Vous êtes sur la page 1sur 26

SECTION 5

Relief Systems
This section is concerned with the design and operation of of the insurance underwriter covering the plant or installation.
pressure relieving systems for gas processing plants. The princi- State and federal regulations not only cover safety but also
pal elements of pressure relief systems are the individual pres- environmental considerations such as air and water pollution
sure relief devices, the flare piping system, the flare separator and noise abatement. This section presents a convenient sum-
drum, and the flare including igniters, tips, sealing devices, mary of relief system information obtained from API and other
purge and steam injection for smokeless burning. Application sources, abridged and modified for this data book. Final design
of relief devices must comply with appropriate ASME Vessel work should be consistent with the full scope of API, ASME,
Codes. Design of relief systems must also comply with applica- and other code and specification requirements.
ble state and federal codes and laws as well as the requirements

FIG. 5-1
Nomenclature

a = sonic velocity, m/s I = radiation intensity at point X, W/m2


A = required discharge area of the valve, cm2. Use k = specific heat ratio, Cp/Cv (see Section13)
valve with the next larger standard orifice size/area Kb = capacity correction factor due to back pressure
AB = bellows area, cm2 Kc = combination correction for rupture disk = 0.9
A = discharge area of the valve, cm2, for valve with = 1.0 no rupture disk installed
next standard size larger than required discharge Kd = coefficient of discharge
area Kn = correction factor for Napier steam equation
AD = disk area, cm2 Ksh = correction factor due to the amount of superheat
AN = nozzle seat area, cm2 in the stream
AP = piston area, cm2 Kv = capacity correction factor due to viscosity for liquid
Aw = total wetted surface area of vessel, m2 phase pressure relief
A3 = vessel area exposed to fire, m2 Kw = capacity correction factor due to back pressure for
B = liquid expansion coefficient, 1/C, at relieving balanced bellows pressure relief valves in liquid
temperature [or (Vol/Vol)/C] service (Fig. 5-14)
C = drag coefficient L = drum length, m
Cp = specific heat at constant pressure, kJ/(kg K) L/D = length to diameter ratio of pipe
Cv = specific heat at constant volume, kJ/(kg K) Lf = length of flame, m
C1 = coefficient determined by the ratio of specific M = Mach number at pipe outlet
heats of the gas or vapor at standard conditions MW = molecular mass of gas or vapor
d = flare tip diameter, mm MABP = maximum allowable back pressure, kPa(ga)
D = particle diameter, m NHV = net heating value of flare gas, kJ/kg
f = correction factor based on the ratio of specific heats P = set pressure, kPa(ga)
F = environment factor (see Fig.5-16) PCF = critical-flow pressure, kPa(abs)
F = relief valve factor, dimensionless Pn = normal operating gas pressure, kPa(abs)
F* = fraction of heat radiated P1 = upstream relieving pressure, kPa(abs). This is
F2 = coefficient for subcritical flow (Fig. 5-12) the set pressure plus the allowable overpressure
Fs = spring force, Newtons plus the atmospheric pressure
g = acceleration due to gravity, 9.81m/s2 P1g = upstream relieving pressure, kPa (ga). This is the
G = relative density of gas referred to air = 1.00 at set pressure plus the allowable overpressure
15C and 101.325 kPa(abs); or, if liquid, the relative P2 = downstream pressure at the valve outlet, kPa(abs)
density of liquid at flowing temperature referred to Pb = back pressure, kPa(ga)
water = 1.00 at 15C P = pressure drop, kPa
hL1 = enthalpy of saturated liquid at upstream Pw = pressure drop, mm of water
pressure, kJ/kg Q = heat input, W
hL2 = enthalpy of saturated liquid at downstream Qr = heat released, W
pressure, kJ/kg Qv = flow through valve, m3/h at standard conditions
hG2 = enthalpy of vapor at downstream pressure, kJ/kg (101.325 kPa (abs), 0C)
H = height of vapor space of vessel, m r = ratio of downstream pressure to upstream pres-
Hl = latent heat of the liquid exposed to fire, kJ/kg sure, P2/P1
HS = flare stack height, m R = distance from flame center to point X, m

5-1
FIG. 5-1 (Contd)
Nomenclature

J Wf = flare gas flow rate, kg/h


Ro = universal gas constant = 8314

kg mol K Wr = vapor rate to be relieved by the relief valve, kg/h
Re = Reynolds number (dimensionless) xi = weight fraction of component i in total stream
S = specific heat, kJ/(kg C) X = distance from the base of the stack to another
t = temperature,C point at the same elevation, m
T = absolute temperature of the inlet vapor, K Xc = dimensional reference for sizing a flare stack
Tn = normal operating gas temperature, K (Fig.5-19)
T1 = gas temperature, K, at the upstream pressure Yc = dimensional reference for sizing a flare stack
Tw = vessel wall temperature, K (Fig.5-19)
Ud = maximum allowable vapor velocity for vertical Z = compressibility factor at flowing conditions
vessel, m/s Greek
V = gas velocity, m/s = prefix, indicates finite increment
Vex = exit velocity, m/s = fraction of heat radiated
Vl = flow rate, liters/s at flowing temperature and L = density of liquid, kg/m3
pressure
v = density of vapor, kg/m3
Vw = wind velocity, m/s
= angle of flare flame from vertical, degrees
W = flow, kg/h
= viscosity at flowing temperature, mPa s
Whc = hydrocarbon flow, kg/h (centipoise)
Wstm = steam flow, kg/h S = viscosity at flowing temperature, Saybolt Universal
Seconds (SSU)

DOCUMENTATION Preliminary hazard review using process flow diagrams


and a preliminary layout, to identify hazards in the pro-
A facilitys documentation allows the user to determine that cess, with the proposed facility location, and layout, and
the facility was designed in accordance with relevant codes and with storage and handling of feed materials or intermedi-
standards. The relief system design documentation is one facet ate and final products.
of the overall facility documentation, which helps demonstrate
that the process can be operated in a safe manner. Any equip- Early engineering hazard review with more advanced
ment modifications, operations, or changes made to process pa- work products.
rameters, or operating procedures, can have a direct impact on Detailed hazards review using one of several possible
the relief system, and should therefore be documented as part techniques sanctioned by local authorities (e.g., HAZOP,
of a facility management of change (MOC) process. Hazard and Operability Analysis, What-if, Quantitative
The relief system documentation should demonstrate that Risk Evaluation), utilizing process and instrumentation
all pressure-containing equipment has been identified and that diagrams, plot plan, and other detailed design deliver-
the overpressure protection has been analyzed. Documenta- ables.
tion based on the individual protected systems can facilitate Safety Integrity Level (SIL) Review.
ensuring that all systems requiring pressure protection have
been identified. The documentation should show that potential Engineering management of change (MOC) process.
causes of overpressure have been identified, rationale has been
provided as to whether a scenario is or is not credible, and cred- Facility management of change (MOC) process.
ible causes of overpressure have been evaluated. The design Pre-start-up detailed hazard review.
basis of the disposal system, including all assumptions made
in the determination of controlling load(s), and calculated back Periodic detailed hazard review.
pressure at each relief device should be documented. A detailed
list of documentation requirements is presented in ISO 23251 CAUSES OF OVERPRESSURE
(API Std 521).
Pressure relief valves or other relieving devices are used to
protect piping and equipment against excessive over-pressure.
HAZARD REVIEWS Proper selection, use, location, and maintenance of relief de-
Appropriate hazard reviews, as a part of a Process Safety vices are essential to protect personnel and equipment as well
Management Program, are required by U.S. OSHA-29 CFR as to comply with codes and laws.
Part 1910 in the United States, and by similar regulations in Determination of the maximum relief requirements may be
most other localities in the world. These reviews are conducted difficult. Loads for complex systems are determined by conser-
during the design phase, prior to operation, and periodically vative assumptions and detailed analysis. By general assump-
during operation. The relief device sizing, and relief and dispos- tion, two unrelated emergency conditions caused by unrelated
al system design, are critical components of this review. Typical equipment failures or operator error will not occur simulta-
steps in this process are:

5-2
neously (no double jeopardy). The relationship and sequence of ture disk) on, or close to, the low pressure side of the heat
events must be considered. ISO 23251 (API Std 521) provides fur- exchanger, 2) ensure there is an adequate open relief path,
ther guidance on these issues. so that the low pressure side will not be over-pressured by a
tube rupture, or 3) design the low pressure side of the heat
The development of relief loads requires the engineer to be exchanger, and the piping and equipment in the associated
familiar with overall process design, including the type of pump systems, such that the corrected hydro-static test pressure of
drives used, cooling water source, spares provided, plant layout, the low pressure system exceeds the high pressure side design
instrumentation, and emergency shutdown philosophy. The de- pressure (in some cases maximum upstream side operating
sign of the proper relieving device must take into consideration, pressure may be used instead of design pressure). The best
as a minimum, all of the following upset conditions for the indi- option for each application is a function of the operating and
vidual equipment item if such upset can occur. Each upset condi- design pressure for each side, fluid phase on each side, fluid
tion must be carefully evaluated to determine the worst case type and service corrosion history, and the heat exchanger
condition which will dictate the relieving device capacity. design. Systems with gas, two phases, or a liquid which will
The following provides guidance for some common overpres- flash across the tube rupture, on the high pressure side, and
sure scenarios. It must be recognized that it does not and cannot a liquid on the low pressure side, should be thoroughly re-
address all potential overpressure scenarios that may be relevant viewed, since a relief valve may be less effective in preventing
for a specific piece of process equipment. The designer should surges in these circumstances. See ISO 23251 (API Std 521)
employ the Hazard Reviews discussed above to ensure that all for the definition of corrected hydro-static test pressure and
credible overpressure scenarios have been incorporated into a detailed guidance on this subject.
facilitys design. Relief protection for tube rupture is not required for dou-
ble pipe heat exchangers, if the internal parts are constructed
SUMMARY OF COMMON of schedule pipe.
RELIEF SCENARIOS
Control Failure
Blocked Discharge The failure positions of instruments and control valves
The outlet of almost any vessel, pump, compressor, fired heat- must be carefully evaluated. In practice, the control valve
er, or other equipment item can be blocked by mechanical failure may not fail in the desired position. A valve may stick in the
or human error. The relief load for many cases is the maximum wrong position, or a control loop may fail. Relief protection for
flow into the system, at relief conditions, but must be carefully these factors must be provided. Relief valve sizing require-
analyzed for each contingency. ments for these conditions should be based on flow coeffi-
cients (manufacturer data) and pressure differentials for the
Fire Exposure specific control valves and the facility involved. Credit can be
taken for some downstream flow paths, if ensured to be open
Fire is one of the least predictable events which may occur in throughout the relief event. No favorable control valve action
a gas processing facility, but is a condition that may create the may be assumed. In addition, the relief load determination
greatest relieving requirements. If fire can occur on a plant-wide should take into account that the liquid level in the upstream
basis, this condition may dictate the sizing of the entire relief sys- vessel may be lost, causing gas blow-by through the open con-
tem; however, since equipment may be dispersed geographically, trol valve.
the effect of fire exposure on the relief system may be limited to
a specific plot area. Various empirical equations have been devel- ISO 23251 (API Std 521) describes several relief scenarios
oped to determine relief loads from vessels exposed to fire. For- that consider the position of a control valve and its bypass
mula selection varies with the system and fluid considered. Fire valve. If during operation, the bypass valve may be opened to
conditions may overpressure vapor-filled, liquid-filled, or mixed- provide additional flow, then the total maximum flow (control
phase systems. See the discussion on Sizing of Relief Devices, for valve wide open, plus bypass valve at some position, depend-
details, and relief load calculation methods. ing on the service and facility practices, must be considered
when determining the relief load. If the bypass is opened only
Tube Rupture during maintenance, when the control valve is blocked in af-
ter switchover, then a design based on the maximum flow
The tubes of shell and tube heat exchangers are subject to fail- through either the control valve, or the bypass valve, which-
ure from a number of causes; including corrosion, thermal shock, ever is greater, may be considered. In this case the system
and vibration. In the event of such a failure, it is possibile that the must be evaluated during the facility hazard review to en-
high-pressure stream can overpressure the equipment and pip- sure that the proper administrative controls are in place to
ing connected to the low pressure side of the exchanger. A tube prevent a situation in which both the control valve and the
rupture can also cause short duration hydraulic pressure shock, bypass are open simultaneously.
due to the rapid acceleration of the fluid on the low pressure side
at the time of rupture. Thermal Expansion
An internal failure can vary from a leaking tube or tube sheet If isolation of a process line on the cold side of an exchanger
to a complete tube rupture where a sharp break occurs in one tube. can result in excess pressure due to heat input from the warm
The loss of containment of the low-pressure side to atmosphere is side, then the line or cold side of the exchanger should be pro-
unlikely to result from a tube rupture, if the resulting pressure on tected by a relief valve. If any equipment item or line can be
the low-pressure side, including upstream and downstream sys- isolated while full of liquid, a relief valve should be provided
tems, does not exceed the corrected hydrostatic test pressure. for thermal expansion of the contained liquid. Low process
Appropriate design options to be considered for protecting the temperatures, solar radiation, heat tracing, or changes in at-
low pressure side equipment and piping from potential tube rup- mospheric temperature can necessitate thermal overpressure
ture are: 1) Install a relief device (pressure relief valve or rup- protection. Flashing across the relief valve needs to be consid-

