General Integrated Production Control


System CENTUM VP
Specications System Overview (Vnet/IP Edition)
GS 33L01A10-40E

GENERAL
This document provides the overall system specications of the CENTUM VP Systems with Vnet/IP.

SYSTEM CONFIGURATION

Vnet/IP domain
Open
Enclosed ProSafe-RS
Display
Display Safety
Style PC for L3SW
Style HIS Instrumented
Console engineering Layer 3 switch
Console Human System
HIS (ENG)
SNTP HIS Interface Other
Server Station SENG
Vnet/IP
domains

L3SW
Layer 3 switch
Bus 1
Vnet/IP
Bus 2
SCS

V net router
FCS
(for FIO)
SIOS GSGW APCS
System Generic Advanced ESB bus
Other
Integration Subsystem Process
Other system V net
OPC Station Gateway Control
Local node domains
Station
Other
ER bus
PCS
(Subsystem)

Remote node

F01E.ai

Figure Example of System Conguration

Yokogawa Electric Corporation GS 33L01A10-40E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright Feb. 2008 (YK)
Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 12th Edition Apr. 1, 2013 (YK)
<<Contents>> <<Index>> 2
SYSTEM COMPONENTS Generic Subsystem Gateway Station
(GSGW)
Human Interface Station (HIS) A GSGW can collect and set data of various types of
An HIS serves as a human machine interface for subsystems through OPC DA servers. No dedicated
plant operators. Software packages are installed in a communication program is required.
general-purpose personal computer (an IBM PC/AT GSGW is a general-purpose PC with LFS1250 Generic
compatible computer, hereinafter referred to as a Subsystem Gateway Package.
general-purpose PC). The HIS PC can be assembled
For connections to the Vnet/IP, a VI702 Control Bus
in the console box.
Interface Card is required.
For connections to the Vnet/IP, a VI702 Control Bus
For more information, see GSGW Generic Subsystem
Interface Card is required.
Gateway Package (GS 33M20F10-40E).
For more information on HIS hardware requirements,
see the following General Specications: Safety Control Station (SCS)
Enclosed Display Style Console Assembly An SCS is a component of Safety Instrumented
(GS 33M50B40-40E) Systems (ProSafe-RS). ProSafe-RS has been
Open Display Style Console Assembly approved by German safety test labs TV (Technische
(GS 33M50B50-40E) berwachungs Verein) as the SIS (Safety Instrumented
Standard Operation and Monitoring Function System) that meets SIL (Safety Integrity Levels) 3
(GS 33M05D10-40E) established by IEC 61508.
Vnet/IP Interface Card (GS 33L50C10-40E)
The SCS for ProSafe-RS monitors the state of plants
PC for Engineering (ENG) and performs predetermined safety operation according
to each request for safety control.
This is a PC with engineering functions used to perform
CENTUM VP system generation and maintenance
management. Safety Engineering PC (SENG)
It can be the same type as the general-purpose PC for An SENG is a PC with engineering functions for
the HIS, and can even be the same PC as the HIS. ProSafe-RS such as editing, downloading and testing
applications as well as carrying out maintenance tasks
By having HIS operation and monitoring functions on on safety control stations (SCSs).
the same PC, you can execute virtual test (control
station emulation) functions to provide an efcient and The SENG functions can be installed in a PC that has
easy-to-use engineering environment. HIS or ENG functions.
For connections to the Vnet/IP, a VI702 Control Bus For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required. Interface Card is required.
For more information, see Safety Instrumented
Field Control Station (FCS) Systems ProSafe-RS System Overview (for Vnet/IP)
(GS 32R01B10-21E).
An FCS performs process control. Two types of eld
control stations are available:
System Integration OPC Station (SIOS)
AFV10S: Field Control Unit (for Vnet/IP, FIO, rack-
mounted) System Integration OPC Station (SIOS) is a station
AFV10D: Duplexed Field Control Unit (for Vnet/IP, used to integrate other venders PCS (Process Control
FIO, rack-mounted) System) to CENTUM VP system. SIOS enables HISs
One eld control station has 8 slots for I/O modules, to access the process data, alarms and events of other
and extra I/O expansion nodes can be also connected venders PCSs through OPC DA and AE.
via ESB bus or via ER bus. The SIOS is a general-purpose PC with LBC2100
For more information on the FCS hardware System Integration OPC Client Package.
requirements, see the following General Specications: For connections to the Vnet/IP, a VI702 Control Bus
Field Control Unit (for Vnet/IP and FIO) Interface Card is required.
(GS 33L50E20-40E) For more information, see System Integration OPC
ESB Bus Coupler Module (GS 33M50E25-40E) Client Package (GS 33M20D10-40E).
ER Bus Interface Master Module (for FIO)
(GS 33M50F25-40E) Advanced Process Control Station (APCS)
Node Units (for FIO) (GS 33M50F20-40E) An APCS advanced process control station implements
FIO System Overview (for AFV10) control functions with a general-purpose PC connected
(GS 33L50F10-40E) to a Vnet/IP, aimed at improving advanced control and
plant efciency. The APCS requires LFS 1200 APCS
Control Functions (GS 33M15U10-40E) to be installed.
For connections to the Vnet/IP, a VI702 Control Bus
Interface Card is required.
For more information, see APCS Control Functions
(GS 33M15U10-40E).

