Y 11 neutral solidly
earthed, transformer oil including cost of all necessary
materials complete in all respects for the under
mentioned capacities. And according to Latest IEC-60076.

a) 2500 KVA 1 No.

b) 2000 KVA 1 No.

Jean-Factory MV-BOQ
6 of 6