5-3
ered. Administrative controls for block valves around heat ex- spection practices for critical check valves, when relief protec-
changer are discussed in ASME Section VIII, Appendix M. tion is required, and recommended practices for determining
the controlling relief rate.
As a practical manner, thermal relief valves are not installed
in all instances where piping systems may be blocked in by two Reflux Failure and/or Loss of Overhead
valves. The decision to install a thermal relief valve for pip-
ing systems is typically based on the following factors: length Cooling For Fractionators
and size of piping, vapor pressure of the fluid at the elevated The failure of electrical or mechanical equipment that pro-
temperature possible, volatility and/or toxicity of the fluid, po- vides cooling or condensation in process streams can cause
tential for valve leakage (metal vs. soft seated valves), and the overpressure in fractionators and process vessels. The evalua-
presence of automatic shut down valves in the system. It is tion of relief scenarios for towers, in order to determine the ap-
common to provide thermal relief valves for cryogenic liquid ap- propriate load for the relief device, is complex. Various simpli-
plications. Guidance for when to specify thermal relief and for fied approaches have been used in the past, however the most
sizing of the valve are provided in ISO 23251 (API Std 521). A common method used today is a modified steady state material
sizing equation for a simple thermal relief valve is given later balance at relief conditions, as described by Nezami.11 Dynamic
in this chapter. A 19 mm 25 mm relief valve is commonly simulation may also be applied to evaluate the tower relief load
used for liquid filled, non-flashing piping systems containing vs. time. Care should be exercised when using the dynamic ap-
non-cryogenic liquids. proach since the results can be highly dependent on the specific
assumptions used, and may not be conservative.
Utility Failure
Loss of cooling water may occur on an area-wide or plant- Abnormal Heat Input
wide basis. Commonly affected are fractionating columns and Reboilers and other process heating equipment are designed
other equipment utilizing water cooling. Cooling water failure with a specified heat input. When they are new or recently
must be considered for individual relief devices. In addition, it cleaned, and/or due to loss of control, additional heat input
is often the governing case in sizing flare systems. above the normal design can occur. In the event of a failure of
Electric power failure, similar to cooling water failure, may temperature control, vapor generation can exceed the process
occur on an area-wide or plant-wide basis and may have a vari- systems ability to condense or otherwise absorb the build-up
ety of effects. Since electric pump and air cooler fan drives are of pressure, which may include non-condensables generated by
often employed in process units, a power failure may cause the overheating. The system should be evaluated at the relief condi-
immediate loss of reflux to fractionators. Motor driven compres- tion using a modified material balance approach.
sors will also shut down. Power failures may result in major
device and flare system relief loads.
Process Upset
Instrument air system failure, whether related to electric The source of a process upset can vary depending of the ap-
power failure or not, must be considered in sizing of the flare plication. Therefore this contingency must be analyzed individ-
system since pneumatic control loops will be interrupted. Also ually based on the specific circumstances. For example, guid-
control valves will assume the position as specified on loss of ance for fractionation towers is included in reference 11.
air and the resulting effect on the flare system must be con-
sidered. Liquid Overfilling of a Vessel
Fans on air cooled heat exchangers or cooling towers oc- Vessels are subject to overfilling and must be protected from
casionally become inoperative because of a loss of power or a overpressure from that source. The cause can be an loss of con-
mechanical breakdown. On cooling towers and on air cooled trol on the inlet, or a failure of the controls or pump on the
exchangers where independent operation of the louvers can be outlet.
maintained, credit may be taken for the cooling effect obtained
by convection and radiation in still air at ambient conditions. Transients
Transient pressure surges can occur as a result of liquid
Check Valve Failure hammer, steam hammer, or steam condensate induced ham-
mer, A pressure relief valve is normally not effective as a pro-
Failure of a check valve to close must be considered. A single tective device for these causes of overpressure, so the focus
check valve is not an effective means for preventing overpres- should be on avoiding transient pressure surges through design
sure by reverse flow from a high-pressure source. In most cases, and operation, and/or the use of a surge suppressor device.
focus should be on prevention of reverse flow. It is important to
note that, in addition to overpressure of the upstream system, Vacuum Protection
reverse flow through machinery can destroy rotating equip-
ment, causing loss of containment. If this hazard is of concern, Vessels may be subject to (partial) vacuum from liquid pump
additional means of backflow prevention should be provided out, condensation of volatiles, or other causes. Typically, indus-
(i.e. emergency shut down inter-lock and valve). try practices for vessels containing hydrocarbons is to design
for the maximum possible vacuum. In some services (i.e., very
For relief purposes, a single check valve is treated as if it is large low design pressure vessels) alternate vacuum protection
not there, unless specific maintenance and inspection practices is generally necessary.
are adhered to. Two check valves in series reduce the likelihood,
and potential magnitude of reverse flow, but over-pressuring Relief Scenarios For
of the low pressure side can still take place due to even small
check valve leaks, assuming the pressure is high enough. ISO
Specific Equipment Types
23251 (API Std 521) provides specific guidance both on how to The following equipment considerations should be followed
treat check valve failure as a relief scenario, maintenance/in- for relief system design.

5-4
Centrifugal Compressors Centrifugal compressor sys- (API Std 2000), which sets thermal breathing rates, and fire
tems should be analyzed in order to properly understand the relief rules for this equipment. Note that the fire sizing equa-
maximum pressure that can occur, and required relief protec- tions for low pressure equipment covered by ISO 28300 (API
tion (if any) for each part of the system, during operation (nor- Std 2000) differ from those in ISO 23251 (API Std 521).
mal and upset), start-up, and at shutdown, based on the normal
and maximum suction, and/or discharge conditions. The maxi- At a minimum, design of overpressure protection for tanks
mum settle out pressure for each portion of the system should should consider: liquid movement into the tank, tank breathing
be calculated based on the configuration of the recycle valves, due to weather changes that heat the tank, inert gas pad and/or
check valve, seal balance line, and the volumes of the drums, purge regulator failure, internal and external heat transfer devic-
piping and coolers. At compressor shutdown, the pressure in es, failure of vent collection systems, utility failure, blow-through
one portion of the system may temporarily rise to a higher pres- of gas from a higher pressure source, composition changes, cooling
sure than the overall final settle out pressure. failure upstream of the tank, fire, and overfilling.

Reciprocating Compressors Each positive displace- At a minimum, design of vacuum protection for tanks should
ment compressor must have a relief valve on the discharge up- consider: liquid movement out of the tank due to pump transfer,
stream of the block and check valves in order to protect the com- liquid movement out of the tank due to opening of a drain valve,
pressor and downstream equipment. Commonly, relief valves tank breathing due to weather changes that cool the tank, fail-
are also provided on each individual stage to protect the inter- ure of inert pads, utility failures.
stage equipment. Reciprocating compressor systems should be
analyzed in order to properly understand the maximum pres- SPECIAL RELIEF SYSTEM
sure that can occur, and required relief protection for each part CONSIDERATIONS
of the system, during operation (normal and upset), start-up,
and at shutdown, based on the normal and maximum suction, Administrative Controls
and/or discharge conditions.
Administrative controls are procedures that, in combination
Fired Heaters General best practice is to design fired with mechanical locking elements, are intended to ensure that
heaters such that the process side cannot be blocked in. Typical- personnel actions do not compromise the overpressure protec-
ly, the heater control system will shut down the heater in case tion of the equipment. They include, as a minimum, document-
of loss of flow on the process side, but the safety integrity level ed operation and maintenance procedures, and training of op-
(SIL) may be inadequate to avoid overpressure. If there is a pos- erator and maintenance personnel in these procedures [ASME
sibility that the process side of a fired heater may be blocked in, Boiler & Pressure Vessel Code Section VIII, Appendix M].
then a relief valve should be provided to protect the heater. The
relief valve should be installed on the downstream of the heater Block Valves in the Relief Path
to help ensure flow through the heater upon blocked outlet. ASME Section VIII, Appendix M, provides requirements, in-
cluding specific administrative controls, for block valves associ-
Pumps Relief valves are required on the discharge of ated with the inlet and outlet of pressure relief devices, block
each positive displacement pump. Normally, these relief valves valves around equipment, such as heat exchangers, which may be
are piped back to the source vessel. In some instances, the relief isolated and drained for maintenance, and block valves between
device discharge can be returned to the suction line, depending two pieces of equipment protected by a single relief device.
on the service and extent of heat up due to recycle. In either in-
stallation, the pressure present at the discharge of the pressure High Integrity Protection Systems (HIPS)
relief valve must be considered in determining the set pressure
of a conventional pressure relief valve. Isolation valves around A High Integrity Protection System (HIPS) is an instru-
the pressure relief valves may not be required, if the recycle is mented system that has multiple redundancies to ensure the
to the suction line and the pump itself can be isolated for main- system is reliable and will react with desired effects as close to
tenance. Many small metering pumps will have built-in inter- 100% of the time as possible. As part of this, the instruments
nal relief protection. As these internal reliefs are typically not and valves, and the safeguarding system, are rated and main-
identified in facility documentation (e.g., P&IDs, critical device tained to a stricter standard than most instruments. These sys-
lists, etc.), they are typically not tested or maintained. For this tems are even on a different control system. The instruments
reason, they generally should not be relied upon as a means to have a Safety Instrument Level (SIL); the higher the level the
prevent overpressure. more reliable the system. HIPS are typically used to mitigate
flare loads that otherwise would become excessively large, or
Atmospheric Storage Tanks, and Low Pressure Tanks where a pressure relief valve would not adequately protect the
Atmospheric storage tanks are typically protected against system. See Section 4 of the Data Book for more information on
overpressure and vacuum due to process conditions and atmo- High Integrity Protection Systems (HIPS).
spheric changes. In addition, relief protection for fire and other
upset conditions is required. Tanks are commonly protected by In some very limited instances (i.e. loss of control for an in-
weighted or spring loaded pallet operated relief devices (con- let valve downstream of a large packed pipeline upstream of
servation vents). A pilot-operated pressure relief can also be a treating facility, or protection against runaway reaction,) a
utilized. Storage tanks with diameters of 15 m or larger may be High Integrity Protection System may be considered to replace
fitted with a frangible roof (weak roof to shell attachment which the requirement for a pressure relief device. This is now rec-
will fail upon overpressure); such a roof-to-shell joint serves as ognized by ASME Section VIII, Division 1 (UG-140),15 with a
emergency pressure relief device in lieu of a separate fire relief number of requirements including:
valve valve (See API Std 650). All other tanks require fire over-
The user shall ensure that the MAWP of the vessel is
pressure protection by an emergency relief vent.
greater than the highest pressure that can reasonably
Pressure relief requirements and relief device sizing for at- be expected to be achieved by the system. The user shall
mospheric tanks and any tanks, vessels, or other equipment conduct a detailed analysis of all credible overpressure
designed for less than 103 kPa (ga), are covered by ISO 28300 scenarios.