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Oct. 5, 2010-00
<<Contents>> <<Index>> 3
Vnet/IP Layer 3 Switch
Vnet/IP is the IEEE 802.3 compliant, dual-redundant This is the COTS switch with the routing function, and
high-speed (1Gbps) control network. All the can divide the Vnet/IP network into several domains.
components of the Vnet/IP network are connected to
the Layer 2 switches. Layer 2 switches are required V net Router
for each of the dual redundant networks. One of the
This is the equipment to connect a Vnet/IP system
dual-redundant networks (called Bus 1) is exclusively
and a V net system. This router enables the HIS of
used for process control communication. The other
both Vnet/IP and V net to operate the FCS of the other
(called Bus 2) is used not only for process control
systems.
communication redundant with Bus 1, but also for
the open communication with the generic Ethernet The following product is available.
protocol. AVR10D: Duplexed V net Router (for redundant use
Using Layer 3 switches, the Vnet/IP can be divided into of communications and power supply
several domains. VI702 the NIC (Network Interface modules)
Card) for Vnet/IP is required for each PC, which is For information on the hardware specications, see
connected to the Vnet/IP. Commercially available Duplexed V net Router (GS 33L50D30-40E).
products are used for all other network equipment such
as switches, LAN cables, or repeaters. SNTP Server
The time of all the components connected to the
Layer 2 Switch Vnet/IP network is synchronized. By connecting the
This is the COTS (Commercial off-the-shelf) switch COTS SNTP server on the Vnet/IP network, the time
equipment. At least two switches are mandatory for one of Vnet/IP components can be synchronized with UTC
Vnet/IP system. The transmission speed for Vnet/IP (Coordinated Universal Time).
has to be 1 Gbps.
Peripherals Device
Please use compatible models of the peripheral
devices, such as printers, which support the designated
Operation Systems. Consult with a Yokogawa
sales department for more information about those
compatible devices with HIS.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E June 1, 2010-00
<<Contents>> <<Index>> 4
SYSTEM SPECIFICATIONS Installing of Server PCs
Each number shown below includes the number of CS
Number of Tag 3000 PCs.
Up to 100,000 per system (when using LHS4000, up to CENTUM VP achieves many functions using le
1,000,000 per system) sharing function of Windows. The number of PCs to
share les simultaneously is restricted on the Windows
Minimum System Workstation OS. Therefore, when there are 9 or more
A minimum system consists of one HIS with stations (HIS, ENG, Exaopc) in one project, the PC with
engineering function and one FCS. a server OS may be required.
Please count the total station number in one project
Maximum System using the equations shown below in order to judge
whether server PC is required or not. If the number
64 components/domain
is eight or smaller, a server PC is not required. If the
16 domain/system number is larger than 8, consult with a Yokogawa sales
256 stations/system representative for further examination.
Components: In case of PCs storing master Engineering
Human Interface Station (HIS) database le
Field Control Station (FCS) When not using Engineering Tool for FOUNDATION
Advanced Process Control Station (APCS) eldbus (SSS5700)
Generic Subsystem Gateway (GSGW) Total station number =
System Integration OPC Station (SIOS) HIS + ((ENG - 1) x 2) + Exaopc
Safety Instrumented Systems (ProSafe-RS) When using Engineering Tool for FOUNDATION eldbus
OPC Interface Package (Exaopc) OPC server (SSS5700)
Field Communications Server for Plant Resource
Total station number =
Manager (PRM)
HIS + ((ENG - 1) x 2) + Exaopc + 2
V net Router (AVR10D)
On the bus 2, up to 124 general-use Ethernet devices
HIS : Number of PCs in which Standard
(including intelligent network devices) other than listed
Operation and Monitoring Function
above can be additionally connected.
(LHS1100 or LHM1101) is installed
ENG: Number of PCs in which Standard Builder
Expanded System Function (LHS5100 or LHM5100) is
The former systems than V net such as HF bus or RL installed.
bus can be connected on a Vnet/IP system through a Exaopc: Number of PCs with Exaopc Interface
bus converter on a V net. Package (NTPF100)
Vnet/IP domains and V net domains can be managed When using Multiple Project Connection Package
in the same project, or can be connected with a (LHS4450), see Multiple Project Connection Package
Multiple Project Connection Package. (GS 33M05K20-40E).
For more information, see Multiple Project Connection When using Expanded Test Function (LHS5425),
Package (GS 33M05K20-40E). a server PC is always required for storing master
Engineering database.
In case of PCs storing audit trail data
When using LHS5170 Access Administrator Package,
one PC which is dedicated for storing audit trail data
must be prepared. When there are 9 or more stations
(ENG, Recipe Management PC) in one project, the
server PC may be required for storing audit trail data.
Please count the total station number in one project
using the equations shown below in order to judge
whether server PC is required or not. If the number
is eight or smaller, a server PC is not required. If the
number is larger than 8, consult with a Yokogawa sales
representative for further examination.
Total station number = ENG + Recipe Management

