Académique Documents
Professionnel Documents
Culture Documents
InteliMains
Mains supervision controller
User guide
Features and specification in this manual are subject to change without prior notice.
Because of large variety of InteliMains parameters settings, it is not possible to describe any combination.
Some InteliGen / InteliSys / InteliMains function are subject of changes depend on SW version.
The data in this manual only describes the product and are not warranty of performance or characteristic.
Text
PAGE (Capital letters in the frame) buttons on the controller front panel
Break Return (Italic) set points
Generator protections (Bold) Set point group
REMOTE START/STOP (Capital letters) binary inputs and outputs
Conformity declaration
Following described machine complies with the appropriate basic safety and health
requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
The following instructions are for qualified personnel only. To avoid personal injury
do not perform any action not specified in this User guide !!!
Application archives
Application archive Description
IM-6.1.aig InteliMains standard up to 7000V Ph-N
IM+IOM-6.1.aig InteliMains standard with IG-IOM or IGS-PTM
Compatibility table
IM version IG version IS version
5.0 5.5 and lower 2.6 and lower
5.1 and higher 5.6 and higher 2.7 and higher
Hint:
The gen-set group requested power value distribution via CAN feature only available if IM-6.1 + IS-3.3 SW
versions used.
Grounding Terminal
BI1
BI5
BI6
BI7
BI8
BI9
L1k
L2k
L3k
L1
L2
L3
BI2
BI3
BI4
L1
L2
L3
L1l
L2l
L3l
LB 4
iM-CU
EXTENSION MODULE
EXTENSION MODULES
iG-COM / iG-IOM
iM-PCLSM
RS 232
BOOT JUMPER
BO2
+ -
COM
BO3
BO4
BO5
BO6
BO7
BO8
BO9
AI1
AI2
AI3
IM-PCLSM Terminals
LB 5
+ -
BO10
BO12
BO13
BO11
BI10
BI12
BI13
BI11
LB 4
CAN 2 EXTENSION MODULE CAN 1
CAN R 120
IGS-PTM can be connected to IG-CU, IM-CU or IS-CU. Detail description see in IGS-PTM manual.
AI4
C OM
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
iG-IOM
IG -C U
RS232
8-36V DC
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
Dimensions
AI4
COM
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
BINARY INPUTS ANALOG INPUTS ANALOG OUT
96 mm (3,8)
iG-IOM
IG-CU
RS232
BINARY OUTPUTS POWER
8-36V DC
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
95 mm 43 mm
(3,7) (1,7)
IGS-PTM
AO+
GND
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
AI4
AO-
0-20 mA
BINARY INPUTS ANALOG INPUTS ANALOG OUT
COMPENSATION
96 mm (3,8)
Rx
iGS-PTM
H COM L
CAN
CAN
Tx
LB 4
8-36V DC
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
95 mm 43 mm
(3,7) (1,7)
LB 3
95 (3,74")
iG-MTU
N L1 L2 L3
155(6,10") 60 (2,36")
Hint:
IG-MTU-C phase shift is 3. Use two IG-MTU-C units for both generator and bus voltage measuring or set
Sync/Load ctrl: GtoB angle Req setpoint.
IG-MTU and IG-MTU-C units are the same dimension and DIN 35 mm rail mounted.
ETHERNET LB 5
RJ 45
1 2
96 mm (3,8)
MODEM / IB CONFIG
iG-IB
IG-CU / DONGLE
3 4 5 6
95 mm 43 mm
(3,7) (1,7)
106 (4,2)
120 (4,7)
125 (4,9)
~ 25 (1,0)
165 (6,5)
~ 75 (3,0)
~ 35 (1,4)
38 (1,5)
40 (1,6)
180 (7,1)
185 (7,3)
DISABLE
SYNC
MCB
+24V
Ko1
MCB
iG-COM
CLOSE/O PEN
Ko2 iM-CU
MAINS FAIL
LOAD
CAN
3xU B
3xU M
3xIM
CAN
MCB 3x
GCB1
3x 3x
G1
iG-AVRi
TRANS
CAN
3xU B
3xU G
3xI G
Ko1
AVR
iG -AVRi
iG -PCLSM
MCB iG-CU AVRi AVRi
iG-COM
O UT
or
iS-CU+
iS-PCLSM -PM S LSM
Vout SPEED
GOVERNOR
SYS START/STOP
MASTER SELECT LO AD SHARING LINE
MCB FEEDBACK
GCB2 3x
MASTER SELECTOR
G2
iG-AVRi
TRANS
CAN
3xU G
3xU B
3xIG
AVR
iG-PCLSM iG-AVRi
iG-CU AVRi
AVRi
OUT
iG-CO M
PARALL.
or
TO M AINS
REQ UIRED iS-CU+
iS-PCLSM -PM S Vout SPEED
LSM
MCB GOVERNOR
Ko2
SYS START/STO P
MASTER SELECT
MCB FEEDBACK
MCB
Specification
Synchronize gen-sets to mains
Base load power control
Automatic start-up when mains fails
After mains returns GCBs opening (BI SYNC DISABLE is closed), reclosing MCB and synchronizing
gen-sets to mains
Gen-sets unload
Power management (if IG-COMs are installed)
Description
1) InteliMains opens MCB after the mains fails.
2) At the same time the IM binary output MAINS FAIL starts Power management by closing of SYS
START/STOP input, if the gen-sets had not run before.
3) When the mains returns, SYS START/STOP input opens and then GCBs open.
4) InteliMains detects no voltage and with its time delay MCB close del closes MCB.
5) If the switch Parallel to mains required is closed, gen-sets are synchronized again to the bus.
6) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
7) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
8) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Setpoint #SysAMFstrtDel is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint #SysAMFstpDel is not used in this case.
FEEDBACK
DISABLE
SYNC
MCB
+24V
Ko1
iM-PCLSM
LSM
MCB
iG-COM
CLOSE/OPEN
iM-CU
LOAD
CAN
3xUM
3xUB
3xIM
CAN
3x
MCB
3x 3x
GCB1
G1
iG-AVRi
TRANS AVR
3xU B
CAN
3xUG
3xIG
Ko1
iG-AVRi
iG-PCLSM
AVR
MCB iG-CU AVRi
iG-COM
i OUT
or
iS-CU
iS-PCLSM-PMS LSM
Vout SPEED
GOVERNOR
SYS START/STOP
MASTER SELECT LOAD SHARING LINE
MCB FEEDBACK
GCB2 3x
MASTER SELECTOR
G2
iG-AVRi
TRANS
CAN AVR
3xUG
3xUB
3xIG
iG-AVRi
iG-PCLSM
AVR
iG-CU AVRi i
iG-COM
OUT
PARALL.
TO MAINS or
REQUIRED iS-CU
iS-PCLSM-PMS LSM
Vout SPEED
GOVERNOR
MCB SYS START/STOP
MASTER SELECT
MCB FEEDBACK
MCB
Specification
Synchronizes gen-sets to mains
Import-Export or Base load power control
Uninterruptible stand-by
After mains returns MCB synchronizing
Automatic stand-by with Short time parallel to mains
Gen-sets soft unload
Power management
Description
1) The system is started by MCB opening or by the switch Parallel to mains required.
2) The IM-CU opens MCB after the mains fails. At the same time the MCB aux contact starts sequencing
by closing of SYS START/STOP input, if the gen-sets had not run before.
3) When the mains returns, IM-PCLSM synchronizer synchronizes gen-sets to the mains.
4) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
5) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
6) MASTER SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hints
Setpoint #SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint #SysAMFstp del is not used in this case.