5-5
This analysis shall utilize an organized, systematic process Low Temperature Flaring
safety analysis approach such as: a Hazards and Operabil-
ity (HAZOP) review; a failure mode, effects and criticality Natural gas plants frequently have more than one flare
analysis (FMECA); fault tree analysis; event tree analysis; system. (i.e. high pressure flare, low pressure flare, cryogen-
what-if analysis, or other similar methodology. ic flare). The segregation of flare systems should be carefully
evaluated, based on the fluid compositions, temperatures, and
Instrumentation associated with a HIPS shall be tested allowable back pressures in the relief header. Several incidents
at regular intervals to ensure it functions per design. have raised industry awareness on the need to properly con-
sider segregation of flare headers and systems.
Documentation of the HIPS system design and testing
shall be developed and maintained. When low temperature streams are relieved, the flare sys-
tem piping and equipment exposed to cryogenic temperature
The user shall consult ASME Section VIII, Division 1 (UG-
may require stainless steel or other acceptable alloys. The sys-
140) for the complete set of requirements for the use of HIPS as
tem should be designed for the coldest process stream to be re-
a means of overpressure protection.
lieved including the cooling effect of the expanding fluid (Joule-
Emergency Depressuring Thomson effect). Materials selection should be made according
to applicable code recommendations.
Emergency depressuring system are commonly used in
natural gas facilities. The system can be automatically actu- Industry experience has shown that formation of limited quan-
ated or operator actuated, on emergency shutdown of a piece tity of hydrates at a relief valve outlet can typically be handled
of equipment, a process unit, or an entire facility. The purpose safely. However, relieving large amounts of hydrates, or solid
of the depressurization system is one or more of the following: CO2/H2S/ methane solids to a closed flare system should be avoid-
1) minimize risk of loss of containment due to fire/runaway re- ed. Industry experience has shown that pure CO2 can be safely
action for pressure vessels, 2) minimize risk of fire, explosion, vented to the atmosphere, utilizing proper design practices.
or release of toxic gas due to partial loss of containment (e.g.,
piping or flange leak), or 3) minimize risk of fire, explosion, or SET PRESSURE FOR PRESSURE
release of toxic gas due to partial or total seal/packing failure of RELIEF VALVES
rotating equipment.
Fig. 5-2, extracted from ISO 23251 (API Std 521), shows the
Depressurization systems are often used to prevent poten- characteristics of safety relief valves for vessel protection. It can
tial stress rupture of a vessel when the metal temperature is be used as a general guide in determining the proper set pres-
raised above the design temperature due to an abnormal heat sure of a pressure relief valve, for a protected system. Refer to
source. This source is usually from a fire, but could also be from the Standard for further guidance on setting single or multiple
a runaway exothermic reaction or other source of heat. This pressure relief valves.
type of rupture can occur before a vessel reaches the set pres-
sure of relief devices on the vessel. A general guideline is that a
depressurization system should be able to reduce the pressure RELIEVING DEVICES
in the vessel to 50% of the design pressure in 15 minutes in Several pressure relief devices are certified and approved
the event of a pool fire. However, the required depressurization under SectionVIII of the ASME Boiler and Pressure Vessel
time is dependent on the vessel material and wall thickness. A Code covering unfired pressure vessels. They include spring
detailed discussion of emergency depressurization design basis loaded direct-acting pressure relief valves, pilot operated pres-
is provided in ISO 23251 (API Std 521). sure relief valves, and rupture disks and shearing pin devices.
Another application for a depressurization system is to re- When the governing code is ANSI B31.3 or ANSI B31.8, other
duce the consequences of a leak by quickly reducing the pres- types of pressure relieving devices such as monitoring regula-
sure of the system/plant/compressor. By reducing the equip- tors, series regulators, weight-loaded relief valves, liquid seals,
ment pressure, both the leak rate and the total inventory of etc. are permitted. The discussion below is limited to ASME,
fluid leaked can be reduced. A general criterion for system de- SectionVIII, devices. The devices must be compatible with the
pressurization is to reduce the pressure in the system to 690 service and the overall design of the system. See ASME, Sec-
kPa (ga) in fifteen minutes or less. tionI, for fired boiler relieving criteria.

For compressors, the depressurization time is partially a Conventional Pressure Relief Valves
function of the location of the machine, and de-pressurization
In a conventional pressure relief valve, the inlet pressure to
times of less than 15 minutes is often used. For compressors
the valve is directly opposed by a spring. Tension on the spring
located in buildings, a depressurization time of 3-5 minutes to
is set to keep the valve shut at normal operating pressure but
near atmospheric pressure are not uncommon.
allow the valve to open when the pressure reaches relieving
For each application, the designer must verify that all com- conditions. This is a differential pressure valve. Most conven-
ponents (especially vessel internals and machinery elastomer tional safety-relief valves available to the petroleum industry
seals) can withstand the chosen de-pressurization rate. In ad- have disks which have a greater area, AD, than the nozzle seat
dition, cold metal temperatures can be developed both in the area, AN. The effect of back pressure on such valves is illustrat-
source vessel and the flare system during de-pressuring. Both ed in Fig. 5-3b. If the bonnet is vented to atmospheric pressure,
systems must be designed for these conditions. the back pressure acts with the vessel pressure so as to over-
come the spring force, FS, thus making the relieving pressure
Note that the ASME Pressure Vessel Section VIII code re- less than when set with atmospheric pressure on the outlet.
quires a pressure relief device or HIPS to be installed to protect However, if the spring bonnet is vented to the valve discharge
the vessel even if a depressuring system is used. rather than to the atmosphere, the back pressure acts with the

5-6
spring pressure so as to increase the opening pressure. If the A typical pilot operated relief valve is shown in Fig.5-5. Pilot
back pressure were constant, it could be taken into account in operated valves may be used in liquid or vapor services. These
adjusting the set pressure. In operation the back pressure is not valves contain nonmetallic components (elastomers), therefore
constant when a number of valves discharge into a manifold. fluid pressure and temperature, fluid characteristics, polymer-
ization, fouling, solids, and corrosion can limit their use.
A cut-away of a conventional relief valve is shown in Fig. 5-
3a. Materials of construction for relief valves vary by service. Pilot operated valves are available with snap-action or mod-
ulating action. The modulating type relieves only the amount of
Balanced Pressure Relief Valves fluid required to control the overpressure.
Balanced safety-relief valves incorporate means for mini- When specifying pilot operated pressure relief valves, the
mizing the effect of back pressure on the performance charac- elastomers chosen for the o-rings, and seals should be carefully
teristicsopening pressure, closing pressure, lift, and reliev- considered. Temperature (maximum and minimum), chemical
ing capacity. compatibility (for the principle and trace components, and for
potential liquid carryover), and resistance to explosive de-com-
These valves are of two types, the piston type and the bel-
pression, are all factors in the choice of elastomers.
lows type. A cross section drawing of a balanced (bellows) relief
valve is shown in Fig. 5-4a. In the piston type, of which several eat Leakage, and Resilient
S
variations are manufactured, the guide is vented so that the
back pressure on opposing faces of the valve disk cancels itself; Pressure Seat Relief Valves
the top face of the piston, which has the same area, AP, as the Some leakage can be expected through the seats of with met-
nozzle seat area, AN, is subjected to atmospheric pressure by al-to-metal seated, conventional or balanced type relief valves,
venting the bonnet. The bonnet-vented gases from balanced pis- when the operating pressure rises too close to the set pressure.
ton-type valves should be disposed of with a minimum restric- Allowable seat leakage rates are specified in API Std 527.16 Re-
tion and in a safe manner. silient seat pressure relief valves (see Fig. 5-6), with either an
In the bellows type of balanced valve, the effective bellows O-ring seat seal or a plastic seat, can provide seat integrities
area, AB, is the same as the nozzle seat area, AN, and, by at- which are significantly higher than metal seated valves. API
tachment to the valve body, excludes the back pressure from Std 52716 specifies that, soft seated, pressure relief valves shall
acting on the top side of that area of the disk. The disk area ex- have zero bubbles/minute leakage at the same test pressures as
tending beyond the bellows and seat area cancel, so that there metal seated valves. This can allow bubble tight operation to
are no unbalanced forces under any downstream pressure. The 90%, of the set pressure, or higher.Proper elastomer choice is
bellows covers the disk guide so as to exclude the working fluid critical for resilient seat pressure relief valves.
from the bonnet. To provide for a possible bellows failure or
leak, the bonnet must be vented separately from the discharge. Vapor Trim vs. Liquid Trim
The balanced safety-relief valve makes higher pressures in For Pressure Relief Valves
the relief discharge manifolds possible. Balanced-type valves
Pressure relief valves handling gas or vapor are supplied
should have bonnet vents large enough to assure no appreciable
with vapor trim. Valves which releive liquid, two-phase, or po-
back pressure during design flow conditions. If the valve is in
tentially two-phase fluids, require a liquid trim. It is important
a location in which atmospheric venting (usually not a large
that the supplier is properly informed of the full range of expect-
amount) presents a hazard, the vent should be piped to a safe
ed operation when procuring pressure relief valves. In addition,
location independent of the valve discharge system. The user
liquid trim pressure relief valves have a significantly higher
should obtain performance data on the specific type of valve
blowdown as compared to vapor trim. In these applications the
being considered. A diagram of the force balance for piston and
designer must be prudent to allow sufficient pressure margin
bellows balanced pressure relief valves is shown in Fig. 5-4b.
between the operating pressure and the relief valve set pres-
Pilot Operated Pressure Relief Valves sure to ensure reclosure of the valve following a relief event.

A pilot operated pressure relief valve consists of two princi- Rupture Disk
pal parts, a main valve and a pilot. The valve utilizes a piston
A rupture disk consists of a thin diaphragm held between
instead of a shaft. Inlet pressure is directed to the top of the
flanges. The disk is designed to rupture and relieve pressure
main valve piston. More area is exposed to pressure on the top
within tolerances established by ASME Code Section VIII. Rup-
of the piston than on the bottom so pressure, instead of a spring,
ture disks can be used in gas processing plants, upstream of
holds the main valve closed. At the set pressure, the pilot opens,
relief valves, to reduce minor leakage and valve deterioration.
reducing the pressure on top of the piston thereby allowing the
In these installations, the pressure in the cavity between the
main valve to open fully. For some applications, pilot-operated
rupture disk and the relief valve should be monitored to detect
relief valves are available in minimum friction, light-weight
a ruptured or leaking disk. In some applications a rupture disk
diaphragm construction (in place of heavy pistons).
with a higher pressure rating is installed in parallel to a relief
Pilot operated valves can allow backflow if downstream valve.
pressure exceeds set points. Backflow prevention is required
Rupture disks should be used as the primary relieving de-
on valves, connected to common relief headers, where protected
vice only if using a pressure relief valve is not practical. Some
equipment can be depressured and isolated while connected to
examples of such situations are:
an active flare header, where a vacuum could occur at the inlet,
or where the downstream is connected to a system or vessel (a) Rapid rates of pressure rise. A pressure relief valve sys-
where the pressure could exceed the inlet pressure. tem does not react fast enough or cannot be made large
enough to prevent overpressure (e.g., an exchanger rup-
A check valve, split piston type valve, or backflow preventer
tured tube case or a runaway reaction in a vessel).
in the pilot line can be used.