ENG: Number of PCs in which Standard Builder


Function (LHS5100 or LHM5100) is
installed.
Recipe Management: Number of PCs in which CS
Batch 3000 Recipe Management package
(LHS5161) is installed

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E June 1, 2010-00
<<Contents>> <<Index>> 5
Vnet/IP NETWORK SPECIFICATIONS
The Vnet/IP is a real-time process control network used to connect system components. The Vnet/IP supports
two types of communications: control-bus communications and open communications. The Vnet/IP is always dual-
redundant. Usually, control bus communications are carried out via bus 1. Open communications are carried out via
bus 2. If a control communications error occurs on bus 1, control bus communications will be carried out via bus 2.
The Vnet/IP uses general-purpose communications devices for network connection.
Vnet/IP domain

HIS ENG
APCS GSGW A wide area connection
Exaopc via dedicated network is
available.
Max.7 levels
1000BASE-T for Layer 2
Max. 100 m Switch

Bus 1 Layer 3
V net router Switch
Layer 2 Switch
V net Vnet/IP Vnet/IP
domain Bus 2 domain domain
Layer 2 Switch
Layer 3
Switch
BCV

HF-bus FFCS-L
domain
F03E.ai

Figure Network Conguration

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Apr. 1, 2013-00
<<Contents>> <<Index>> 6
Communications Specications Required Network Equipment
Control communications
Specications
Communication Method: Read/write communication, Layer 2 switch
message communication, and inter- Connection Port: 1000BASE-T, full duplex
controller communication Connection between switches: 1000BASE-T,
Inter-Controller Communication Period: 100 msec 1000BASE-LX with speed, 1 Gbps (1.5
Open communications Mpps@64 byte) or faster, full duplex
Open communications are executed via bus 2. Auto-Negotiation: Mandatory
Commercially available Ethernet communications Layer 3 switch
devices can be connected. Connection Port: 1000BASE-T, full duplex
The total bandwidth that can be used for open Connection between switches: 1000BASE-T,
communications on bus 2 is up to 300 Mbps. 1000BASE-LX with speed, 1 Gbps (1.5
Transmission Path Specications Mpps@64 byte) or faster, full duplex
Network Topology: Star Topology Unicast dynamic routing protocol: RIPv2 (RIPv1
Transmission Path Redundancy: Available (control compatible mode is mandatory)
bus communications only)
Transmission Cable: Unshielded twisted pair (UTP) at Multicast Protocol:
enhanced category 5 or better. IGMP: Mandatory
DVMRP or PIM-DM: Mandatory
Cable Maximum
Connection Speed
Standard Distance
100BASE-TX 100 Mbps
Management function
Between (IEEE802.3u) (*1) SNMP
component and 100 m
1000BASE-T
a layer 2 switch
(IEEE802.3ab)
1 Gbps Address Reserved for Vnet/IP
1000BASE-T Class C private address is used for communications
1 Gbps 100 m for control and open communications.
Between layer 2 (IEEE802.3ab)
switches 1000BASE-LX For Yokogawa equipment supporting Vnet/IP, three
1 Gbps 5 km IP addressed are reserved: One for bus 1 control
(IEEE802.3z)
1000BASE-T
communication; one for bus 2 control communication;
Between a layer 2 1 Gbps 100 m one for bus 2 open communication.
(IEEE802.3ab)
switch and a layer Make sure that there are no overlaps in IP addresses.
3 switch 1000BASE-LX
(IEEE802.3z)
1 Gbps 5 km Communications for control
Bus 1: 192.168.(Domain No.).1 to 129 or 254
*1: For V net Router, SCS and Open communication Bus 2: 192.168.(128 + Domain No.).1 to 129 or
network. 254

Communications between Components The following addresses are reserved for multicast
Maximum distance between arbitrary stations: 40 km communications.
Only a couple of media converter between For stations within domains
components can be connected. Bus 1: 239.192.24.0
Bus 2: 239.192.24.1
For all domains
Bus 1: 239.192.24.4
Bus 2: 239.192.24.5

Class B address is reserved for the TCP/IP protocol


communications on Vnet/IP.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E July 1, 2008-00
<<Contents>> <<Index>> 7
I/O COMMUNICATIONS BUS
ESB Bus
Application
An ESB bus is an I/O communications bus that connects the processing unit of an FCS to the I/O expansion nodes.
The nodes connected on the ESB bus are named local node.
Communication Specications
Connectable Devices: Node units (ANB10S and ANB10D)
Number of Connectable Devices: The number of local node units that can be connected to an ESB bus varies
according to the database selected.
Maximum Number of Total Number of
Database
Local Nodes Local and Remote Nodes
Control Function for Standard Field Control Unit (*1) 3 3
Control Function for Standard Field Control Unit plus Application Capacity
9 14
Expansion Package (LFS1530)

*1: If local nodes are connected to an AFV10S or AFV10D FCU, ESB Bus Coupler Modules (EC401) have to be installed in
slots 7 and 8.
Transmission Path Specications
Network Topology: Bus topology
Transmission Path Redundancy: Available
Transmission Speed: 128 Mbps
Transmission Cable: Dedicated cable (YCB301)
Transmission Distance: 10 m max.

ER Bus
Application
An ER bus is a remote I/O communications bus to connect an FCU or local node unit to the I/O expansion nodes
remotely. The nodes connected on the ER bus are named remote node.
Communication Specications
Connectable Devices: Remote node units (ANR10S, ANR10D)
Number of ER buses: Max. 4 per FCU
Number of Connectable Devices: The number of remote node units that can be connected to an ER bus varies
according to the model and database selected.
Maximum Number of Total Number of
Database
Remote Nodes Local and Remote Nodes
Control Function for Standard Field Control Unit 3 3
Control Function for Standard Field Control Unit plus Application Capacity
14 (*1) 14
Expansion Package (LFS1530)

