Features (B)
Fiber
optic
Loop powered type : Power from measured input sensor
M 4 N S N A (I)
SSR/
Measuring input range Power
A DC4-20mA controller
Power supply
N Loop powered type (J)
Measuring function Counter
S Scaling
Specifications Tacho/
Speed/ Pulse
meter
Model M4NS-NA M4YS-NA
(N)
Power supply Loop powered type Display
unit
Display method 7 Segment LED display
Character height 10mm 14mm (O)
Sensor
Display accuracy1 F.S. 0.3% rdg 1digit controller
L-5
M4NS/M4YS
2
1 3 1
2 3 4
1. Display value, parameter, error display 3. , (Up) key: When enter into the status of parameter setting
2. M, key: When enter into parameter group, return to RUN 4. , (Shift) key: When enter into the status of parameter set-
mode, after completing parameter setting ting and move digit
Connections
M4NS-NA M4YS-NA
INPUT
INPUT
1 2 3 4 5 1 2 3 4 5 6 7
+ - - +
DC4-20mA
DC4-20mA
Dimensions
M4NS-NA Panel cut-out (unit: mm)
48
4 48 Min. 60
21.5 +0.5
-0
Min. 37
32.4
21
24
45.5 +0.5
-0
M4YS-NA
Panel cut-out (unit: mm)
85 Min. 91
72 6 77
31.5 +0.5
-0
Min. 40
36
30
+0.7
68 - 0
L-6
Loop powered scaling meter
PEKH 2)00 0)00 Each peak value will be shown by pressing key in
monitoring mode and peak value will be initialized by (C)
RVN pressing key once more.
Door/Area
sensor
PEKL $00 0)00 If no key touched for 60sec., it will return to RUN mode.
(D)
Proximity
sensor
Run mode
(F)
key(3 sec.) Changing SV
Rotary
encoder
Display value for 4mA
Move the setting digit by key and change the Low limit value by key. (H)
Display value for 20mA Temp.
controller
H-SC 2000 2000 2000 2000
(I)
SSR/
Move the setting digit by key and change the High limit value by key. Power
controller
Decimal point
DOT 00.00 0.000 0000 000.0 (J)
Counter
Move the setting digit by key and change the High limit corrected value by key. (N)
Peak value monitoring delay time Display
unit
PEkT 00 5 01 5 30 5 (O)
Sensor
controller
Set peak value monitoring delay time. Setting range: 00 to 30 sec.
key: Setting the delay time, key: Set "00" sec. (P)
Display cycle Switching
mode power
(Q)
Stepper
5.0 5 4.0 5 motor&
Driver&Controller
Change the display cycle by or key. (R)
Set display range Graphic/
Logic
ePCT 3 4 0 1 panel
(S)
2 Field
network
device
1
Change HHHH/LLLL display value(%) by or key.
Lock setting (T)
Software
LOC OFF ON
(U)
Set the Lock in order to disable the Parameter setting by or key.
Other
Press key to complete the setting and move to next Parameter in status of changing setting value.
Press key is pressed for 3 sec. to move to RUN mode after displaying [ RVN]
If any key is untouched for 60 sec., it will return to RUN mode.
1: Lock setting OFF: Enable to change or set Parameter.
ON: Disable to change or set Parameter but enable to check the setting value in Parameter group.
Disable to enter into the status of change setting value by pressing , keys.
L-7
M4NS/M4YS
Display Display Display Display LLLL/ HHHH are displayed when it is over 2%
a b a b ePCT2 out DC4-20mA range
A Input A
A Input A Input
b value
value a value B LLLL/ HHHH are displayed when it is over 3%
B B B ePCT3 out DC4-20mA range
a b Input
value
L-SC/ H-SC are displayed always when it is out of
ePCT4
Decimal point setting[DOT] DC4-20mA range
This function is to set the decimal point position of display
value(Set in Parameter setting group) Error display
When [ LLLL]flashs,
Input current is lower than 3% in 4-20mADC (16mA
00)0 0)00 )000 0000 scale) LLLL will flash when it is under 3.52mA
[16mA3% =0.48mA] 4mA-0.48mA=3.52mA When it
Able to use (Shift) or (Up) for moving decimal. is beyond Min. display value(-1999) [by display value]
When [ HHHH] flashs,
Correction[ INB.H/ INB.L] Input current is higher than 3% in 4-20mADC(16mA
This function is to adjust the error of display value after scale) HHHH flash [16mA3%=0.48mA]
calculating scale value for measuring input and also correct 20mA+0.48mA= 20.48mA.
the input error of sensor etc. When it is higher than 20.48mA.
INbL:-100 to 100 [Adjust deviation of low value] When it is beyond Max. display value(9999)
INbH: 0.900 to 1.100 [Correct gradient(%) of high value] [by display value]
Ex)When display value is 0.0 to 500.0 against 4-20mA
input, if the display value is 1.2 for 4mA input, set -12 Turn Error display off
(Ignore the decimal point) as 1NB.L value to display 0.0.It LLLLand HHHH are displayed when input is out of measur-
is enable to remove offset of Low display value. ing range, therefore it will be disappeared automatically
When completed above Low value setting then apply when input returns to measuring range.
20mA, if the display value is 500.5, the correction value
will be 5005/5000=0.999, set 0.999 as 1NB.H value then Display peak value monitoring
enable to correct High value is 500050.999 = 5000).It is [PEKH / PEKL]
also ignore the decimal point. This function is to monitor Max. value and Min.value by cur-
rent display value then display its Data in PEkH mode and
PEkL mode.
Enable to set delay time in PEkT mode to protect the wrong
Data by initial over current and settable from 0 to 30sec.
and start to monitor after delay time.
L-8