5-7
(b) Large relieving area required. Because of extremely flow at the desired pressure rather than at a pressure higher or
high flow rates and/or low relieving pressure, providing lower than the stamped pressure.
the required relieving area with a pressure relief valve
system is not practical. A rupture disk is subject to fatigue failure due to operating
pressure cycles. To establish recommended replacement inter-
(c) A pressure relief valve system is susceptible to being vals, consult rupture disk suppliers.
plugged, and thus inoperable, during service.
Shearing Pin Device (Rupture Pin)
All rupture disks have a manufacturing design range (MDR),
which essentially specifies the users tolerancefor variations in A shearing pin device is a non-closing pressure relief-device
the burst pressure. Furthermore, disk temperature can have a actuated by differential pressure, or static inlet pressure, de-
significant affect on the pressure at which the disk will open. signed to function by the shearing of a load-carrying member
Therefore, it is essential that the designer communicate the de- that supports a pressure-containing member. The devices are
sired MDR and the full range of expected operating and relief sanctioned by ASME Section VIII, and may be used for circum-
temperatures when specifying requirements for a rupture disk. stances where rupture disks may also be appropriate. They
This will help ensure that the disk ruptures and provides relief have the advantage that the pin can be replaced without re-
moving a piping flange.

FIG. 5-2
Pressure Level Relationships for Pressure Relief Valves14

Courtesy American Petroleum Institute

5-8
FIG. 5-3a FIG. 5-4a
Conventional Pressure Relief Valve 14
Balanced Bellows Pressure Relief Valve14

Courtesy of American Petroleum Institute

Courtesy of American Petroleum Institute


FIG. 5-3b
Effect of Back Pressure for Conventional
Pressure Relief Valve14
FIG. 5-4b
Effect of Back Pressure on Set Pressure of
Balanced Pressure Relief Valve14

Courtesy of American Petroleum Institute Courtesy of American Petroleum Institute

5-9
FIG. 5-6
FIG. 5-5
O-Ring Seals For Conventional and Bellows
Pilot Operated Pressure Relief Valve14
Pressure Relief Valves

Courtesy of American Petroleum Institute

DISC RETAINING RING


DISC

RETAINER
SCREW
O-RING SEAT SEAL O-RING RETAINER

Courtesy Lonergan Company

5-10
SIZING OF RELIEF DEVICES

2
k + 1
C1 = 520 k k 1 Eq 5-3
After the required relief capacity of a relief valve has been k + 1
determined, the minimum orifice area required must be calcu-
lated. Industry standards for orifice designation, orifice area, C1 can be obtained from Figs. 5-8, and 5-9. Note that the
valve dimensions, valve body sizes, and pressure ratings are ideal gas specific heat ratio k = Cp/Cv has to be used for the
available. The standard orifices available by letter designa- determination of C1 in Equation 5-3. The ideal gas specific heat
tion, orifice area, and valve body size are shown in Fig. 5-7. ratio is independent of pressure. The heat capacity ratio used
should be based on the upstream relieving temperature. Note
In addition to the standard sizes, many relief valves are that most process simulators will provide real gas specific heats
manufactured with orifice areas smaller than D, and some at the process pressure and temperature. These should not be
pilot-operated relief valves contain orifice areas larger than used in the above equation because if this value is used, the
T. Manufacturers should be contacted for information on non- pressure relief device may be undersized. For real gases with
standard sizes. a compressibility of less than 0.8 or greater than 1.1, API Std
520 Part I states that use of the ideal gas specific heat ratio
The set pressure and the overpressure allowed must be with- can introduce significant error, and a more thermodynamically
in the limits permitted by the applicable codes. System analysis sound approach should be considered.14 The Theoretical Mass
must include downstream piping. For example, consider the use Flux Isentropic Expansion Method as described in API Std 520
of a relief valve made for a vessel with a maximum allowable Part I provides this foundation.
working pressure of 1000kPa(ga). The relief valve set pressure
is 1000kPa(ga), and the maximum allowable overpressure is Kb can be obtained from Figs. 5-10 and 5-11. For final de-
10% [100kPa(ga)]. The vessel pressure, when relieving, must sign, Kd should be obtained from the valve manufacturer. A
be limited to 1100kPa(ga) [1000kPa(ga) set pressure plus 100 value for Kd of 0.975 may be used for preliminary sizing.
kPa(ga) maximum overpressure]. Pressure buildup downstream
of the relief valve should never cause the vessel pressure to ex- Subcritical Flow For downstream pressures, P2, in ex-
ceed the maximum allowable overpressure. cess of the critical-flow pressure, PCF, the flow through the pres-
sure relief valve is subcritical. Under these conditions, Equation
API vs. Pressure Relief Valve Supplier 5-414 may be used to calculate the required effective discharge
area for a conventional relief valve that has its spring setting
Discharge Coefficient/Orifice Area adjusted to compensate for superimposed backpressure, or for a
API Std 520 Part I (clause 5.2)14 provides a thorough discus- pilot operated relief valve.
sion of the distinctions between the API effective area and the 0.179 W Z T1
actual flow area of a pressure relief valve, as well as those be-
A =
Eq 5-4
tween the API effective coefficient of discharge and the ASME (F2) (Kd Kc) MW (P1) (P1 P2)
certified coefficient of discharge. The designer is cautioned nev-
er to mix the API effective orifice area and discharge coefficient F2is taken from Fig.5-12.
with the certified values of these parameters. Furthermore, k

PCF = P1
final selection of pressure relief valve and sizing of associated 2
k 1
Eq 5-5
(inlet/outlet) piping should always use the certified values. k + 1
Balanced pressure relief valves should be sized using Equation
Sizing for Gas or Vapor Relief 5-1 or Equation 5-2 and the back pressure correction factor sup-
The rate of flow through a relief valve nozzle is dependent plied by the valve manufacturer.
on the absolute upstream pressure (as indicated in Equation5-
1, Equation5-2, and Equation5-3) and is independent of the Sizing for Steam Relief
downstream pressure as long as the downstream pressure is Safety-relief valves in steam service are sized by a modi-
less than the critical-flow pressure (See API Std 520-1). Howev- fication of Napiers steam flow formula. Valve manufacturers
er, if the downstream pressure increases above the critical-flow can supply saturated steam capacity tables. A correction fac-
pressure, the flow through the relief valve is materially reduced tor, Ksh, must be applied for safety valves in superheated steam
(e.g., when the downstream pressure equals the upstream pres- service.
sure, there is no flow).
For safety-relief valves in steam service, the required area
The critical-flow pressure, PCF, may be estimated by the per- may be estimated from the following equations from the ASME
fect gas relationship shown in Equation5-5. Code Section VIII, Div. 1 and API-520-1:14
As a rule of thumb if the downstream pressure at the relief
valve is greater than one-half of the valve inlet pressure (both
pressures in absolute units), then the relief valve nozzle will (1.905) W
A =
Eq 5-6
experience subcritical flow. (P1) (Ksh) Kd Kb Kc Kn
Critical Flow Safety valves in gas or vapor service may Kn = 1 for P1 < 10 339 kPa (abs)
be sized by use of one of these equations:14
0.02764 P1 1000
131.6W (T1) (Z) Kn =
Eq 5-7
A = Eq 5-1 0.03324 P1 1061
(C1) (Kd) (P1) (Kb) (Kc) MW
for P1 > 10 339 kPa (abs) and 22 057 kPa (abs), Kn = 1.0 where
P1 13 339 kPa (abs).
5.875Qv (T1) ( MW) (Z)
A = Eq 5-2 See Fig. 5-13 for superheat correction factors. For saturated
(C1) (Kd) (P1) (Kb) (Kc) steam at any pressure, Ksh = 1.0.

5-11
Sizing for Liquid Relief determined for the geographic area and applied to the surface
area to approximate Q (W).
Turbulent Flow Conventional and balanced bellows re-
lief valves in liquid service may be sized by use of Equation5- When the flow rate is calculated, the necessary area for re-
8.14 Pilot-operated relief valves should be used in liquid service lief may be found from the turbulent liquid flow equations.
only when the manufacturer has approved the specific applica-
tion.
Sizing a Pressure Relief Device
(7.07) (Vl) G
for Two Phase Flow
A = Eq 5-8 For two phase fluids and flashing liquids, a choking phenom-
(Kd) (Kc) (Kw) (Kv) (P1 Pb)
enon limits the flow through the pressure relief valve nozzle, in
a manner similar to the choking of a gas in critical flow. In order
Laminar Flow For liquid flow with Reynolds numbers to estimate the relief capacity of a nozzle, it is necessary to es-
less than 4,000, the valve should be sized first with Kv= 1 in timate the choking pressure and then determine the two phase
order to obtain a preliminary required discharge area, A. From physical properties at these conditions. The historical method
manufacturer standard orifice sizes, the next larger orifice size, of calculating areas for liquid and vapor relief separately, and
A, should be used in determining the Reynolds number, Re, then adding the two areas together to get the total orifice size
from the following relationship:14 does not produce a conservative relief device size.
(Vl) (112 654) (G)
Re = Eq 5-9 Improved sizing methods have been developed using the fol-
A lowing assumptions:

(511 300) (l/s) The fluid is in thermodynamic equilibrium through the


Re = Eq 5-10 nozzle.

A S
The overall fluid is well mixed and can be represented by
After the Reynolds number is determined, the factor Kv is weighted averaging the gas and liquid densities (this is
obtained from Fig.5-15. Divide the preliminary area (A) by Kv sometimes referred to as the non-slip assumption).
to obtain an area corrected for viscosity. If the corrected area Use of these assumptions has been found to produce a result
exceeds the standard orifice area chosen, repeat the procedure which in most instances is close to the real flow rate through the
using the next larger standard orifice. nozzle, and which almost always will result in a conservative
calculation of the required nozzle area. However, these methods
Sizing for Thermal Relief require additional equilibrium data along the isentropic expan-
The following may be used to approximate relieving rates of sion path through the relief valve. Refer to API Std 520, Part
liquids expanded by thermal forces where no vapor is generated 1, for a description of the sizing methods for two-phase liquid
at relief valve setting and maximum temperature. These calcu- vapor relief. Two methods are described in API Std. 520, Part
lations assume the liquid is non-compressible.13 1, Annex C; the Omega method and the Mass FluxIsentropic
Expansion Method.14
(B) (Q)
Vl = Eq 5-11
1000 (G) (S) izing for Fire for Partially
S
Liquid Filled Systems
Typical values of the liquid expansion coefficient, B, at 15C The method of calculating the relief rate for fire sizing may
are: be obtained from ISO 23251 (API Std 521), API Standard 2510,
NFPA 58, and possibly other local codes or standards. Each of
API Liquid Expansion these references approach the problem in a slightly different
Relative Density, G
Gravity Coefficient, B, 1/C manner. Note that NFPA-58 applies only to U.S. marine termi-
nals, or U.S. terminals at the end of DOT regulated pipelines.
Water 1.000 0.00018
Most systems requiring fire relief will contain liquids and/or
3 - 34.9 1.052 - 0.850 0.00072 liquids in equilibrium with vapor. Fire relief capacity in this
35 - 50.9 0.850 - 0.775 0.0009 situation is equal to the amount of vaporized liquid generated
51 - 63.9 0.775 - 0.724 0.00108
from the heat energy released from the fire and absorbed by the
liquid containing vessel. The difficult part of this procedure is
64 - 78.9 0.724 - 0.672 0.00126 the determination of heat absorbed. Several methods are avail-
79 - 88.9 0.672 - 0.642 0.00144 able, including ISO/API, and U.S. National Fire Protection As-
sociation. ISO 23251 (API Std 521) applies to the Petroleum
89 - 93.9 0.642 - 0.628 0.00153 and Natural Gas Industries, and is the standard most common-
94 - 100 0.628 - 0.611 0.00162 ly used to assess fire heat load in these services.
n-Butane 0.584 0.0020 ISO 23251/API Std 52113 expresses relief requirements in
Isobutane 0.563 0.0022 terms of heat input from the fire to a vessel containing liquids,
where adequate drainage and fire fighting equipment exist.
Propane 0.507 0.0029
Q = (43 200) (F) (Aw)0.82 Eq 5-12
For heating by atmospheric conditions, such as solar radia- The environment factor, F, in Equation 5-12 is determined
tion, the surface area of the item or line in question should be from Fig. 5-16. Credit for insulation can be taken only if the in-
calculated. Solar radiation [typically 7871040 W/m2] should be sulation system can withstand the fire and the impact of water