FEEDBACK
DISABLE
LOAD SHARING LINE
SYNC
MCB
+24V
Ko1
iM-PCLSM
LSM
MCB
iG-COM
CLOSE/OPEN
iM-CU
LOAD
3xUM
3xU B
3xI M
CAN
MCB
3x 3x 3x
GCB1 3x
G1
iG-AVRi
TRANS AVR
CAN
3xUG
3xUB
3xIG
Ko1
iG-AVRi
iG-PCLSM
MCB iG-CU AVRi
AVRi
iG-COM
OUT
or
iS-CU+
iS-PCLSM-PMS LSM
Vout SPEED
GOVERNOR
SYS START/STOP
MASTER SELECT LOAD SHARING LINE
MCB FEEDBACK
GCB2 3x
MASTER SELECTOR
G2
iG-AVRi
TRANS
AVR
3xUB
3xUG
3xIG
CAN
iG-AVRi
iG-PCLSM
iG-CU AVRi AVRi
iG-COM
OUT
or
iS-CU+
iS-PCLSM-PMS LSM
Vout SPEED
GOVERNOR
MCB SYS START/STOP
MASTER SELECT
MCB FEEDBACK
MCB
FEEDBACK
DISABLE
SYNC
MCB
+24V
Ko1
iM-PCLSM
LSM
MCB
iG-COM
CLOSE/OPEN
Ko2 iM-CU
MGCB
CLOSE/OPEN
LOAD
CAN
3xUM
3xUB
3xIM
CAN
MCB 3x MGCB
3x 3x
GCB1
G1
iG-AVRi
TRANS
+24V
3xU B
CAN
3xUG
3xIG
Ko1
AVR
Ko2 iG-AVRi
iG-PCLSM
AVR
MCB MGCB iG-CU AVRi i
iG-COM
OUT
or
iS-CU +
iS-PCLSM-PMS LSM
Vout SPEED
GOVERNOR
SYS START/STOP
MASTER SELECT LOAD SHARING LINE
MCB FEEDBACK
GCB2 3x
MASTER SELECTOR
G2
iG-AVRi
TRANS
CAN
3xUG
3xUB
3xIG
AVR
iG-AVRi
iG-PCLSM
AVR
iG-CU AVRi i OUT
iG-COM
PARALL.
TO MAINS or
REQUIRED iS-CU +
iS-PCLSM-PMS LSM
Vout SPEED
GOVERNOR
MCB SYS START/STOP
MASTER SELECT
MCB FEEDBACK
MCB ...\IM_MCB.VSD
Specification
Automatic start-up when mains fails
After mains returns MCB synchronizing
One interrupt only stand-by
MGCB support
Gen-sets unload
Power management (if IG-COMs are installed)
Hints
Setpoint #SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint #SysAMFstp del is not used in this case.
0V
FEEDBACK
LOAD SHARING LINE
DISABLE
SYNC
MCB
+24V
Ko1
iM-PCLSM
LSM
MCB
iG-COM
CLOSE/O PEN
Ko10
MAINS PW R
iM-CU
O UT
LOAD
3xU M
3xU B
3xI M
CAN
MCB
3x 3x 3x GCB1 3x
G1
iG-AVRi
TRANS
3xU G
CAN
3xU B
3xI G
Ko1 AVR
iG-AVRi
iG-PCLSM
AVRi
MCB iG-CU AVRi O UT
iG-COM
or
iS-CU+
iS-PCLSM -PM S LSM
Vout SPEED
GOVERNOR
SYS START/STOP
MASTER SELECT LO AD SHARING LINE
MCB FEEDBACK
GCB2 3x
MASTER SELECTOR
G2
iG-AVRi
TRANS
3xU B
3xU G
3xI G
CAN
iG-AVRi AVR
iG-PCLSM
AVRi
iG-CU AVRi
O UT
iG-COM
or
Ko10
iS-CU+
iS-PCLSM -PM S LSM
Vout SPEED
GOVERNOR
MCB SYS START/STOP
MASTER SELECT
MCB FEEDBACK
MCB
Specification
Peak shaving
Synchronize gen-sets to mains
Import-Export or Base load power control
Uninterruptible stand-by
After mains returns MCB synchronizing
Automatic stand-by with Short time parallel to mains
Gen-sets unload
Power management
Hints
Setpoint #SysAMFstrtDel is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint #SysAMFstpDel is not used in this case.
Power supply
To ensure proper function:
Use min. power supply cable 2,5mm2
Hint:
Max current of power minus terminal is 4A and it depends on binary outputs load.
+
- iM-CU
+ iM-PCLSM
-
+ - HUGE
LOADS
Battery STARTER
Grounding
To ensure proper function:
Use as short as possible cable to the grounding point on the switchboard
Use cable min. 2,5mm2
The - terminal of the battery has to be properly grounded
As short
as possible
T1 T2
100V
100V
0V
0V
CURRENT TERMINALS
L2
L1
L3
N
VOLTAGE TERMINALS
L1 MAINS BUS L1
L2 L2
L3 L3
400V
400V
400V
0V
0V
400V
400V
400V
0V
0V
0V
0V
T1 T2 T3 T1 T2 T3
400V
400V
400V
400V
0V
0V
0V
400V
400V
0V
0V
0V
IG-MTU IG-MTU
L2
L1
L3
N
L1
L2
L3
MAINS BUS
VOLTAGE VOLTAGE
IM-CU
Connect one IG-MTU (or MTU-C) unit for separation of mains and bus voltage from controller when is 3wire
mains and 4wire bus or 4wire mains and bus but separated neutral.
L1 MAINS BUS L1
L2 L2
L3 L3
N N
400V
400V
400V
0V
0V
0V
T1 T2 T3
400V
400V
400V
0V
0V
0V
IG-MTU
L2
L1
L3
N
L1
L2
L3
MAINS BUS
VOLTAGE VOLTAGE
IM-CU
Alarm activity Alarm All the time Alarm is active all the time
activity
Sensor characteristic Sensor None unused analog input
Curve A User curve A
Curve B User curve B
Curve C User curve C
PT100PTM For IGS-PTM
PT 1000 IEC 751, range -20 to 120 C
NI100PTM For IGS-PTM
NI 1000 DIN 43760, range -20 to 120 C
VDO Temp See chapter sensor
VDO Press specificationPredefined
VDO Level characteristics
4-20mA/100 external R=120
4-20mA/ 60 external R=120
0-20mA/100PTM For IGS-PTM
4-20mA/100PTM For IGS-PTM
100mV/100PTM For IGS-PTM
Active Active Over Alarm active when over limit
Under Alarm active when under limit
Decimal points Dec 0, 1, 2 Number of decimal points
Measurement type Meas type Resistance Jumper on pins 1,2
Current(linear) Jumper on pins 2,3
Each Analog input has separate setpoint for one level alarm setting. Analog input alarm levels Anl Inp level
and delay Anl Inp del in Protections group.
BI1
BI6
BI7
BI8
BI9
BI4
BI5
BI2
BI3
L1k
L2k
L3k
L1
L2
L3
L1
L2
L3
L1l
L2l
L3l
N
GENERATOR CURRENT GENERATOR VOLTAGE BINARY INPUTS
0-5A 3 x 230 / 400 V
LB 5
iG-CU
EXTENSION MODULES
iG-PCM / iG-PCLSM
EXTENSION MODULES
iG-COM / iG-IOM
RS 232
BOOT JUMPER
(START)
Ink CURRENT
Inl In (Im L3)
(FUEL)
8 - 36 V DC
BO1
BO2
AI2 (TEMP)
AI3 (FUEL)
RPM GND
AI1 (OIL)
RPM IN
+ -
COM
BO3
BO4
BO5
BO6
BO7
BO8
BO9
RPM Grounding Terminal
Jumpers setting
Resistance
3 measurement
2 3
jumper on
1 2
pins 1-2.