*1: Up to eight remote nodes per ER bus can be connected.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Mar. 14, 2008-00
<<Contents>> <<Index>> 8
Transmission Path Specications
Network Topology: Bus topology
Transmission Path Redundancy: Available
Transmission Speed: 10 Mbps
Transmission Cable: Coaxial cable (YCB141, YCB311). Use YCB147 ER-bus Adapter and YCB149 ER Bus
Converter Unit for connecting YCB141 and YCB311 cables.
One grounding unit (YCB117) per segment (*1) should be used when connecting YCB311 cable.
Transmission Distance:
YCB141: Max.185 m
When mixing YCB141 and YCB311:
Length of YCB141 + (185/500) x Length of YCB311 185
Number of Bus Adapter Units: Max. 4 per segment (*1)
General-purpose Ethernet Repeater:
The total transmission distance is limited by the number of repeaters.
L 4 - 0.5 n
L: total transmission distance (km)
n: the number of the general-purpose Ethernet repeater (Max. 4 repeaters)

*1: If repeaters are used on ER bus, each part of the ER bus segregated by a repeater is referred to as a segment.

EB401
AFV10D (Node1)

ER bus

EB501
ANR10D (Node2)

AFV10D EB401
(Node1)

Repeater Repeater

Optical Fiber Optical Fiber


Cable Cable
Repeater Repeater ER bus

EB501 EB501
ANR10D (Node3) ANR10D (Node2)

Repeater Repeater Repeater Repeater Repeater Repeater

Optical Fiber Optical Fiber Optical Fiber Optical Fiber Optical Fiber Optical Fiber
Cable Cable Cable Cable Cable Cable

Repeater Repeater Repeater Repeater Repeater Repeater

EB501 EB501 EB501


ANR10D (Node4) ANR10D (Node3) ANR10D (Node4)