5-12
from a fire hose. Specific criteria are provided in ISO 23251/ configuration, and location of the relief device. For many gas
API Std 521. The appropriate equation to use where adequate plant applications, the assumption of single phase vapor relief
drainage and fire fighting equipment do not exist is also pro- is adequate for pressure relief valve sizing. See ISO 23251 (API
vided in this Standard. Std 521) for further guidance.
Awin equation 5-12 is the total wetted surface, in square me- Sizing for Fire For Supercritical Fluids
ters. Wetted surface is the surface wetted by liquid when the ves-
sel is filled to the maximum operating level. It includes at least Sometimes, the phase condition at the relieving pressure and
that portion of a vessel within a height of 8 m above grade. In temperature will be supercritical. API recommends to consider
the case of spheres and spheroids, the term applies to that por- a dynamic approach where the vessel contents are assumed to
tion of the vessel up to the elevation of its maximum horizontal be single phase (supercritical), and a step by step heat flux is
diameter or a height of 8 m, whichever is greater. Grade usually applied to the vessel walls [See ISO 23251 (API Std 521),] and
refers to ground grade but may be any level at which a sizable Ouderkirk10 for details. The same methodology can also be ap-
area of exposed flammable liquid may be present. plied for gas filled systems.
The amount of vapor generated is calculated from the latent Heavy hydrocarbons can be assumed to crack (i.e., to ther-
heat of the material at the relieving pressure of the valve. For mally decompose), and it is the users responsibility to estimate
fire relief only, this may be calculated at 121% of maximum the effective or equivalent latent heat for these applications.
allowable working pressure. All other conditions must be cal- Traditionally, a minimum latent heat value of 116 kJ/kg has
culated at 110% of maximum allowable working pressure for been used if the conditions can not be quantified.
single relief devices.
When a vessel is subjected to fire temperatures, the resulting
Latent heat data may be obtained by performing flash calcu- metal temperature may greatly reduce the pressure rating of the
lations. Mixed hydrocarbons will boil over a temperature range vessel, in particular for vessels in vapor service. Design for this
depending on the liquid composition; therefore, consideration situation should consider an emergency depressuring system
must be given to the condition on the batch distillation curve and/or a water spray system to keep metal temperatures cooler.
which will cause the largest relief valve orifice area require- For additional discussion on temperatures and flow rates due to
ments due to the heat input of a fire. Generally the calculation depressurization and fires refer to Reference 7.
is continued until some fraction of the fluid is boiled off. Other
dynamic simulation methods are also available. The latent heat RELIEF VALVE INSTALLATION
of pure and some mixed paraffin hydrocarbon materials may be
estimated using Fig. A.1 of ISO 23251 / API Std 521.13 Relief valve installation requires careful consideration of
inlet piping, pressure sensing lines (where used), and startup
When the latent heat is determined, required relieving ca- procedures. Poor installation may render the safety relief valve
pacity may be found by:13 inoperable or severely restrict the valves relieving capacity.
W = Q / Hl Eq 5-13 Either condition compromises the safety of the facility. Many
relief valve installations have block valves before and after the
The value W is used to size the relief valve orifice using relief valve for in-service testing or removal; however, these
Equation5-1 or Equation5-4. block valves must be sealed or locked open, and administrative
controls must be in place, to prevent inadvertent closure.
For vessels containing only vapor, ISO 23251 (API Std521)13
has recommended the following equation for determining re- Inlet Piping
quired relief area based on fire:
The proper design of inlet piping to safety relief valves is
183.3 (F) (A3) extremely important. Relief valves should not be installed at
A = Eq 5-14

P1 physically convenient locations unless inlet pressure losses are
given careful consideration. The ideal location is the direct con-
F can be determined using Equation 5-15.13 If the result is nection to protected equipment to minimize inlet losses. API
less than 0.01, then use F = 0.01. If insufficient information is STD 520, PartII recommends a maximum non-recoverable
available to use Equation 5-15, then use F = 0.045. pressure loss to a relief valve of three percent of set pressure,

= (Tw T1)
except for remote sensing pilot-operated pressure relief valves.
0.1406 1.25
Eq 5-15 This pressure loss shall be the total of the inlet loss, line loss,
(C1) (Kd) T10.6506
F
and the block valve loss (if used). The loss should be calculated
using the maximum rated flow through the safety relief valve.
To take credit for insulation, ISO 23251 (API Std 521) re-
quires the insulation material to function effectively at tem- Discharge Piping and Backpressure
peratures of 900C, and to retain its shape, and most of its in-
tegrity in covering the vessel in a fire, and during fire fighting. Proper discharge and relief header piping size is critical for
Typically, this requires proper insulation, plus an insulation the functioning of a pressure relief valve. Inadequate piping can
jacket constructed of a suitable material, and banding that can result in reduced relief valve capacity, cause unstable opera-
withstand the fire conditions. However, other systems may be tion, and/or, relief device damage.
able to meet these requirements. The pressure existing at the outlet of a pressure relief valve
is defined as backpressure. Backpressure which is present at
Sizing for Fire for Liquid the outlet of a pressure relief valve, when it is required to op-
Full or Nearly Full Equipment erate, is defined as superimposed backpressure. Backpressure
which develops in the discharge system, after the pressure re-
For totally or near totally liquid filled systems, the control-
lief valve opens, is built-up backpressure. The magnitude of
ling relief condition can be single vapor phase, liquid phase, or
pressure which exists at the outlet of the pressure relief valve,
two phase, depending on the fluid, liquid level, vessel size and

5-13
FIG. 5-7
API Pressure Relief Valve Designations

Orifice Orifice
Area Area
cm2 (in.2)
D 0.710 0.110
E 1.265 0.196
F 1.981 0.307
G 3.245 0.503
Standard Orifice Designation

H 5.065 0.785
J 8.303 1.287
K 11.858 1.838
L 18.406 2.853
M 23.226 3.60
N 28.000 4.34
P 41.161 6.38
Q 71.290 11.05
R 103.226 16.0
T 167.742 26.0
in. 12 1.5 2 1.5 3 23 34 36 46 68 6 10 8 10
mm 25 50 38 50 38 75 50 75 75 100 75 150 100 150 150 200 150 250 200 250
Valve Body Size (Inlet Diameter times Outlet Diameter)

FIG. 5-9
Values of C1 for Various Gases

FIG. 5-8 Mol mass k C1


Acetylene 26 1.28 345
Values of Coefficient C1 vs. k
Air 29 1.40 356
Ammonia 17 1.33 351
k C1 Argon 40 1.66 377
0.4 216.9274 Benzene 78 1.10 327
0.5 238.8252 Carbon disulfide 76 1.21 338
Carbon dioxide 44 1.28 345
0.6 257.7858
Carbon monoxide 28 1.40 356
0.7 274.5192
Chlorine 71 1.36 352
0.8 289.494
Cyclohexane 84 1.08 324
0.9 303.0392
Ethane 30 1.22 339
1.0 315.37*
Ethylene 28 1.20 337
1.1 326.7473
Helium 4 1.66 377
1.2 337.2362
Hexane 86 1.08 324
1.3 346.9764
Hydrochloric acid 36.5 1.40 356
1.4 356.0604
Hydrogen 2 1.40 356
1.5 364.5641
Hydrogen sulfide 34 1.32 348
1.6 372.5513
Iso-butane 58 1.11 328
1.7 380.0755 Methane 16 1.30 346
1.8 387.1823 Methyl alcohol 32 1.20 337
1.9 393.9112 Methyl chloride 50.5 1.20 337
2.0 400.2962 N-butane 58 1.11 328
2.1 406.3669 Natural gas 19 1.27 345
2.2 412.1494 Nitrogen 28 1.40 356
Oxygen 32 1.40 356
*Interpolated values since C1 becomes indeterminate as k approaches 1.00
Pentane 72 1.09 325
Note: Calculated from Eq. 5-3.
Propane 44 1.14 331
Sulfur dioxide 64 1.26 342

5-14
FIG. 5-10
Back Pressure Correction Factor, Kb, for Conventional Pressure Relief Valves (Vapors and Gases)14

Courtesy American Petroleum Institute

FIG. 5-11
Back-Pressure Correction Factor, Kb, for Balanced Bellows Pressure Relief Valves (Vapors and Gases)14

Note: The above curves represent a compromise of the val-


ues recommended by a number of relief valve manufactur-
ers and may be used when the make of valve or the actual
critical-flow pressure point for the vapor or gas is unknown.
When the make is known, the manufacturer should be con-
sulted for the correction factor.

These curves are for set pressures of 350 kPa gauge and
above. They are limited to back pressure below critical-flow
pressure for a given set pressure. For subcritical-flow back
pressures below 350 kPa gauge, the manufacturer must be
consulted for the values of Kb.
Courtesy American Petroleum Institute

5-15
FIG. 5-12
Values of F2 for Subcritical Flow14

Courtesy American Petroleum Institute

FIG. 5-13
Superheat Correction Factors for Pressure Relief Valves in Steam Service14

Total Temperature Superheated Steam, C


Set
Pressure 149 204 260 316 371 427 482 538 593 649
kPa (ga) Correction Factor, Ksh
100 1 0.98 0.93 0.88 0.84 0.8 0.77 0.74 0.72 0.7
140 1 0.98 0.93 0.88 0.84 0.8 0.77 0.74 0.72 0.7
275 1 0.99 0.93 0.88 0.84 0.81 0.77 0.74 0.72 0.7
415 1 0.99 0.93 0.88 0.84 0.81 0.77 0.75 0.72 0.7
550 1 0.99 0.94 0.88 0.84 0.81 0.77 0.75 0.72 0.7
690 1 0.99 0.94 0.89 0.84 0.81 0.77 0.75 0.72 0.7
830 1 0.99 0.94 0.89 0.84 0.81 0.78 0.75 0.72 0.7
970 1 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 100 1 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 250 1 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 380 1 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 520 1 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 660 1 0.95 0.9 0.85 0.81 0.78 0.75 0.72 0.7
1 790 1 0.95 0.9 0.85 0.81 0.78 0.75 0.72 0.7
1 930 1 0.96 0.9 0.85 0.81 0.78 0.75 0.72 0.7
2 070 1 0.96 0.9 0.85 0.81 0.78 0.75 0.72 0.7
2 410 1 0.96 0.9 0.86 0.82 0.78 0.75 0.72 0.7
2 760 1 0.96 0.91 0.86 0.82 0.78 0.75 0.72 0.7
3 450 1 0.96 0.92 0.86 0.82 0.78 0.75 0.73 0.7
4 140 1 0.97 0.92 0.87 0.82 0.79 0.75 0.73 0.7
5 520 1 0.95 0.88 0.83 0.79 0.76 0.73 0.7
6 900 1 0.96 0.89 0.84 0.78 0.76 0.73 0.71
8 620 1 0.97 0.91 0.85 0.8 0.77 0.74 0.71
10 350 1 0.93 0.86 0.81 0.77 0.74 0.71
12 070 1 0.94 0.86 0.81 0.77 0.73 0.7
13 790 1 0.95 0.86 0.8 0.76 0.72 0.69
17 240 1 0.95 0.85 0.78 0.73 0.69 0.66
20 690 1 0.82 0.74 0.69 0.65 0.62

Courtesy American Petroleum Institute

5-16
FIG. 5-14
Back-Pressure Sizing Correction Factor Kw for 25 Percent Overpressure on Balanced
Bellows Pressure Relief Valves (Liquids Only)14

Note:
The above curve represents a compromise of the values recommended by
a number of relief-valve manufacturers. This curve may be used when the
make of the valve is not known. When the make is known, the manufacturer
should be consulted for the correction factor.