AI1
AI2
AI3
1 Default
settings.
3 Current
measurement
2
jumper on
1 pins 2-3.
3 Voltage
measurement
2
no jumper
1 connected.
4-20mA/600 4-20mA/1000
No. Primary Converted No. Primary Converted
1 400 0 1 400 0
2 2000 600 2 2000 1000
0 to 4VDC measuring
Default characteristics Customer characteristics
A,B,C example
No analog input jumper =
Default characteristics
Following table describes how to use default characteristics.
IG-CU IGS-PTM
WinEdit cfg: WinEdit cfg:
Sensor Jumper on Meas type= Jumper on Meas type =
PT100/C 1-2, Resistance Resistance
Not possible on IM-CU
NI 100/C
PT1000/C Resistance Resistance
NI 1000/C Pins 1-2
VDO Temp Resistance Resistance
VDO Press Pins 1-2 Not possible on IGS-PTM
VDO Level
0-20mA/100 Current (linear) Current (linear)
4-20mA/100 Pins 2-3
0-20mA/100-PTM Pins 2-3, Resistance
4-20mA/100-PTM Current
Not possible on IM-CU
100mV/100-PTM No jumper, Resistance
Voltage
Hint:
External resistors 120 ohm for 20mA current measuring are not needed for IG hardware version 5 and above
when analog input jumper is set to 2-3.
Hardware connection
Connection of IM-CU analog inputs
- POWER
AI3
AI1
AI2
3x RESISTIVE
SENSOR
COM
AI3
AI1
AI2
Example of connection of two wire sensors.
3x RESISTIVE
SENSOR
- POWER
IG-CU
- POWER
+24V
AI1 CURRENT SENSOR
AI2 RESISTIVE SENSOR
AI3 BINARY INPUT
IG-CU
- PO W ER
Some types of transducers are not suitable for connection to InteliMains analog inputs because of
influencing by InteliMains analog input. In this case change default 4-20mA/60 or 4-20mA/100 sensor
characteristic to get proper reading.
Binary input
Open, close state is detected, threshold level is 750 .
Abbr: Abbreviation is used in history record for column labelling. Maximal length is 4characters (e.g. Oil
Pressure OilP or OPr).
Set to: OilP
Dim: Physical dimension of measured value (C, %, Bar, ..) Maximal dimension length is three characters.
Set to: Bar
Inverted: selection of polarity only when is analog input configured as Binary or Tri-state. When is analog
input configured as analog this setting has no sense.
Open to activate polarity of binary or tri-state input
Close to activate polarity of binary or tri-state input
When Analog input configuration is finished set the setpoints Anl Inp level1, Anl Inp del in Protections
group.
Each Analog input has separate setpoints: Anl Inp level1, Anl Inp del. Names of these setpoints are fix
defined do not depend on the name of measured value which can be changed.
Number of decimal points of Anl Inp level1 is the same as the configured number of decimal points of
measured value.
Binary inputs
4k7
iM-CU
+ -
Power
Supply
T1A + -
24VDC Battery
Binary outputs
LOAD
iM-CU
+ -
Power
Supply
T1A + -
24VDC Battery
Fuse
K1 K1 K2
K2
IM controller
T1A
+
-
DC relays
- +
24VDC Battery
120
There is different wiring of IG-COM CAN
connectors from hardware version 4.0
H L
COM COM Green CAN connectors are separated:
L H
CAN 1 EXTENSION MODULE CAN 2
CAN1 = for extension modules
- IG-IOM, IGS-PTM, IGL-RA15,
- connection to Extension module 9 pin
connector:
CAN H = pin 5
H L CAN L = pin 9
COM COM
L H CAN2 = inter-controller CAN,
CAN 1 EXTENSION MODULE CAN 2 - galvanically separated
- internal resistor 120 ohm via jumper
iG-MU
ETHERNET LB 4
RJ 45 No internal resistor 120 ohm available on
1 2
IG-IB.
MODEM / IB CONFIG
IG-CU / DONGLE
iG-IB
3 4 5 6
120
Hint:
For CAN cables details see chapter Technical data Communication interface.
CAN bus have to be to line connected, both end by the 120 ohm resistor terminated.
For longer distances is recommended to connect COM terminals between IG-COM units.
IM-IM+IOM-6.1.pdf
CAN EXTENSION MODULE CAN
H L
COM COM
L H
CAN EXTENSION MODULE CAN
Note that Binary inputs and outputs configured on IM-CU (and IM-PC(LS)M ) have much faster response
against IG-IOM. It is recommended to configure function inputs like Emergency stop, GCB feedback, MCB
feedback and others exclusively to IS-CU.
Binary inputs IM-CU default
BI1 MCB FEEDBACK
BI2 LOAD RESERVE 2
BI3 LOAD RESERVE 3
BI4 REMOTE OFF
BI5 ALARM
If the input is closed, warning is activated.
BI6 ALARM
If the input is closed, warning is activated.
BI7 ALARM
If the input is closed, warning is activated.
BI11 ALARM
If the input is closed, warning is activated.
BI12 ALARM
If the input is closed, warning is activated.
BI13 ALARM
If the input is closed, warning is activated.
Hint:
Use WinEdit to configure required type of alarms.
Not used
Binary input has no function. Use this configuration when Binary input is not connected.
MCB feedback
This input indicates, whether the gen-sets group operates in parallel to mains (MCB FEEDBACK is closed)
or parallel isolated (MCB FEEDBACK is open) .
Load reserve 2
If the input LOAD RESERVE 2 is closed the InteliGen / InteliSys controllers MINT (or MEXT) setpoints Pwr
management: #LoadRes strt 2 and #LoadRes stp 2 will be selected.
Load reserve 3
If the input LOAD RESERVE 3 is closed the InteliGen / InteliSys controllers MINT (or MEXT) setpoints Pwr
management: #LoadRes strt 3 and #LoadRes stp 3 will be selected.
Load reserve 4
If the input LOAD RESERVE 4 is closed the InteliGen / InteliSys controllers MINT (or MEXT) setpoints Pwr
management: #LoadRes strt 4 and #LoadRes stp 4 will be selected.
Hint:
When more than one Load reserve binary input is closed, the higher number has higher priority.
MinRun power 1
MinRun power 2
MinRun power 3
If the input MinRun power 1 or 2 or 3 is closed the InteliGen / InteliSys controllers MINT (or MEXT) setpoints
Pwr management: #MinRun power 1 or 2 or 3 is selected. When not configured or not active, minimal
running power is 0.
Hint:
When more than one MinRun power binary input is closed, the higher number has higher priority.
Sync disable
MCB synchronizing is blocked when input is closed.
FaultResButton
Binary input has the same function as Fault reset button on the InteliMains front panel.
HornResButton
Binary input has the same function as Horn reset button on the InteliMains front panel.
MCBButton
Binary input has the same function as MCB button on the InteliMains front panel. It is active in MAN mode
only.
MGCBButton
Binary input for MGCB manual control, active in MAN mode only.
TestOnLoad
When Binary Input TestOnLoad is closed InteliMains transfers Load from mains to generators and opens
MCB (even if Mains is OK) see chapter Function description.
Access lock
If the input is closed, no setpoints can be adjusted from controller front panel and controller mode OFF-MAN-
AUT cannot be changed.
Hint:
Access lock does not protect setpoints and mode changing from WinEdit. To avoid unqualified changes of
selected setpoints, use password protection.
Remote MAN
When is closed InteliMains switches to MAN mode. When opened controller is switched back to previous
mode.
Ext MF relay
If the input is active, the mains is evaluated as failed even if the voltage/frequency at the InteliMains voltage
terminals is within limits.
Input should be configured, if external MF relay is used for detection of Mains failure.
MCB close/open
The output controls the mains circuit breaker.