F04.ai

Figure Example of ER Bus connection

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Feb. 1, 2009-00
<<Contents>> <<Index>> 9
SOFTWARE Standard FCS Software
LFS1500 Control Function for Standard Field
Operation and Monitoring Software Control Unit (for FIO, Vnet/IP)
LHS1100 Standard Operation and Monitoring LFS1530 Application Capacity Expansion Package
Function (for AFV10)
LHS1120 Console HIS Support Package for For more information, see Control Function for Basic
Enclosed Display Style Field Control Unit, Application Capacity Expansion
LHS1130 Console HIS Support Package for Open Package (GS 33L15C20-40E).
Display Style
LHS1150 Server for Remote Operation and Optional FCS Software
Monitoring Function LFS3132 Valve Pattern Monitor Package
LHS2411 Exaopc OPC Interface Package (for HIS) LFS8620 Off-site Block Package
LHS2412 CENTUM Data Access Library For more information, see the respective GSs.
LHS4000 Million Tag Handling Package
LHS4100 Congured Information Reference
Subsystem Communication Software
Package
LHS4150 Recorder Output Package For each subsystem, optional communications software
LHS4190 Line Printer Support Package is available.
LHS4200 Consolidated Historical Message Viewer LFS2410 FA-M3 Communication Package (for
(Meeting FDA) ALR111, ALR121)
LHS4410 Control Drawing Status Display Package LFS2420 YS Communication Package (for ALR121)
LHS4420 Logic Chart Status Display Package LFS2421 YS Communication Package with Direct
LHS4450 Multiple Project Connection Package Connection (for ALR121)
LHS4600 Multiple-monitor Package LFS2430 MELSEC Communication Package (for
LHS4700 Advanced Alarm Filter Package ALE111)
LHS6510 Long-term Data Archive Package LFS2431 FA-M3 Communication Package (for
LHS6530 Report Package ALE111)
LHS6660 Process Management Package LFS2432 DARWIN/DAQSTATION Communication
LHS6710 FCS Data Setting/Acquisition Package Package (for ALE111)
(PICOT) LFS2433 PLC-5/SLC500 Communication Package
For more information on the above functions, see the (for ALE111)
respective GSs. LFS2453 Modbus Communication Package (for
The following operating systems can be used on HIS ALE111)
which supports operation, monitoring, and engineering. LFS2456 SLC500 Communication Package (for
ALR111, ALR121)
Windows Vista Business Edition
LFS2457 PLC-5 Communication Package (for
Windows XP Professional Edition
ALR111, ALR121)
Windows Server 2003 Standard Edition
LFS2542 PROFIBUS Communication Package (for
Windows Server 2008 Standard Edition
ALP111)
As for Windows OS and Service Pack, see Standard
LFS2610 Foundation Fieldbus Communication
Operation and Monitoring Function (GS 33M05D10-
Package (for ALF111)
40E) and Standard Builder Function (GS 33M10D10-
LFS2710 HART Communication Package (for
40E).
AI-H)
If it is necessary to run other third-party software on LFS2753 YFGW Communication Package (for
the HIS, consult with a Yokogawa sales department to ALE111) (*1)
conrm that it is supported. LFS9153 Modbus Communication Package (for
ALR111, ALR121)
Engineering Software LFS9162 MELSEC-A Communication Package (for
LHS5100 Standard Builder Function ALR111, ALR121)