Courtesy American Petroleum Institute

FIG. 5-15
Capacity Correction Factor Due to Viscosity for Liquid Phase Pressure Relief14

Courtesy American Petroleum Institute

5-17
ration), are not affected by backpressure. Therefore, for most
FIG. 5-16 applications the performance of pilot operating pressure relief
Fire Sizing Environmental Factors valves it not affected by either superimposed or built-up back-
pressure. The relief valve capacity can be affected if the flow
becomes sub-critical for gases, or due to reduced pressure drop
Environment1 F Factor available for liquids. In addition, if the discharge pressure can
Bare metal vessel 1.0
exceed the inlet pressure (e.g., tanks storing low vapor pressure
material), a back-flow pre-venter is required for pilot operated
Insulation Note 2 pressure relief valve.
Water-application facilities 1.0
Depressuring facilities 1.0 Pressure relief valve discharge piping must be at least the
same diameter as the valve outlet, but generally must be larger
Underground storage 0.0
to minimize backpressure.
Earth-covered storage 0.03
Reactive Force
Notes:
On high pressure valves, the reactive forces during relief are
1
See ISO 23251 (API Std 521) for appropriate use of these environmental substantial and external bracing may be required. See equa-
factors.
tions in API RP520-II for computing this force.
2
See ISO 23251 (API Std 521) for the equations to use if insulation credit
is taken. Rapid Cycling
Rapid cycling can occur when the pressure at the valve inlet
decreases at the start of relief valve flow because of excessive
after it is opened, is the total of the super imposed and built-up pressure loss in the piping to the valve, or excessive back-pres-
backpressure, and is commonly referred to a total backpres- sure.
sure. Pressure relief valves are designed with a given blow-down
The total backpressure, for all pressure relief valve styles, (difference between the set pressure and closing pressure of a
can affect the capacity of the valve. For gas service the capacity pressure relief valve), that is adjustable within limits. Under
will be affected if the flow through the valve is sub-critical. For conditions of high inlet loss, the valve may cycle at a rapid rate
liquid service the outlet backpressure will directly affect the ca- which is referred to as chattering. Rapid cycling reduces capac-
pacity. This is shown by Equations 5-2 through 5-10. ity and is destructive to the valve seat, subjects all the moving
parts in the valve to excessive wear, and can induce potentially
For a conventional (spring loaded) pressure relief valve, su- destructive vibration in the piping system. The valve responds
per imposed backpressure at the outlet of the valve acts to hold to the pressure at its inlet. If the pressure decreases during flow
the valve disc closed with a force additive to the spring force to below the valve reseat point, the valve will close; however, as
(see Fig. 5-3b). The pressure relief valve set pressure is essen- soon as the flow stops, the inlet pipe pressure loss becomes zero
tially increased by the amount of super imposed backpressure and the pressure at the valve inlet rises to relieving pressure
present. once again. If the vessel pressure is still equal to or greater than
Conventional spring loaded pressure relief valves exhibit the relief valve set pressure, the valve will open and close again.
unacceptable performance (unstable operation, and possible The mechanism of chatter is complicated and not uniquely as-
chatter), when excessive backpressure develops during a relief sociated with inlet pressure loss. However, experience has
incident due to the flow through the valve and outlet piping. shown that chattering can be prevented if the non-recoverable
For this reason API-520-1 specifies that the built-up backpres- inlet pressure loss is limited to 3% of the set pressure. Excessive
sure for conventional pressure relief valves should not exceed back-pressure for conventional and balanced-bellows pressure
10% of the set pressure, at 10% allowable overpressure (process relief valves can also cause chatter, and must be avoided. An
relief scenarios).14 Higher allowable built-up backpressure may oversized relief valve may chatter since the valve may quickly
be acceptable for other, allowable overpressures (see API-520-1 relieve enough contained fluid to allow the vessel pressure to
for specifics). momentarily fall back to below set pressure only to rapidly in-
crease again. In some cases multiple relief valves, may be pre-
A balanced pressure relief valve, Fig. 5-4a and 5-4b, can be ferred, depending on the relief contingencies.
applied where the built-up backpressure is too high for a con-
ventional pressure relief valve, and/or the superimposed or to- Resonant Chatter
tal backpressure is unacceptable for a conventional valve. The
Resonant chatter can occur with pressure relief valves when
balanced style can typically be used up to a total backpressure
the inlet piping produces excessive pressure losses at the valve
of 50% (consult with manufacturer for specific limits). The set
inlet and the natural acoustical frequency of the inlet piping ap-
pressure for a balanced pressure relief valve is not affected by
proaches the natural mechanical frequency of the valves basic
superimposed backpressure. The capacity of a balance pressure
moving parts. The higher the set pressure, the larger the valve
relief valve, however, can be affected by total backpressure, due
size, or the greater the inlet pipe pressure loss, the more likely
to a reduction in lift caused by a closing force on the unbalance
resonant chatter will occur. Resonant chatter is uncontrollable;
portion of the disk at high backpressure. See Figs. 5-11 and
that is, once started it cannot be stopped unless the pressure is
5-14 for typical capacity correction factors for gas and liquid
removed from the valve inlet. In actual application, however, the
service for balanced pressure relief valve.
valve can self-destruct before a shutdown can take place because
The lift and set pressure of pilot operated relief valves, of the very large magnitude of the impact forces involved.
where the pilot is vented to the atmosphere (typical configu-

5-18
DESIGN OF RELIEF SYSTEM TO FLARE Back Pressure Consideration
Grouping of Systems The next step in the analysis involves setting a preliminary
maximum back pressure for the system at various locations in
The first step in designing a flare system for a facility is to the flare system, and choosing between conventional, pilot op-
determine the number of segregated vent and flare headers, if erated, or balanced pressure relief valves for the various relief
more than one, which are required. Depending on plot plan, the stations. A pressure relief device inventory should be prepared,
range of equipment design pressures, desirability of isolating summarizing set pressure, estimated relieving temperature,
certain streams, temperature of the relief streams, possibility of and approximate capacity, if available. The flare style should
liquid carryover, heating value of the streams, and quantities of be considered, as well as the maximum pressure expected at
the relief streams, it may prove desirable to provide two or more the flare base.
segregated headers to the flare K.O. drum, or even to use totally
independent flare systems. Separation of high pressure and low Pressure relief valves that can tolerate higher back pressure
pressure headers, or low-temperature and wet headers, is not (e.g., balanced or pilot operated pressure relief valves) may be
uncommon. Some large integrated gas treating facilities have a selected if the back pressure is too high for conventional pres-
high pressure, low pressure, and a cryogenic flare. sure relief valves. Excessive built-up back pressure will affect
the operation of conventional pressure relief valves; high super-
Load Determination imposed back pressure will affect the set point of these valves.

The first step in determining controlling loads for a relief Flare Header Sizing Methods
header and flare system is to identify the credible major flar-
ing scenarios. These scenarios may be associated with pressure Line sizing for flare headers and relief lines requires the
relief, emergency depressuring, or transitory operating (e.g., use of compressible flow equations. Computer programs are
startup, shutdown, etc.) events. A case may be controlling be- normally used to size flare headers and to calculate the back
cause of the back-pressure it will generate in the relief header, pressure at the relief devices. The header sizes are checked for
the heat release at the flare stack, or the nature of the fluid to the major relief scenarios and then fixed. Based on these header
be flared (i.e. low heating value, composition of the fluid, low sizes, each pressure relief device is checked for proper style,
temperature, high liquid flow rate, etc.). This analysis may in- backpressure, and the effect of other devices on the set pres-
clude dividing the plant into fire zones (fire zone size is dis- sure and operation of the valve. API RP 520-II requires that the
cussed in ISO 23251 (API Std 521), identifying large individual pressure relief valve inlet and outlet piping be sized for the rat-
process relief loads, identifying common mode process failure ed relief device capacity for all devices except modulating pilot
loads, identifying common mode local or plant wide utility fail- operated relief valves, while header systems may be sized using
ure, identifying which process valves that discharge to the flare the required capacity of the controlling scenario(s). A manual
may already be open when an upset occurs (e.g., during startup sizing method is outlined below:
or shutdown), identifying maximum depressurization rates, 1. Start at the flare tip, where the outlet pressure is atmos-
and identifying possible common events of pressure relief and pheric, use design flows and work toward the individual
venting or depressurization. relief valves (pressure drop across the tip will vary with
Some favorable instrument response may be included in the the style of the flare and available system pressure drop
design of flare systems. ISO 23251 (API Std 521), Fifth Edition check with the tip manufacturer).
states, Although favorable response of conventional instrumen- 2. Establish equivalent pipe lengths between points in the
tation should not be assumed when sizing individual process system and establish losses through fittings, expansion,
equipment pressure relief, in the design of some components and contraction losses.
of a relieving system, such as the blow-down header, flare, and
flare tip, favorable response of some instruments can be as- 3. Many users limit the maximum allowed velocity at any
sumed. In practice, the relief system design basis should be part of the flare system to Mach 0.7. This limit is intend-
thoroughly analyzed using appropriate methodology (i.e. layers ed to minimize the possible effects of acoustically or flow
of protection analysis, SIL review, quantitative method), before induced vibration on the piping in the flare system. More
credit is taken. The basis of the flare design load determination detailed methods to evaluate these effects are presented
should be part of the plant formal hazard review. in references 8 and 9.
For gas plants, another key decision is whether to design 4. Estimate properties of gases in the headers from the fol-
the flare system for the maximum inlet flow of the production lowing mixture relationships (i indicates the ith compo-
header or inlet pipeline, or instead rely on a shutdown system nent).
at the plant inlet, and/or an automatic or manual well shut-in. MW = Wi / (W / MW)i Eq 5-16
Provisions also may be needed to allow venting some or all of
the produced gas to the flare on facility start-up, pipeline de- T = Wi Ti / Wi Eq 5-17
pressurization, or during an emergency in one process unit.
= xi i (MW)i0.5 / xi (MW)i0.5 Eq 5-18
Flare Location 5. Calculate the inlet pressure for each section of the line
After the load is determined, it is necessary to decide on the by adding the calculated pressure drop for that section to
location of the flares, and size of the headers and flare lines. Lo- the known outlet pressure.
cation and height of the flares must consider flare stack height, 6. Calculate sections of pipe individually using the inlet
thermal radiation, emissions during flaring, ground level con- pressure of a calculated section as the outlet pressure for
centrations in case of a flame-out, consequences of liquid car- the new section.
ryover, and noise. Frequently, the controlling criterion for flare
location is the minimum distance to continuously operating 7. Continue calculations, working towards the relief valve
equipment, which may require maintenance. or other flow source.