Hint:
When InteliMains is switched off, the output is open, see set point MCB logic (CLOSE-ON / CLOSE-OFF) [-
]in Mains protect group. Supposed time to close (reaction time) of MCB is 0,1 sec.
MCB ON coil
Pulse output for MCB closing.
MCB UV coil
MCB undervoltage coil.
Hint:
In MAN mode the outputs for MCB control work regardless of the feedback, i.e. it is possible to close MCB
even if the feedback is closed to confirm its real state and then reset the alarm.
Sys res1 OK
The output closes when the system load reserve LoadRes strt 1 is achieved.
PBNom > PAkt + LoadRes strt 1
PBNom Sum of the nominal power of all running gen-sets on the bus
PAkt System load sum of actual load of running gen-sets
Sys res2 OK
The output closes when the system load reserve LoadRes strt 2 is achieved.
PBNom > PAkt + LoadRes strt 2
Hint:
LoadRes strt 2 is selected when binary input LD Res 2 is closed.
Sys res3 OK
The output closes when the system load reserve LoadRes strt 3 is achieved.
PBNom > PAkt + LoadRes strt 3
Hint:
LoadRes strt 3 is selected when binary input LD Res 3 is closed.
Sys res4 OK
The output closes when the system load reserve LoadRes strt 4 is achieved.
PBNom > PAkt + LoadRes strt 4
Hint:
LoadRes strt 4 is selected when binary input LD Res 4 is closed.
Sys res OK
The output closes when selected system load reserve is achieved.
PBNom > PAkt + Reserve
PBNom Sum of the nominal power of all gen-sets on the bus
Hints
Gen-sets have to be included in Power management by closing of input SYS START/STOP.
Gen-sets have to be in AUT mode.
Synchronise
The output closes when InteliMains controller synchronizes gen-set group to mains and opens after MCB is
closed.
Mns/AnExPwrOut
Output closes when Mains power exceeds setpoint Process control: Mns/AnExt ON for Mns/AnExONdel
and opens when Mains power falls below Mns/AnExt OFF for Mns/AnExOFFdel.
Mns/AnExPwrOut output behaves according to selection by ProcessControl:LS/BldCtrlType setpoint:
Hint:
Use binary output Mns/AnExPwrOut for Peak shaving function to start gen-sets group when mains power
exceeds adjusted level Mns/AnExt ON .
Mains
import
Mns/AnExt ON
Mns/AnExt OFF
Mns/AnExPwrOut
t
Mns/AnExON del Mns/AnExOFF del Mns/AnExON del
Mns/AnExt OFF
Mns/AnExt ON
Mns/AnExPwrOut
t
Mns/AnExOFF del Mns/AnExON del Mns/AnExOFF del
Hint:
If ProcessControl:#SysLdCtrlPtM = LDSHARING, the requested gen-set group power is
distributed via Load sharing line. If ProcessControl:#SysLdCtrlPtM = BASELOAD, the requested
gen-set group power is distributed via CAN bus line (substitution for #SysBaseload setpoint).
This feature only available in cooperation with IS-3.3 and higher SW.
Alarm
The output closes if any alarm comes up. The output opens if FAULT RESET is pressed.
The output closes again if a new fault comes up. Alarm management
Horn
The output closes if any alarm comes up.
The output opens if:
FAULT RESET is pressed or
HORN RESET is pressed or
Max time of HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Bus fail
The output closes if the bus over/under voltage or voltage asymmetry or over/under frequency is detected.
Bus fail = Vb fail or fb fail. The output opens, when bus params are within limits again.
Vb fail
The output closes if the bus over/under voltage or voltage asymmetry is detected. The output opens, when
bus voltage is within its limits again.
fb fail
The output closes if the bus over/under frequency is detected. The output opens, when bus frequency is
within its limits again.
Mains OK
Binary output closes MainsReturn del [s] delayed after mains return. Opens with delay corresponding to
over/under voltage/frequency alarms when mains goes out of limits.
Vm fail
The output closes if the mains over/under voltage or voltage asymmetry is detected. The output opens, when
mains voltage is within its limits again.
fm fail
The output closes if the mains over/under frequency is detected. The output opens, when mains frequency is
within its limits again.
MainsOverCurr
The output closes if the mains IDMT over current or mains short current or mains current unbalance alarm is
activated.
The output opens, if
alarm is not active and
FAULT RESET is pressed
BattVolts
Output closes when battery over/under voltage warning appears.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Com Warn
Output closes when any warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Com Warn BI
Output closes when any Binary Input warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Com WR HST
Output closes when any history record caused by closing or opening of binary input (with Alarm type
configured to WrHstActOnly, WrHstActOnly+C, WriteHistory or WriteHistory+C) appears.
The output opens, if
FAULT RESET is pressed.
Common Fls
Output closes when any sensor fail alarm appears.
The output opens, if
No sensor fail alarm is active and
FAULT RESET is pressed
LoadShedding 1 (2, 3)
Output closes when gen-set power exceeds Ld shed level [%] limit for LD Shed del time.
Output opens automatically when setpoint AutoLd recon (DISABLED / ENABLED) [-] = ENABLED or
manually by rising edge of Binary input Man load recon. One edge moves only by one stage.
Principle of Load shedding is described in the chapter Function description Load shedding
MAN mode
The output is closed, if MAN mode is selected.
AUT mode
The output is closed, if AUT mode is selected.
MGCB ON coil
Pulse output for MGCB closing. MGCB has the same pulses timing like MCB control.
MGCB UV coil
MGCB under voltage coil.
Hint:
MGCB control description see in chapter function description.
MGCB close/open
MGCB ON coil
MGCB UV coil
1s 2s 2s 1s
Object Pwr Out
Output closes when Object power exceeds setpoint Process control: Object ON Pwr [ kW ] for Object ON
del and opens when Mains power falls below Object OFF Pwr [ kW ] for Object OFF del.
Bus OK
The output is a copy of Bus status LED on InteliMains front panel. The output is closed if bus voltage is
present and within limits.
Mains RevPower
The output closes if the mains reverse power protection is activated.
MCB fail
Output closes if MCB fail alarm is active.
GCB blocking output closes after mains failure and opens 2 seconds after MCB feedback deactivates.
Mains OK
Mains fail
BO MCB close/open
BI MCB Feedback
BO GCB blocking
Mains fail
Sys start/stop
G1
MCB GCB1
IG/IS
G2
GCB2
MGCB is used
If MGCB is used (i.e. any MGCB binary output is configured), the output MCB fdb mirror behaves as shown
in the diagram below.
All gen-set controllers must have MCB feedback binary input connected through this MCB fdb mirror binary
output of the InteliMains.
If the Mains fails, MCB stays closed but MCB fdb mirror opens. Gen-sets start and close GCB to the bus
behind MGCB.
If there is gen-set voltage present, this voltage is externally used to activate MCB opening coil. InteliMains
holds this signal active, so immediately after MCB really has opened, it
BO MCB close/open
BO MCB UV coil
BI MCB feedback
Any GCB
closed to bus
Load res OK
MGCB close/open
Recommended wiring
Mains fail
G1
MCB MGCB GCB1
LOAD
IG/IS
G2
GCB2
VectorShiftAct
The output closes when Vector shift protection activates and opens after 3 seconds. (Check that
setpoints Mains protect: VectorS prot and VectorS limit are set properly.)
GCB blocking
Output closes immediately after Mains failure and opens 2 seconds after the binary input MCB feedback
deactivates (see MCB fdb mirror description).
AI1
InteliMains Analog input 1.
AI2
InteliMains Analog input 2.
AI3
InteliMains Analog input 3.
AI2 IOM
IG-IOM or IGS-PTM Analog input 2.