LHS5110 Access Control Package For more information, see the respective GSs.
LHS5150 Graphic Builder *1: Supported by R4.02.30 or later versions
LHS5165 Batch Builder
LHS5166 Recipe Management Package
LHS5170 Access Administrator Package (FDA: 21
CFR Part 11 compliant)
LHS5420 Test Function
LHS5425 Expanded Test Functions
LHS5426 FCS Simulator Package
LHS5427 HIS Simulator Package
LHS5450 Multiple Project Connection Builder
LHS5490 Self-documentation Package
LHS5800 Turbomachinery I/O Module Logic Builder
Package
For more information on the above functions, see the
respective GSs.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Oct. 5, 2010-00
<<Contents>> <<Index>> 10
Sequence of Events Manager Software INSTALLATION AND
LPC6900 SOE Server Package ENVIRONMENTAL CONDITIONS
LPC6910 SOE Server Congurator Package The installation and environmental conditions for
LPC6920 SOE Viewer Package Yokogawas components (not including the general-
LPC6930 SEM OPC Interface Package purpose PCs, General-Purpose Network Device,
For more information, see SEM Sequence of Events console HISs, node units for FIO and I/O modules) are
Manager (for FIO and Vnet/IP) (GS 33L30D10-40E). shown below.
For a general-purpose PC and Network equipment,
Documents
see their specications. For an Enclosed display style
LHS5495 Electronic Document console HIS, an Open display style console HIS, a
For more information, see Electronic Instruction node unit for FIO, or an I/O module, see the general
Manual (GS 33M01W10-40E). specications for each device (GS 33M50B40-40E, GS
33M50B50-40E or GS 33M50F10-40E).
Plant Resource Management Ambient Temperature:
SSS7700 Plant Resource Management Server 5 to 40 C (YAX101, YAX801)
SSS7710 Plant Resource Management Client 0 to 50 C (FCS)
SSS7720 Field Communications Server Ambient Humidity:
For more information, see Plant Resource Manager 20 to 80 %RH
(GS 33Y05Q10-32E). 10 to 90 %RH (FCS)
Non-condensation
Operation Support Software (for HIS) Temperature Change Rate:
NTPS100 Exaplog Event Analysis Package 10 C per hour
NTPS200 Exapilot Operation Efciency Power Requirements:
Improvement Package 100 to 120 V AC 10 %, 50 or 60 Hz
For more information, see NTPS100 Exaplog Event 3 Hz
Analysis Package (GS 36J06A10-01E) and NTPS200 220 to 240 V AC 10 %, 50 or 60 Hz 3
Exapilot Operation Efciency Improvement Package Hz
(GS 36J06B20-01E). 24 V DC 10 %
Withstanding Voltage:
1500 V AC for 1 minute (for 100-120 and
Safety Instrumented System 220-240 V AC model)
CHS5100 Safety System Generation and 500 V AC for 1 minute (for 24 V DC
Maintenance Package model)
CFS1100 Safety Control Functions Package Insulation Resistance:
For more information, see ProSafe-RS Safety 20 M at 500 V DC
Instrumented System Overview (for Vnet/IP) (GS 10 M at 500 V DC (YAX101, YAX801)
32S51B10-01E). Grounding:
Independent ground of up to 100
Noise:
Electric Field: Up to 3 V/m (26 MHz to 1.0 GHz)
Up to 3 V/m (1.4 to 2.0 GHz)
Up to 1 V/m (2.0 to 2.7 GHz)
Magnetic Field: Up to 30 A/m (AC), up to 400 A/m
(DC)
Static: Up to 4 kV (direct discharge), up to 8 kV
(aerial discharge)
Continuous Vibration:
Displacement amplitude: Up to 0.25 mm
(1 to 14 Hz)
Acceleration: Up to 2 m/s2 (14 to 100 Hz)