5-19
8. Check calculated maximum superimposed backpressure, A molecular purge reduction seal is a seal device, installed in
built-up backpressure, and total back pressure at the re- a flare stack, which uses the difference in relative molecular
lief valve against piping design pressure and the maxi- masses of purge gas and infiltrating air to reduce the rate at
mum allowable back pressure (MABP) of the flow source. which air will enter the stack. A velocity seal is a purge reduc-
See Discharge Piping and Backpressure, in this section tion seal which operates on the principle that air infiltrating
for a definition of these terms, and API Std 520-I for maxi- the stack counter to the purge flow hugs the inner wall of the
mum allowable values. flare tip. The seal looks like one or more orifices located be-
low the flare tip, which forces the air to the center of the stack
9. Adjust line size of headers until the calculated back pres- where it is swept up by the purge gas.
sure is less than both the MABP for each valve in the
system and the design pressure of the associated piping. To be effective, purge reduction seals require a purge gas,
typically natural gas or nitrogen. These seals do not stop flash-
The method outlined above employs sizing equations which back, but rather minimize the chances that the air concentra-
assume isothermal flow in the flare header. This is adequate for tion below the flare tip becomes high enough to support flash-
most uses; however, if the actual flow condition differs greatly back. These devices reduce the flow rate of purge gas which
from isothermal, the use of more complex equations and meth- otherwise would be required to accomplish this. The minimum
ods is required to predict pressure and more accurately and seal purge gas rate will be specified by flare supplier.
temperature profiles for the headers.
Purge gas is normally supplied at the end of all major flare
The choice of piping material other than carbon steel may headers and sub-headers, to ensure that the flare headers are
be dictated by temperatures and pressures in some parts of the free of air. Changes in ambient temperature, or cooling of the
flare system. Flare systems relieving fluids that produce cryo- flare header after a hot relief could cause a partial vacuum in
genic temperatures may require special metallurgy. the flare header if no purge is provided. In most cases, the sum
of the purge rates needed for the flare headers is greater than
Flare Knockout Drums the purge needed for the flare seal.
Gas streams from reliefs are frequently at or near their dew
Flare systems are commonly designed for a mechanical de-
point, where condensation may occur, and some systems may
sign pressure of at least 335 kPa (ga), to minimize the chances
relieve liquids or two-phase fluids in an overpressure event.
of equipment damage due to a flashback.
A knockout drum is usually provided near the flare base, and
serves to recover liquid hydrocarbons or water, prevent liquid
slugs, and remove large (300600 micron diameter and larger) FLARE SYSTEMS
liquid particles. The knockout drum reduces hazards caused by
burning liquid that could escape from the flare stack. All flare Types of Flares
lines should be sloped toward the knockout drum to permit con- A number of different types of flares are used in natural gas
densed liquid to drain into the drum for removal. Liquid traps processing facilities. The most common can be classified as:
in flare lines should be avoided. If liquid traps are unavoidable,
a method for liquid removal should be provided. The location of 1. Elevated Pipe Flares This style consists of an el-
the flare knockout drum also needs to take into account radia- evated flare riser with typically a flame stability device
tion effect from the burning flare. Typically these drums are constructed of stainless steel at the tip. The degree of
located between the flare and the process area, where the maxi- smokeless operation is dependent on the gas composi-
mum flare radiation exposure may be higher than allowable for tion and discharge velocity (natural gas lean in NGL may
continuously operating equipment, but reasonable enough to burn relatively smokelessly)
allow properly trained personnel appropriate time to leave in
2. Elevated Assisted Smokeless Flare A general clas-
a major flaring event.
sification of several different styles of elevated flares, de-
Knockout drums may be vertical external to the flare stack, signed to minimize smoke formation. The mechanism is
built into the bottom of a self supporting flare stack, or hori- improved combustion due to the turbulence caused by the
zontal external to the flare stack. Internals which may break assist gas. Assist gas mixing can be external at the flare
free and block the relief path are not allowed in a flare knock tip exit, internal to the flare tip, or both. These flares can
out drum. operate from below 0.5 Mach to sonic. The decision de-
pends on the acceptable back-pressure for the flare head-
Additional material on design and sizing for flare knock out er, the availability of utility streams, and the particular
drums, including sizing examples are provided in ISO 23252 design of the flare tip. The required quantity of assist gas
(API Std 521). depends on the type.
Flare Seals and Flare System Purging Steam assisted flare tip: most common type of flare
used in refinery and natural gas service where suf-
A seal is provided in the flare system between the knockout ficient steam is available. Can achieve a smokeless
drum and the flaretip to prevent flashbacks due to air ingress., operation over a wide range of flared fluids and oper-
which can result in a sudden substantial increase in pressure in ating conditions
the flare system, and potential damage. Several types of seals
can be used: 1) a water seal drum, 2) a molecular purge reduc- Low Pressure Air Assist: commonly uses air supplied
tion seal (buoyancy seal), or 3) a velocity purge reduction seal. by a blower in a channel around the flare stack to
promote smokeless operation. Generally, these sys-
A water seal drum is almost always installed in refinery tems will permit smokeless operation during day-
flare systems, and is sometimes used in natural gas processing to-day operation, but not necessarily at full flaring
plants. It separates the flare system from the flare stack and rate.
provides a water barrier which is capable of stopping flashback.

5-20
Natural gas assisted Flare: uses high pressure natu- Several non-proprietary methods for predicting thermal ra-
ral gas to provide the discharge turbulence required diation from flares are available. One method based on flare
for smokeless operation. supplier input, which can be used for preliminary calculations
for simple flares with smokeless capacity of 10% or less, at tip
3. High Pressure Elevated Staged Flare Flare tips mach number of 0.5 or less, is presented below. ISO 23521 (API
operating at sonic velocity, which use pressure energy Std 521)13 presents a similar method, which in general will pro-
to promote smokeless burning. Typically, the flare tips duce more conservative results. This and other radiation mod-
are staged using valves at the flare base. This design is els are reviewed in a paper by Schwartz and White.6
most efficient when the flare stream is high pressure
natural gas. Preliminary Elevated Flare Thermal Radiation
Calculation
4. Horizontal Ground Flare A ground flare typically
consists of a flare system operated with the flame hori- Spherical Radiation Intensity Formula:
zontally on the ground. The most common style is similar
to staged flare tips. They are often used in remote loca- (Wf) (NHV) ()
I = Eq 5-19
tions where emissions, noise and flame visibility are not 14.4 (R2)
of significant concern.
This equation has been found to be accurate for distances as
5. Enclosed Ground Flare an enclosed ground flare close to the flame as one flame length.
consisting of a burner surrounded by a shell. The system
Equation 5-19 is valid so long as the proper value of fraction
operates by introducing the flare gas into the unit via
of heat radiated, , is inserted. Classically, has been considered
a burner. Air enters the bottom of the shell via air lou-
a fuel property alone. Brzustowski et al.2 experimentally observed
vers. Enclosed ground flares are normally used only for
a dependence of on jet exit velocity. Other authors have present-
small capacity, low pressure flaring operations (such as
ed models that consider the carbon particle concentration in the
tank flares) where an elevated flare is inconvenient, and
flame. The fraction of heat radiated is a function of many variables
for high capacity situations where an elevated flare is not
including gas composition, tip diameter, flare burner design, flow-
practical due to thermal radiation or community visibility
rate and velocity, flame temperature, air-fuel mixing, and steam
concerns. Special flame arrestor burners are used in tank
or air injection; therefore a flare supplier should be consulted to
applications to minimize the possibility of back flash.
determine the specific values for a given application. A list of ven-
6. Loading and Tank Flares Several designs of elevat- dor recommended fraction of heat radiated values for the most
ed flares are available that are tailored to the destruction frequently flared gases is shown in Fig. 5-18.
of vapors during truck loading and from tanks. These de-
signs deal with the problems of low pressure, large varia- FIG. 5-17
tion in flow rate, and the potential of air ingress.
Permissible Design Flare Thermal Radiation Levels13
Elevated Flare Allowable Thermal Radiation
Thermal radiation is a prime concern in flare design and Permissible
location. Thermal radiation calculations must be performed to design level Conditions
avoid dangerous exposure to personnel, equipment, and the K (kW/m2)
surrounding area (trees, grass). Thermal radiation exposure 9.46 Maximum radiant heat intensity at any location
limits, and the effects on personnel, equipment and instrumen- where urgent emergency action by personnel is
tation on shown in Fig. 5-17 from ISO-23251 (API Std 521).13 required. When personnel enter or work in an area
with the potential for radiant heat intensity greater
Equipment protection should be evaluated on a case by case
than 6.31 kW/m2 (2000 Btu/hft2), then radiation
basis, as various pieces of equipment have different protection
shielding and/or special protective apparel (e.g. a
needs.
fire approach suit) should be considered. SAFETY
Solar radiation may add to the calculated flame radiation PRECAUTION It is important to recognize that
and is dependent upon specific atmospheric conditions and site personnel with appropriate clothing a cannot toler-
location. A typical design range for a temperate climate is 0.79 ate thermal radiation at 6.31 kW/m2 (2000 Btu/hft2)
to 1.04 kW/m2, but depends on the location. The decision to in- for more than a few seconds.
clude solar radiation, is dependent on design critieria, and is 6.31 Maximum radiant heat intensity in areas where
dependent and the site and the intent of the evaluation. emergency actions lasting up to 30 s can be required
by personnel without shielding but with appropriate
Determining Elevated Flare clothinga
Thermal Radiation 4.73 Maximum radiant heat intensity in areas where
Flare suppliers have developed proprietary radiation mod- emergency actions lasting 2 min to 3 min can be
eling programs based on equations and empirical values, and required by personnel without shielding but with
these are commonly used to assess the effects of flare radiation, appropriate clothinga
and set the flare height. The F* factor (fraction of heat radiat- 1.58 Maximum radiant heat intensity at any location
ed) values used in these programs are specific to the equations where personnel with appropriate clothing a can be
used, and are generally not interchangeable with the F* factor continuously exposed
values used in other methods. These programs have not been
 ppropriate clothing consists of hard hat, long-sleeved shirts with cuffs but-
A
a
subject to review and verification in the open literature, and are toned, work gloves, long-legged pants and work shoes. Appropriate clothing
specific to a particular flare design and exit velocity. minimizes direct skin exposure to thermal radiation.

5-21
To calculate the intensity of radiation at different locations, The coordinates of the flame center with respect to the tip
it is necessary to determine the length of the flame and its angle are:
in relation to the stack (see Fig.5-19). A convenient expression
to estimate length of flame, Lf, is shown below, based on infor- Xc = (Lf / 3) (sin ) Eq 5-26
mation from equipment suppliers. Yc = (Lf / 3) (cos ) Eq 5-27


The distance from any point on the ground level to the center

Lf = (0.12) (d)

Pw
1400
Eq 5-20 of the flame is:

R = (X Xc)2 + (Hs + Yc)2
Eq 5-28
For conventional (open pipe) subsonic flares, an estimate of to-
tal flare pressure drop is 1.5 velocity heads based on nominal Equations5-19 and 5-28 allow radiation to be calculated at any
flare tip diameter. The pressure drop equivalent to 1 velocity location.
head is given by:
The stack height results from considering the worst position
(0.102) V2 V2 vertically below the center of the flame for a given condition of
Pw = = Eq 5-21 gas flow and wind velocities (see Fig.5-19).
2
19.62
Pw is the pressure drop at the tip in mm of water. After deter- R2 = (Hs + Yc)2 Eq 5-29
mining tip diameter, d, using Equation 5-22, and the maximum R = (Hs + Yc) Eq 5-30
required relieving capacity, flame length for conditions other
than maximum flow can be calculated using Equation5-20. Hs = (R Yc) Eq 5-31

The flare radiation method applies to flare tip Mach number Hs = R [(Lf / 3) (cos )] Eq 5-32
of 0.50 or less in Equation 5-22. This method assumes that for different wind velocities the
length of the flame remains constant. In reality this is not true.

1000 Eq 5-22
0.5 When the wind blows at more than 25 m/s, the flame tends to
d = 3.23 105 W Z T shorten. For practical design, this effect is neglected.

P2 M k MW API Preliminary Elevated Flare Thermal Radia-
tion Method ISO 23251 (API Std 521) presents a similar
Sonic velocity of a gas is given by: methodology for calculation of flare radiation. The API method
is generally more conservative to that shown above. The follow-
ing are the major differences.

a


= k R0 T Eq 5-23
MW FIG. 5-19
Dimensional References for Sizing a Flare Stack
The center of the flame is assumed to be located at a distance
equal to 1/3 the length of the flame from the tip.
The angle of the flame results from the vectorial addition of
the velocity of the wind and the gas exit velocity.