AI3 IOM
IG-IOM or IGS-PTM Analog input 3.
AI4 IOM
IG-IOM or IGS-PTM Analog input 4.
EnterPassword
Password is a four-digit number. Password enables change of relevant protected set points depends on
configured Password level.
Use numeric keyboard to enter the password.
ChangePassword 1
Use or keys to set and ENTER key to change the password.
Hint:
At first the old Password 1 has to be entered before the new Password 1can be changed.
ChangePassword 2
Use or keys to set and ENTER key to change the password.
Hint:
At first the old Password 2 has to be entered before the new Password 2 or Password 1 can be changed.
ChangePassword 3
Use or keys to set and ENTER key to change the password.
Hint:
At first the old Password 3 has to be entered before the new Password 3 or Password 2 or Password 1 can
be changed.
ChngAccessCode
Use or keys to set and ENTER key to change the Access code. Access code has to be used when
remote communication is opened (SMS or modem).
Hint:
At first the Password 3 has to be entered before the new Access code can be changed.
Commands protection
Commands password protection protects following commands from WinEdit / MultiEdit direct, modem or
GSM modem connection: Horn reset, Fault reset, MCB close/open.
Selected Command password level 0, 1, 2, 3 is valid for all commands. Selected level is in RED color.
Process control
Hint:
#SystBaseLoad, #SystPwrFactor, #SystLdCtrlPtm, #SysPFCtrl PtM are replicated from InteliMains via CAN
bus into other InteliGen / InteliSys controllers.
#SystPwrFactor
The required power factor of gen-sets group operating in parallel to mains when #SystPFCtrl PtM =
BASEPF.
Step: 0,01
Range: 0,60 1,00
SysImport PF [-]
The required power factor on mains side when gen-sets group operates in parallel to mains and #SysPFCtrl
PtM = VSHARING and VS ctrl type = CTINT-I/E. InteliMains measures mains PF and regulates gen-sets
groups PF via the CAN bus.
Step: 0,01
Range: 0,60 1,00
L-Im kVAr Inductive L load character is required (where InteliMains measures), Reactive power is
imported.
C-Ex kVAr Capacitive - C load character is required (where InteliMains measures), Reactive power is
exported.
Hint:
See chapter Active and reactive power terminology.
Process control:
LS/BldCtrlType Process control:
#SysLdCtrlPtM
Process Control: CTINT - I/E
SysImport load Requested gen-set
Required I/E LDSHARING
ANEXT - I/E group power on LS line
Actual I/E
Required
baseload
PID loop
Process Control:
Temp By Pwr gain
Actual water Temp By Pwr int
AI selected by temperature
Process Control: Temp By Pwr der
Temp By Pwr extern
Process Control:
Temp By Pwr Treg Required water
temperature * SysImport load serves as limit value for Import/Export
CTINT - I/E
Actual I/E PF
ANEXT - I/E
ANEXT - BFP
Required Base PF
Requested PF
0,8
1 1R
1,2 0,8C 0,6
1,4 0,6C
0,4
0,2
0
0,6 0,8 1 1,2 1,4
Analog input
Hint:
For Import/Export PF control via analog input (ANEXT-I/E), you can enter the curve up to 0,6C (= 1,4 input
value).
Selection of IM-CU, IG-IOM or IGS-PTM Analog input for temperature measuring when temperature control
loop is active - #SysLdCtrlPtm = LDSHARING and LS/BldCtrlType = T BY PWR.
Temperature by power function changes genset group power to keep measured temperature. See following
PID lop setpoints TempByPwr Treq, TempByPwr gain, int, der.
Hint:
Select AIN IOMx analog input when use Analog input x on IGS-PTM module.
Scale for genset power setting is in kW. E.g. reading 100 on selected analog input means required 100 kW
power.
TempByPwr Treq [ C ]
Required temperature value for Temperature control By generator Power.
Step: 1 C
Range: 0 to 120 C
Hint:
To activate Temperature control by power function configure at first #SysLdCtrlPtm = LDSHARING and
LS/BldCtrlType = T BY PWR.
Mns/AnExt ON [ kW ]
When measured Mains power exceeds Mains ON Pwr the binary output Mns/AnExPwrOut closes.
Step: 1 kW
Range: -32000 kW to 32000 kW
Mns/AnExt OFF [ kW ]
When measured Mains power fall below Mains OFF Pwr the binary output Mns/AnExPwrOut opens.
Step: 1 kW
Range: -32000 kW to 32000 kW
Mns/AnExONdel [s]
Delay for opening of the binary output Mns/AnExPwrOut, when Mains ON or OFF power limit is exceeded.
Step: 1s
Range: 0 s to 600 s
Mns/AnExOFFdel [s]
Delay for closing of the binary output Mns/AnExPwrOut, when Mains ON or OFF power limit is exceeded.
Step: 1s
Range: 0 s to 600 s
Hint:
Configure binary output Mns/AnExPwrOut to indicate adjusted level of mains power.
Connect binary output Mns/AnExPwrOut to MINT - SYS START/STOP to perform Peak shaving function.
Object ON Pwr [ kW ]
When calculated object power (GensetsMains) exceeds Object ON Pwr the binary output Object Pwr Out
closes.
Step: 1 kW
Range: -32000 kW to 32000 kW
Object Pwr Out binary output behavior according to Object ON/OFF Pwr and ObjectON/OFF del setpoints:
1. Object ON Pwr > Object OFF Pwr
t
Object
Pwr Out
t
ObjectON del ObjectOFF del ObjectON del
Object
consum
Object
OFF Pwr
Object
ON Pwr
t
Object
Pwr Out
t
ObjectOFF del ObjectON del ObjectOFF del
Basic settings
ControllerName
User defined name, used for InteliMains identification at remote phone or mobile connection.
Controller name is max 14 characters long and has to be entered manually using WinEdit software.
NominMainsVPh-Ph [V]
Nominal mains voltage phase to phase.
Step: 1V
Range: 1 65000 V
NominBusVPh-Ph [V]
Nominal bus voltage phase to phase.
Step: 1V
Range: 1 65000 V
NominMainsV [V]
Nominal mains voltage phase to neutral.
Step: 1V
Range: 100 37527 V
NominBusV [V]
Nominal bus voltage phase to neutral.
Step: 1V
Range: 100 37527 V
NominMainsImp [ kW]
Nominal Mains import value. It is reference for
a) load shedding levels which are set in %
Load shedding: LdShedBased on = MAINS IMP
b) TestOnLoad function, where MCB opens when Import value is les 5% for 1 sec.
Step: 1 kW
Range: 0 32000 kW
CT ratio [ /5A]
Mains current transformer ratio. Three phases current and voltage measuring is used for mains power
measuring.
Step: 1 A/5A
Range: 1 10000 A/5A
Vm PT ratio [/1]
Mains potential transformers ratio.
Step: 0,1 V / V
Vb PT ratio [/1]
Bus potential transformers ratio.
Step: 0,1 V / V
Range: 0,1 500,0 V / V
Hint:
When is connected e.g. 22 kV to 100 V potential transformer adjust PT ratio to 220.
AnOut/kW/20mA
Conversion constant of Mains Import/Export power or Genset total running power for IG-IOM (IGS-PTM)
analog 0 to 20 mA output.
Step: 1 kW/20mA
Range: 32000 kW/20mA
AnlInp2 level1 []
The threshold level for Analog input 2 alarm detection.
Step: 1
Range: -100 10000
AnlInp3 level1 []
The threshold level for Analog input 3 alarm detection.
Step: 1
Range: -100 10000
Mains protect
Mains >V [%]
Threshold for mains and bus over voltage. All three phases are checked. Maximum of three phases is used.
