V.M.RAJAN,M.E.(Struct),FIE,
Former CE/Civil/TANGEDCO
******
Example:
Data:
Joint A B C D
Member AB BA BC CB CD DC
DF - 0.24 0.76 0.76 0.24 -
FEM -252.66 +252.66
Distribution 60.64 192.02 -192.02 -60.64
At Mid span:
= 378.98 KN.m
Maximum +ve Bending moment at mid span BC = 378.98 92.44 =286.54 KN.m
MAB= 41.84 KNm. (At Bottom) MBA = 92.44 KNm (At Top)
= 0.36 x 20 x 2250 x 120 x (707- 0.42 x 120) = 1276.43 x 106 Nm =1276.43 KNm
Mulim=KT bwd2 fck = 0.589 x 300 x 7072 x 20/1x106 = 1766.47 kN-m > Mu i.e 429.81
KNm . Hence Safe.
Hence (3 +3) Nos. of #20 at bottom and 3 Nos. #20 at top in the mid span
Hence 3 Nos. of #20 at the top near the ends for a distance of o.25 L = 2.50 m from
face of the column as shown in Fig 6.6
Nominal shear stress v= 216.57 x 103 /300 x 707=1.02 N/mm2 < 2.80 N/mm2
For pt=100x 942/(300x707)=0.44
= 95.70 KN
Web Reinforcement:
Provide 2 Nos #8 RTS on either side at mid depth (Ast=452 mm2 > 225 mm2)
For pt = 100 x 6 x 314/2250 x 707 =0.12% Modification Factor from Fig 3 of IS 456-
2000 = 1= 1.90 For flanged section bw/bf= 300/2250=0.133 < 0.3
Modification factor 3
<707 mm Ok.
Design of Column Section :
Mmini = Pu emini= 242.87 x 22.28/1000=5.41 KNm < 138.66 KNm Mu1=138.66 KNm
Since the column is subjected to vertical load only and its top end is held in position
hence Leff is assumed to 0.8 x unsupported length of column.
p= 0.060 x 20 = 1.20
Provide (4 Nos. 20 mm Dia + 4 Nos. 16mm Dia) RTS Distributed equally on each face.
The Column is braced at lintel level by beam of size 230 mm x 300mm at height of
2.50m above plinth level.
Referring to chart 46 of SP 16 p/fck < Mini. Chart value. Hence adopt same
reinforcement.
Provide (4 Nos. 20 Dia +4 Nos. 16 mm Dia) RTS Distributed equally on each face.
Using one way continuous slab coefficients given in Table 9 of IS 456-2000, the
bending moment for End beam may be calculated and designed similar to Main Beam.
Design of Footing:
Provide 1.50 x 1.30m size of footing with equal projection on both sides.
100
Development length:
Hence bent the rod at the end upwards for footing depth.
Shear at d=285mm from face of the column = 0.215 x 1.3 x 203.22 =56.80KN
Actual shear stress = 56.80 x 103 /1500 x 285 = 0.13 N/mm2 < 0.342 N/mm2
Clear distance between bars = (1500 -100-10)/ (12-1) =126.36mm <180mm Ok.
Actual Shear stress = Column load/Area of top of footing = 1.5 x 264.18 x 103
500 x 300
Sketch :
Grade Beam Design : the Grade Beam may be Designed for wl2/30 as per IS 2911.