Vw
= tan1 Eq 5-24
Vex Lf
WIND

P
Vex = 168

w
Eq 5-25 yC
1400

XC
FIG. 5-18 d
Typical Fraction of Heat Radiated Values for Flared R
HS + Y C
Gases
HS

Carbon Monoxide 0.075


Hydrogen 0.075
Hydrogen Sulfide 0.070
Ammonia 0.070
Methane 0.10
Propane 0.11 X - XC
Butane 0.12
Ethylene 0.12 X
Propylene 0.13
The maximum value of for any gas is 0.13. Courtesy American Petroleum Institute

5-22
Different equation used for length flame mittent and non-scheduled. The flare must be instantly available
for full emergency duty to prevent any possibility of a hazard-
Different values used for fraction of heat radiated for ous or environmentally offensive discharge to the atmosphere.
flared gas by component Wind-shields and flame-retention devices may be used to ensure
The API method gives a leaner flame angle continuous piloting under the most adverse conditions. Most pi-
lots are designed to operate at wind velocities of 160 km/h and
Low Heating Value Gas Flaring higher. Multiple pilots are generally provided.
Low heating value gases are common in many gas plants; The most common flare pilot ignition system is a flame front
for example, vent gas from a sweet gas amine system or the generator, where a flame generated by compressed air and fuel
feed gas to a sulfur plant. These streams can be a challenge for gas is sent through a pipe at high velocity up the flare stack
a flare system. A number of tests were performed in the 1980s to ignite the pilot gas. Spark plug type igniters are sometimes
to assess flare flame stability, and combustion efficiency, for a used as well.
wide range of fluids. Based on this testing it was concluded that
Proper flame monitoring is critical to flare operation. Typi-
high heating value gases can be flared with a thermal destruc-
cal systems consist of multiple flame detectors, or multiple
tion efficiency of greater than 98% over a wide range of flare
thermocouples, along with closed-circuit television.
types and flare tip velocities. For low heating value gas, howev-
er, the testing found that a minimum heating value is needed, Flare Siting and Regulations
and that flare tip velocity must be limited in order to achieve
high destruction efficiency. To flare gas streams with low heat- Flare design must comply with local, state, and federal reg-
ing value, the gas must be supplemented by natural gas injec- ulations regarding pollution, noise, and location. Permits are
tion in the flare header or at the flare tip, to ensure a minimum usually required prior to construction. Flaring of gas for the
heating value of approximately 7450 kJ/Nm3 for an unassisted purpose of emissions control (as opposed to relief), is regulated
flare and 9315 to 11 180 kJ/Nm3 for an assisted flare, and the in the U.S.A. by the Environmental Protection Agency (EPA),
maximum flare tip velocity must be substantially limited. and specific maximum flare tip velocities may apply. Stand-
ards for design of flare systems are covered by API Std 537 and
Smokeless Operation ISO23251 (API Std 521).
Most smokeless flares utilize outside motive forces to pro- Atmospheric Vent Stacks
duce efficient gas/air mixing and turbulence from the momen-
tum transferred by the high velocities of the external motive jet Atmospheric vent stacks can be used to dispose of non-toxic
streams (steam, fuel, gas, etc.). The assist medium mass flow hydrocarbons to the atmosphere, under the proper conditions.
requirements are low for steam and fuel gas because of their In the natural gas industry, vent stacks for hydrocarbons are
high velocity relative to the flare gas. Flare suppliers should typically limited to atmospheric disposal of lighter-than-air
be consulted, because the assist gas rate is dependent on the gases. Stacks are many times used in natural gas compressor
flare design. stations to vent an individual compressor or the entire station
to the atmosphere on an emergency shutdown.
ISO 23251 (API Std 521) presents a table with suggested
injection steam rates based on the type of gas being flared. The Before designing a vent stack system for a facility, it is
following fitting equation may be used for calculation of the in- important to consider a number of factors: vent stack location
jection steam rate for a mixture of paraffins (reference 12): relative to plant and public facilities (permanent or temporary),
vent stack height, possibility of a combustible or toxic mixture
10.8 at grade or at an elevated platform, layers of protection in place
Wstm = Whc 0.49 Eq 5-33
MW at upstream equipment, level controls to prevent overflow of
volatile liquids into the stack, appropriately sized knock out
For a mixture of olefins, the fitting equation becomes:
drum, possibility of explosive release of energy due to detona-
10.8 tion of a vapor cloud, radiation due to a jet fire at the vent stack
Wstm = Whc 0.79 Eq 5-34 tip caused by static ignition or lightning. The decision to dis-
MW
charge hydrocarbons or other flammable or hazardous vapors
The water spray and air blower methods provide necessary to the atmosphere usually requires that a dispersion analysis
mixing with low velocities and greater mass flow rates. The re- be carried out to ensure that disposal can be accomplished with-
quired assist fluid injection rate is highly dependent upon the out creating a hazard. These topics are covered extensively in
method of injection and atomization. Wind also has a signifi- ISO 23251 (API Std 521).
cant effect on water spray flares and may greatly reduce their
effectiveness. APPLICABLE CODES, STANDARDS, AND
The blower assisted flare uses air to produce smokeless op- RECOMMENDED PRACTICES
eration. Forced draft from a blower assists combustion and air/
gas turbulence, promoting smokeless operation. With blower The designers of relief systems should be familiar with the
assisted flares it is common, for high capacity flares, to design following documents related to pressure relief valves in process
the air assist for a the portion of the maximum capacity ex- plants and natural-gas systems.
pected during operation, and to allow a degree of smoke during ASME Boiler and Pressure Vessel Code, Section I, Rules for
the full emergency relief. This, however, is dependant on local Construction of Power Boilers
requirements.
ASME Boiler and Pressure Vessel Code, Section VIII.
Pilots and Ignition ASME B31.1 Power Piping
Reliable pilot operation under all wind and weather condi-
ASME B31.3 Process Piping
tions is essential. Flaring operations are for the most part inter-

5-23
ASME B31.4 Pipeline Transportation Systems for Liquid OSHA PublicationsOSHA Title29, Part1910 Part
Hydrocarbons and Other Liquids 1910 includes handling, storage, and safety requirements for
LPG and ammonia.
ASME B31.8 Gas Transmission & Distribution Systems.
CGA (Compressed Gas Association) Publications Se-
API Std 520-I Sizing, Selection, and Installation of Pres- ries of standards covering transportation, handling, and stor-
sure-Relieving Devices in Refineries, Part I Sizing and Selec- age of compressed gases including:
tion.
Pamphlet S-1.2 Safety Relief Device Standards
API RP 520-II Sizing, Selection, and Installation of Pres-
sure-Relieving Devices in Refineries, Part II - Installation. Part 2: Cargo and portable tanks for compressed gases.
API Std 526 Flanged Steel Pressure Relief Valves. Pamphlet S-1.3 Safety Relief Service Standards
API Std 527 Seat Tightness of Pressure Relief Valves. Part 3: Compressed Gas Storage Containers.
API Std 537 Flare details for General Refinery and Pet-
rochemical Service. REFERENCES
API Standard 620 Design and Construction of Large, 1. Min, T. C., Fauske, H. K., Patrick, M., Industrial Engineering
Chemical Fundamentals, (1966), pp.50-51.
Welded, Low-Pressure Storage Tanks.
2. Brzustowski, T. A., Flaring In The Energy Industry, Process
API Standard 650 Welded Steel Tanks for Oil Storage. Energy Combustion Science, Pergamon Press, Great Britain,
API STD 2508 Design and Construction of Ethane and V.2, pp.129-144, 1976.
Ethylene Installations at Marine and Pipeline Terminals, Nat- 3. Straitz III, J. F., Nomograms Determining Proper Flame Tip Di-
ural Gas Processing Plants, Refineries, Petrochemical Plants, ameter and Height, Oil Gas and Petroleum Equipment, Tulsa,
and Tank Farms Covers the design, construction, and loca- Oklahoma, July and August, 1979.
tion of refrigerated (including autorefrigerated) liquefied eth- 4. Recommendations and Guidelines Gasoline Plants, Pam-
ane and ethylene installations, which may be associated with phlet 301, Oil Insurance Association, 175 West Jackson Blvd.,
one or more of the following: railroad, truck, pipeline stations, Chicago, Illinois 60604, August 1971.
or marine loading or unloading racks or docks.
5. Van Boskirk, B. A., Sensitivity of Relief Valves to Inlet and
API STD 2510 Design and Construction of LPG Installa- Outlet Line Lengths, Chemical Engineering, August 23, 1982,
tions. Covers LPG Storage Vessels, Loading and Unloading Fa- pages 77-82.
cilities at Marine and Pipeline Terminals, Natural Gas Process- 6. Schwartz, Robert E. and White, Jeff W., Predict Radiation From
ing Plants, Refineries, Petrochemical Plants, and Tank Farms. Flares, Chemical Engineering Progress, Vol. 93, pp. 42-49, July
API Specification 12F Specification for Shop Welded 1997 .
Tanks for Storage of Production Liquids. 7. Overa, Sverre J., Strange, Ellen and Salater, Per, Determina-
tion of Temperatures and Flare Rates During Depressurization
API Specification 12D Specification for Field Welded and Fire, GPA Convention, San Antonio, Texas, 1517 March,
Tanks for Storage of Production Liquids. 1993.
API Bulletin 2521 Use of Pressure Vacuum Vent Valves 8. Carucci, V.M., and Mueller, R.T., Acoustically Induced Piping
for Atmospheric Pressure Tanks to Reduce Evaporation Loss. Vibration in High Capacity Pressure Reducing Systems, ASME
Paper 82-WA/PVP-8, 1982.
National Board Pressure Relief Device Certifications NB-
18 (RedBook) 9. Energy Institute, IP SAFE Hydrocarbon Leak Reduction Volume
2.00, Guidelines for the Avoidance of Vibration Induced Fatigue
ISO 15156/NACE MR0175 Petroleum and Natural Gas In- in Process Pipework, ISBN 9780852934630, 2nd edition, March
dustries Materials for Use in H2S-containing Environments 2008.
in Oil and Gas Production. 10. Ouderkirk, R., Rigorously Size Relief Valves for Supercritical
ISO 23251 (API Std 521), Pressure-Relieving and Depres- Fluids, Chemical Engineering Progress, August 2002.
suring Systems. 11. Nezami, P.L., Distillation Column Relief Loads Part 1, Hydro-
carbon Processing, April 2008, and Part 2 May 2008.
ISO 28300 (API Std 2000), Venting Atmospheric and Low-
Pressure Storage Tanks (Nonrefrigerated and Refrigerated). 12. O.C. Leite, Smokeless, Efficient, Non-toxic Flaring, Hydrocar-
bon Processing, March 1991, page 77.
NFPA 30 Flammable and Combustible Liquids Code
13. ISO 23251 API Std521 Pressure-relieving and Depressuring
NFPA 58 Liquefied Petroleum Gas Code Systems (Fifth Edition, 2007), American Petroleum Institute,
1220 L Street, NW, Washington, DC 20005.
NFPA 59 LP-Gas, Plant Code (Note: For Utility Plants)
14. API 520-520-I Recommended Practice for the Design of Pres-
NFPA 59A Production Storage and Handling of Liquid sure Relieving Systems in Refineries (Eighth Edition, 2008,
Natural Gas (LNG) American Petroleum Institute, 1220 L Street, NW, Washington,
DC 20005.
NFPA 68 Standard of Explosion Prevention by Deflagra-
tion Venting 15. ASME Boiler and Pressure Vessel Code, Section VIII, Div. 1,
2010.
NFPA 69 Standard of Explosion Prevention Systems
16. API Std 527, Seat Tightness for Pressure Relief Valves, Reaf-
firmed 2007.

5-24
BIBLIOGRAPHY  traitz III, J. F., Solving Flare-Noise Problems, Inter. Noise78, San
S
Francisco 8-10, May 1978, Pages 1-6.
Chiu, C. H. Apply Depressuring Analysis to Cryogenic Plant Safety,
Hydrocarbon Processing, November 1982, Pages 255-264. Straitz III, J. F., Flaring for Safety and Environmental Protection,
Drilling-DCW, November 1977.
Kandell, Paul Program Sizes Pipe and Flare Manifolds for Compress-
ible Flow, Chemical Engineering, June 29, 1981, Pages 89-93. Straitz III, J. F., Make the Flare Protect the Environment, Hydrocar-
bon Processing, October 1977.
Powell, W. W., and Papa, D. M., Precision Valves for Industry, Ander-
son, Greenwood Company, Houston, Texas, 1982, Pages 52-61. an, S. H., Flare Systems Design Simplified, Hydrocarbon Process-
T
ing (Waste Treatment & Flare Stack Design Handbook) 1968, Pages
81-85.

5-25
NOTES:

5-26

Vous aimerez peut-être aussi