Step: 1 % of Nomin voltage
Range: 100 150 % of Nomin voltage
MainsIshort [%]
When Short circuit limit Mains Ishort is reached, the binary output MCB CLOS/OPEN is immediately opened
and Mains Short current alarm is detected.
Short circuit alarm is recorded to Alarm list and History. The engine cools and stops down when, Fault reset
button is not pressed.
Step: 1 % of Nomin current
Range: 100 - 500 %
IDMT protection opens Binary output MCB CLOSE/OPEN when becomes active. IDMT protection is
recorded to Alarm list and History.
Hint:
Reaction time is limited up to 900 sec = 15 minutes. IDMT protection is not active for Reaction time values
longer than 15 minutes.
EXAMPLE of Reaction time for different over current levels. Values in column 200% are 2Inom del.
Overcurrent
200 % = 100 % 101 % 110 %
Mains2Inom del
0,2 s No action 20 s 2s
Reaction time 2s No action 200 s 20 s
20 s No action No action 200 s
(time > 900 s)
MCurrUnbal [%]
Threshold for mains current unbalance detection.
Step: 1 % of Nominal current
Range: 1 200 % of Nominal current
VectorS limit []
Vector shift protection limit see chapter Vector shift protection.
Before setting see actual MaxVectorS value on InteliMains Gensets screen. This value displays maximal
value from the last MCB closing and is set to zero after MCB opens.
Step: 1
Range: 1 45
IM OFF IM ON
Mains O.K. Mains O.K.
AUX.
INVERTING
RELAY
iG-CU
DO 4
MCB
- +
Battery
Hint:
In case MCB logic = CLOSE-OFF it is necessary to change externally the polarity of the output signal.
MainsRevPwrDel [s]
Delay for Mains reverse power protection.
Step: 0.1s
Range: 0.0 600.0s
Pwr management
Hint:
All parameters in the Pwr management group have to be equal throughout all the controllers. They are
automatically replicated from one IG or IM controller to the other CAN bus connected IG controllers. Those
setpoint names begin with # character.
400 kW
300 kW
500 kW
100 kW
0 kW
160 kW
260 kW
360 kW
60 kW
Actual power
1. Genset running
2. Genset running
3. Genset running
4. Genset running
5. Genset running
40 % of 400 kW
40 % of 300 kW
40 % of 100 kW
40 % of 200 kW
400 kW
500 kW
100 kW
200 kW
300 kW
0 kW
260 kW
360 kW
Actual power
40 80 120 160
kW kW kW kW
1. Genset running
2. Genset running
3. Genset running
4. Genset running
5. Genset running
Hint:
Pwr management mode REL (%) is available from InteliGen V6.0, InteliSys V3.0.
#SysAMFstrtDel [s]
#SysAMFstpDel [s]
#LoadResStrt 1 (2, 3, 4) [kW%]
#LoadResStp 1 (2, 3, 4) [kW%]
LoadRes Stp has to be higher than corresponding LoadRes Strt for Pwrmgm mode = ABS (kW)
LoadRes Stp has to be lover than corresponding LoadRes Strt for Pwrmgm mode = REL (%)
#NextStrtDel [s]
#OverldNextDel [s]
#NextStopDel [s]
#SlowStopDel [s]
#MinRun power 1 [kW]
#MinRun power 2 [kW]
#MinRun power 3 [kW]
DetectOtherCAN [ DISABLED, ENABLED ]
ENABLED: Message WrnCANbusEmpty is recorded to Alarm list and History when no other controller is on
the CAN bus.
DISABLED: No message.
Load Shedding
Load shedding is active in InteliMains AUT and MAN modes.
Sync/Load ctrl
Hint:
See IM IG MINT setpoints adjustment.
BtoM AngleReq []
Phase difference between bus and mains voltage. Use this setpoint for phase correction of potential
transformers connection.
Phase window []
Maximum phase angle difference between bus voltage and mains.
Step: 1
Range: 0 90
Volt/PF ctrl
Voltage gain [%]
Gain of voltage control loop.
Step: 0.1 %
Range: 0.0 to +200.0 %
PF gain [%]
Gain of power factor control loop.
Step: 0.1 %
Range: 0.0 200.0 %
PF int [%]
Relative integration factor of power factor control loop. Increasing of integration value causes quicker
response.
Step: 1%
Range: 0 100 %
Act. calls/SMS
Warning call [DISABLED / ENABLED]
Enables or disables active calls/SMS to selected phone or mobile when a warning alarm occurs.
AcallCH1..3Type
Up to three separate channels are available for any one of the following types of messages:
DISABLED: Channel is disabled.
DATA: Standard analog, GSM or ISDN modem connection to WinEdit.
SMS: Channel sends SMS message. Only when GSM modem connected.
E-MAIL: Channel sends E-mail. Only when is IG-IB connected.
EML-SMS: Channel sends E-mail with short SMS. Only when is IG-IB connected.
Email contains
- header with serial number and application info.
- Alarm list
- 20 History records (reason, date, time)
Example of EML-SMS:
AL=(Sd Water Temp,Wrn Water Temp,!Emerg Stop,ActCallCH1Fail)
Hint:
GSM modem must be connected to controller for Active GSM call or SMS.
IG-IB does not support direct SMS, just as an email.
AcallCH1..3Addr
Address for channel 1...3 active call. Each above message type has either a number or an e-mail address
associated to it.
For more details see WinEdit-MultiEdit guide chapter IG-IB Internet communication.
Hint:
To receive active call run WinEdit Type of connection = Active call. WinEdit Active call window contains list
of received AIG or AIS files. Each list item contains Gen-set name, Date, Time, controller serial number.
NumberRings AA [-]
Number of rings prior to answering the modem connection from PC to controller.
Step: 1
Range: 1 30
Hint:
NumberRings AA change is not accepted immedately but after controller is switched on or when modem is
connected to controller.
Time [HHMMSS]
Real time clock adjustment
Date [DDMMYY]
Actual date adjustment
Sensor spec
Calibr AI1 (AI2, AI3) []
Calibr AIM1 (AIM2, AIM3, AIM4) [] only when IG-IOM configured
Calibrating constant to adjust the measured value of IM-CU and IG-IOM or IGS-PTM (when configured)
analog inputs. Physical dimension of calibrating constant is corresponding to Analog input.
Step: 1
Range: -1000 +1000
Calibrating Constant
Resistor R
Sensor
R2
R3
R4
R5
Hint:
Calibr AI1, Calibr AI1, Calibr AI3 have to be adjusted when measured value is near the alarm level.
LOAD
MAINS GEN
Q Q Q
Cos < 0 L Cos > 0 L Cos > 0 L Cos < 0 L Cos > 0 L
Export P Import P Consumption P Consumption P Generation P
Import Q Import Q Inductive LOAD Generation Q Generation Q
Mains
Exported active power is supplied to the mains. It is displayed in negative numbers e.g. 20kW.
Imported active power is consumed from the mains. It is displayed in positive numbers e.g. +20kW.
When reactive power is imported (>0) InteliMains displays L (inductive) character of the load. Process
control: SysImportLdChr = L-Im kVAr.
When reactive power is exported (<0) InteliMains displays C (capacitive) character of the load.
Process control: SysImportLdChr = C-Ex kVAr.
Load
Active power consumed by Load is displayed in positive numbers e.g. 20kW.
When reactive power is positive (>0) InteliMains displays L (inductive) character of the load.
When reactive power is negative (<0) InteliMains displays C (capacitive) character of the load.
Genset
Generated active power is displayed in positive numbers e.g. 20kW.
When reactive power is positive (>0) InteliMains displays L (inductive) character of the load.
When reactive power is negative (<0) InteliMains displays C (capacitive) character of the load.
To decrease Speed governor out sensitivity use IG-PCLSM VoutR output and connect external
resistor R2 in parallel to output.