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Nov. 1, 2008-00
<<Contents>> <<Index>> 11
CENTUM VP Entry Class
The CENTUM VP Entry Class is available for small-scale systems. Up to 8000 tag names can be used in a CENTUM
VP Entry Class system.

Components and Software


The CENTUM VP Entry Class uses specic Entry Class packages such as built-in HIS packages. There is no
restriction on FCS models.

Operation and Monitoring Software


The following software packages are provided for the Entry Class. Except for the packages listed below, current
CENTUM VP system operation and monitoring software packages can be used. But, the LHS4000 Million Tag
Handling Package cannot be used in an HIS with the built-in LHM1101 Standard Operation and Monitoring Function.
Operation and Monitoring Software
Entry Class Model Product Remarks
LHM1101 Standard Operation and Monitoring Function Number of operation and monitoring tags : up to 8000
LHM1150 Server for Remote Operation and Monitoring Function
LHM4410 Control Drawing Status Display Package
LHM4420 Logic Chart Status Display Package
Process Management Package Maximum number of active recipes:
Type A: 4
LHM6660
Type B: 10
Type C: 999
LHM6710 FCS Data Setting/Acquisition Package (PICOT)

Engineering Software

Entry Class Model Product Remarks


LHM5100 Standard Builder Function
LHM5150 Test Function
LHM5490 Self-documentation Package