VoutR output voltage is in this case R2 / (R1+R2) = 1 / 11 = 0.09 times less than Vout voltage.
Speed
VoutR range: depends on
IG-PCLSM resistor R2 value governor
G ND G ND
R2=1k
R1=10k
VoutR AUX input
Vout range:
-10.0 V to +10.0 V
Each genset in the group should have the same speed governor out sensitivity. Speed governor
characteristics difference unbalances Load sharing during synchronizing of loaded gensets group to
the mains.
Each genset should have the same AVRi out sensitivity. AVR characteristics difference unbalances PF
sharing during synchronizing of loaded gensets group to the mains.
3. Voltage control
Conditions: idle running single gen-set, analog Volt/PF control using IG-AVRi module.
Voltage matching
4. Forward synchronizing
Conditions: two idle running gen-sets, one is connected in MAN mode to dead bus, on the second
genset press in MAN mode GCB close/open button to start synchronizing to the bus.
Adjust Sync control set points of each gen-set separately. Check InteliGen / InteliSys-MINT
synchroscope screen.
IG - Sync/Load control: Voltage window, Phase window, Dwell time,
Speed gov bias, Freq gain, Freq int, Freq der and Angle gain, Angle der.
Hint:
At first set Phase window = 0 to avoid GCB closing.
Simulate speed steps by changing of Speed gov bias setpoint or press repeatedly GCB close/open button to
start stop synchronizing and check stability of synchronizing.
5. Load sharing
Conditions: two gensets are running in isolated parallel (MCB is opened). In the first step no load, then
apply full load.
When all gensets are running idle voltage of Load sharing line is zero V.
When all gensets are running at Nominal power voltage of Load sharing is 7,5V.
In parallel isolated mode (MCB is opened) adjust following Load sharing set points.
When genset is loaded, unloaded, loading, unloading check the Load sharing. Check if Speed governor
analog output does not reach limits below 10V or over 10V of the range.
IG - Sync/Load control: Load ramp, LS gain, LS int, LS der,
GCB open level, GCB open del
Hint:
When one genset is running loaded in MAN mode press GCB close/open button of the second genset to
synchronize and load. Then press STOP button to unload genset and open GCB. Pressing of the START
button returns IG controller back from Cooling to Running state.
Hint:
Output values of Sync/Load and Volt/PF control loops check at InteliGen / InteliSys MINT synchroscope
screen.
SpeedRegOut indicates IG-PCLSM Speed governor output in the range from 10.0V to +10.0V.
VoltRegOut indicates IG-PCLSM AVRi output in the range from 0% to 100%.
Load and PF sharing can be unbalanced during synchronizing when different sizes of gensets (or
different adjusting of speed governors) are running in parallel.
Adjust following InteliMains synchronizing set points, check InteliMains synchroscope screen.
IM - Sync/Load control: Voltage window, Phase window, Dwell time,
Slip freq gain, Slip freq int, Slip freq der and Angle gain, Angle der.
Hint:
Press repeatedly MCB close/open button on InteliMains controller (in MAN mode) to start /stop
synchronizing and check IM synchroscope screen. At first set Phase window = 0 to avoid MCB closing.
fmains
Speed gov bias
Load and PF sharing can be unbalanced during synchronizing when different sizes of gensets (or
different adjusting of speed governors) are running in parallel.
During synchronizing (Volt matching is active) adjust following Voltage control set points:
IM - Volt/PF control: Volt gain, Volt int, Volt der.
Hint:
At first set Phase window = 0 to avoid MCB closing.
Press repeatedly MCB close/open button on InteliMains controller (in MAN mode) to start /stop
synchronizing and check IM synchroscope screen.
For test, adjust Nominal voltage of gensets group to different value from the mains voltage (e.g.210V).
Voltage matching
Vbus InteliMains IG / IS - MINT
AVRi
Voltage gain VS gain analog output
CAN bus +
Voltage int VS int
Voltage der VS der +
Vmains
AVR DCout bias
#SysBasePF IG / IS - MINT
AVRi
PF gain analog output
PF int +
PF der
+
Genset PF
AVR DCout bias
Hint:
Forward synchronizing test
When mains is connected to the bus in MAN mode press the GCB close/open button of IG-MINT controller
to start forward synchronizing and voltage matching of single genset to the mains.
InteliMains via LS line and CAN bus controls SysImport load and SysImport PF value which is shared
between gensets in the group.
When the STOP button of IG-MINT controller is pressed, genset unloads, opens GCB and steps to Cooling
state. Pressing of the START button returns controller back from Cooling to Running state.
SysImport load
Speed gov bias
Actual
PF control
Mains InteliMains IG / IS - MINT
PF AVRi
PF gain VS gain analog output
CAN bus +
PF int VS int
PF der VS der +
SysImport PF
AVR DCout bias
Hint:
Output values of Sync/Load and Volt/PF control loops check at InteliMains synchroscope screen.
LSO indicates IM-PCLSM load sharing output in the range from 10.00V to +10.00V.
VVO indicates IM Volt/PF output to CAN bus in the range from -10000 to +10000.
2000 200
1800
Resistance [ohm]
Resistance [ohm]
1600
1400
150
1200
1000 100
800
600 50
400
200
0
0
0 20 30 40 50 60 70 80 90 110 0 2 4 6 8 10
Temperature [ C] Pressure [bar]
Predefined characteristics
Pt100 Pt1000 Ni100 Ni1000
C R [ ] C R [ ] C R [ ] C R[]
Hint:
When measured value is 6% out of range the Sensor fail FLS is detected.
3 2 1 4
12
6
7
13
9 11 10 5 14
Pushbuttons:
1. MODE Cyclic forward selection the gen-set operation mode (OFF -> MAN -> AUT )
2. MODE Cyclic backward selection the gen-set operation mode (AUT -> MAN ->OFF )
3. HORN RESET Deactivates the HORN
4. FAULT RESET Acknowledges faults and alarms
5. MCB ON/OFF Manual open/close of the Mains circuit breaker in MAN mode.
6. PAGE Cyclic selection of the display mode(MEASUREMENT->ADJUSTEMENT-
>HISTORY)
7. Select the set point, select the screen or increase set point value
8. Select the set point, select the screen or decrease set point value
9. ENTER Confirm set point value
Display menus
There are 3 display menus available: MEASUREMENT, ADJUSTMENT and HISTORY
Each menu consists of several screens. Press repeatedly PAGE button to select requested menu.
Hint:
Available in MEASUREMENT menu only.
Left up corner: Actual mode of active power control Base or Imp/Exp and required value.
Actual mode of reactive power control Base or Imp/Exp and required value.
There is indication OFF mode and Island mode (IslOper) as well
Right up corner: L Active access lock indication
! Alarm list reminder
Load: Actual value of active power.
Actual value of PF
Mains: Actual value of active power.
Actual value of PF
Gensets: Actual value of active power.
Actual value of PF
MCB: - MCB closed
/ MCB opened
Hint:
Mains and bus voltage is measured and stored depends on archive
Phase to Neutral voltage in standard archives: IM-5.1.aig, IM+IOM-5.1.aig
Phase to Phase voltage in high voltage archives: IM-HV-5.1.aig, IM+IOM-HV-5.1.aig.