Restrictions
For CENTUM VP Entry Class, the following restrictions apply.
Only one domain per system
The HIS in a CENTUM VP Entry Class project cannot access the FCSs in other projects of CENTUM VP, CENTUM
VP Entry Class, CENTUM CS 3000 and CENTUM CS 3000 Entry Class.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Oct. 5, 2010-00
<<Contents>> <<Index>> 12
REGULATORY COMPLIANCE
CENTUM VP hardware components conform to the following standards. See the applicable general specications to
ensure each devices compliance.
Safety Standards (*1) (*2) Note: According to the New Approach Directive, the
[CSA] manufacturer and the representative ofce in EU
CAN/CSA-C22.2 No. 61010-1 are indicated below:
[CE Marking] Low Voltage Directive Manufacturer: Yokogawa Electric Corporation (2-
9-32 Nakacho, Musashino-shi, Tokyo 180-8750,
EN 61010-1 (*3) Japan).
EMC Conformity Standards (*2) Representative ofce in EU Community:
[CE Marking] EMC Directive Yokogawa Europe B.V. (Euroweg 2, 3825 HD
EN 55011 Class A Group 1 (*4) Amersfoort, The Netherlands).
EN 61000-6-2 (*5)
EN 61000-3-2 (*6) *1: For ensuring all the hardware devices to satisfy
the safety standards, the dedicated breakers in
EN 61000-3-3 (*7) the power supply distribution board must conform
[C-Tick Marking] to the following specications.
EN 55011 Class A Group 1 (*4) [CSA] CAN/CSA-C22.2 No.5 or UL 489
[KC Marking] [CE Marking] EN 60947-1 and EN 60947-3
Korea Electromagnetic Conformity Standard *2: To conform to safety standards and EMC
Standards for Hazardous Location Equipment conformity standards, install 19-inch rack-
mounted devices in a keyed metallic cabinet.
For selecting the right products for explosion protection,
*3: The analog input side of this equipment is
please refer to TI 33Q01J30-01E without fail. measurement category 1.
[CSA Non-Incendive] (*8) For details, see CENTUM VP Installation
Class I, Division 2, Groups A, B, C and D Guidance (TI 33L01J10-40E).
Temperature code T4 *4: A Class A hardware device is designed for use in
CAN/CSA-C22.2 No. 0-M91 the industrial environment.
CAN/CSA-C22.2 No. 0.4-04 Please use this device in the industrial
CAN/CSA-C22.2 No. 157-92 environment only.
*5: A lightning arrestor or its equivalent is required to
C22.2 No. 213-M1987
meet this surge immunity standard.
TN-078 The length of the cable to feed the external power
(for 100-120 V AC and 24 V DC power supply) supply for AGS813 AO channels should not
[FM Non-Incendive] (*9) exceed 30 meters.
Class I, Division 2, Groups A, B, C and D *6: An external device such as a power unit with
Temperature code T4 harmonic current neutralizer and an active
Class 3600: 1998 harmonics conditioner must be connected to meet
Class 3611: 2004 this harmonic current emission standard.
Class 3810: 2005 *7: The specied limits of voltage drops across wiring
must be satised to meet this standard.
(for 100-120 V AC, 220-240 V AC and 24 V DC
*8: To meet the standard for hazardous location
power supply) equipment, 19-inch rack-mounted devices must
[Type n] (*10) be installed in a keyed metallic cabinet approved
II 3 G Ex nA IIC T4 Gc (*11) by CSA or non-incendive regulator in your area.
II 3 G Ex nA nC IIC T4 Gc (*12) *9: To meet the standard for hazardous location
EN 60079-0:2009 equipment, 19-inch rack-mounted devices must
EN 60079-0:2012 be installed in a keyed metallic cabinet approved
EN 60079-15:2010 by FM or non-incendive regulator in your area.
(for 24V DC power supply) *10: To be compatible with Type n, for example the
requirements of cabinet must be met. For details,
II 3G EEx nA II T4
refer to the Explosion Protection (TI 33Q01J30-
EN 50021: 1999 01E).
(I/O Module with built-in barrier, for 24 V DC power *11: Applied for products complied with Type n, except
supply) for AFV10S, AFV10D and ADR541.
[Type i (Intrinsic Safety)] *12: Applied for the below products.
II (1) G D [EEx ia] II C AFV10S, AFV10D and ADR541
EN 50014: 1997 +A1 +A2
EN 50020: 1994
[FM Intrinsic Safety]
Associated intrinsically safe apparatus for
connection to
Class I, II and III, Division 1, Groups A, B, C, D, E,
F and G or
Class I, Zone 0, Group II C
Class 3600: 1998
Class 3610: 2010
ANSI/ISA-60079-0: 2009
ANSI/ISA-60079-11: 2009

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Apr. 1, 2013-00
<<Contents>> <<Index>> 13
TRADEMARKS
CENTUM, Vnet/IP, DARWIN, DAQSTATION ProSafe and Exaopc are registered trademarks of Yokogawa Electric
Corporation.
Exaplog and Exapilot are trademarks of Yokogawa Electric Corporation.
Windows is a registered trademark of Microsoft Corporation in the United States and/or other countries.
Ethernet is a registered trademark of XEROX Corporation.
Modbus is a registered trademark of Schneider Electric and/or such related companies.
PLC, PLC-5 and SLC500 are trademarks or registered trademarks of Rockwell Automation, Inc.
MELSEC and MELSEC-A are registered trademarks of Mitsubishi Electric Corporation.
SYSMAC is a registered trademark of Omron Corporation.
FOUNDATION of FOUNDATION eldbus is a registered trademark of Fieldbus Foundation.
Other product and company names appearing in this document are trademarks or registered trademarks of their
respective holders.

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation GS 33L01A10-40E Apr. 1, 2013-00
Subject to change without notice.