Gensets screen
Gensets total power in kW
Gensets total kVAr
Calculated gensets PF
Mains frequency in Hz
Bus frequency in Hz
MaxVectorS in
Analog inputs
AnIn1 IM IM-CU Analog input 1 (bar graph with one limit mark)
AnIn2 IM IM-CU Analog input 2 (bar graph with one limit mark)
AnIn3 IM IM-CU Analog input 3 (bar graph with one limit mark)
Battery voltage (bargraph)
Power measuring
Mains Import total in kW
Mains Import per phase L1, L2, L3
Mains PF total
Mains PF per phase L1, L2, L3
Mains reactive power total in kVAr
Mains rective power per phase L1, L2, L3
Mains apparent power total in kVA
Mains apparent power per phase L1, L2, L3
Mains statistic
Mains total kWh
Mains total reactive power in kVAhr
Power management
Total Available Pnom = sum of Nominal power
Total Running Pnom = sum of Nominal power
Total Running power bar graph
Active Reserve bar graph with Start,Stop limit
CAN BUS status for addresses 1 to 16
CAN BUS status for addresses 17 to 32
Alarm list
Alarm list screen displays actual alarms. Active alarms have dark background. Alarms presence is
displayed on the main measure screen by exclamation mark in the right up corner.
PAGE
IM-IM+IOM-6.1.pdf
500 ENGINE BASIC
ENGINE PROT
0 1000 GEN BASIC
12345h
GEN PROTECT
Screen
MAINS FAIL
586 kW 14:23:15
PAGE ENTER
GEAR TEETH O F
150 150 -
NOM RPM
Next 1500 1500 RPM
START RPM LE Y
30 30% R
CRANK TIME
Screen 10 10s
B
ENTER
PAGE
85/114
..... TO MEASURE SCREEN
Function description
There are three modes of InteliMains: OFF MAN AUT.
To select the mode use MODE and MODE.
OFF mode
InteliMains has no influence at gen-sets group.
If mains voltage is within limits and no mains alarm is active (e.g. IDMT overcurrent), MCB is closed
after MCB close del.
InteliMains is disconnected from the Load sharing line.
MAN mode
When Mains voltage is out of limits InteliMains switches the MCB off.
If the Mains voltage is within limits (adjusted in the set points group Mains protection) and there is
no Bus voltage press MCB ON/OFF to close MCB.
If Mains or Bus voltage is out of the limits, InteliMains does not respond to MCB ON/OFF.
If the Mains and Bus voltage are in limits pressing of MCB ON/OFF starts synchronizing of MCB.
AUT mode
When Mains voltage is out of limits InteliMains switches the MCB off.
When Mains voltage returns InteliMains switches MCB to dead bus MCB close del delayed.
When Mains voltage returns and bus voltage is within limits InteliMains starts synchronizing Mains
ret del delayed.
Hint:
InteliMains does not respond to MCB ON/OFF button in AUT mode.
Load shedding
Binary input: Man load recon
Binary outputs: Load shedd 1 (2, 3)
Setpoints: Load Shedding
G en-set power
Ld shed level
closed
BO Load shed 1
closed
BO Load shed 2
closed
BO Load shed 3
Ld recon level
MGCB control
MGCB control in AUT mode
MGCB closes when:
b. Actual Load reserve is fulfilled and
c. There is no voltage on the IM Bus
Or
a. MCB is closed, MCB feedback is closed and
b. No GCB is closed
MGCB can be opened in any condition by Binary input MGCBButton in MAN mode.
Hint:
InteliMains see only GCBs from controllers communicating on CAN bus. MGCB is not closed when no
controller communicate on CAN bus.
MGCB is opened in OFF mode.
MGCB closing and opening is written to History record.
TestOnLoad
Initial conditions
InteliMains in AUT mode and
Gensets group is running parallel to the mains and
Process control: SysLsCtrlPtm = LDSHARING and
Process control: LS/BldCtrlType = IMP/EXP and
Actual Load reserve is OK.
When Binary Input TestOnLoad is closed InteliMains transfers Load from mains to generators (reduces
Import/Export value to zero) and opens MCB (even if Mains is OK).
When TestOnLoad is not successful, WrnTstOnLdFail alarm is activated and binary output TestOnLoadFail
is closed.
The VS protection detects mains failure within 30 ms. The total time of disconnection is shorter than 100 ms
including disconnecting time of the circuit breaker (depends on time). The requirement for generator
disconnection comes on power change of more than 15% - 20%. Slow changes of frequency (e.g. governor
commands) dont activate the protection.
As shown in the timing diagram the voltage jumps to another value and the phase position changes. This
procedure is named phase or vector shift. InteliMains continuously measures the cycles, starting each zero
up ward slope. The time cycle is internally compared to the quartz table reference time. In case of vector
Warning
When warning comes up, only alarm outputs are closed.
Possible warnings:
Analog inputs alarm
Binary inputs alarm
Mains voltage, frequency, current alarm
Bus voltage, frequency alarm
MCB failure
Binary inputs
Use WinEdit to configure following alarms on binary inputs:
Analog inputs
When is BO MCB close/open in steady state and MCB feedback is changed the MCB fail is detected
immediately (no delay).
BO MCB close/open closed
opened
BO MCB close/open
closed
BI MCB feedback
BI MCB feedback opened
active
No MCB fail
Hint:
No fail is detected when MCB is closed and MCB feedback opens because MCB can be opened due to an
external protection device.
active
Alarm: MCB fail
R1
R2
R3
R4
R5
Sensor -6% Range of measurement +6% Sensor
100%
Failure Failure
Range of sensor
Load conditions :
No LdShed No load shedding is active.
LdShedL1 Load shedding of the first step is active.
LdShedL2 Load shedding of the second step is active.
LdShedL3 Load shedding of the third step is active.
Timer conditions
No Timer No timing is active.
LdShedChg Load timing is active
LdRecChg Load reconnection timing is active
PC software - WinEdit
On the PC (for direct or modem connection) has to be installed the ComAps software package WinEdit.
(based on Windows 95 or newer platform)
WinEdit enables:
read the quantities,
adjust all set points,
read the history
control the engine
configure the controller
select software configuration
modify alarm inputs and outputs
direct or modem communication
receive active calls
History file
InteliMains controller stores a record of an each important event into the history file. The history file contains
120 records. When the history file is full, the oldest records are removed.
Record structure
Hint:
Mains and bus voltage is measured and stored depends on archive
Phase to Neutral voltage in standard archives: IM-5.1.aig, IM+IOM-5.1.aig
Phase to Phase voltage in high voltage archives: IM-HV-5.1.aig, IM+IOM-HV-5.1.aig.
Mains
Mains phase 1 over voltage Vm1 Over Vm1 Over
Mains phase 1 under voltage 0 Vm1 Under
Mains phase 2 over voltage Vm2 Over Vm2 Over
Mains phase 2 under voltage 0 Vm2 Under
Mains phase 3 over voltage Vm3 Over Vm3 Over
Mains phase 3 under voltage 0 Vm3 Under
Mains voltage unbalance Vm Unbal Vm Unbal
Mains current unbalance Im Unbal Im Unbal
Mains over frequency fm Over fm Over
Mains under frequency 0 fm Under
Short current protection MainsShortCurr MainsShortCurr
IDMT protection Mains IDMT Mains IDMT
Phase sequence
Inverted polarity of bus phase L1 BUS L1 neg 0
Inverted polarity of bus phase L2 BUS L2 neg 0
Inverted polarity of bus phase L3 BUS L3 neg 0
Wrong bus phase sequence BUS ph opposed 0
Wrong bus phase sequence and polarity L1 BUS ph + L1 neg 0
Wrong bus phase sequence and polarity L2 BUS ph + L2 neg 0
Wrong bus phase sequence and polarity L3 BUS ph + L3 neg 0
Inverted polarity of mains phase L1 M L1 neg 0
Inverted polarity of mains phase L2 M L2 neg 0
Inverted polarity of mains phase L3 M L3 neg 0
Bad mains phase sequence M ph opposed 0
Bad mains phase sequence and polarity L1 M ph + L1 neg 0
Bad mains phase sequence and polarity L2 M ph + L2 neg 0
Bad mains phase sequence and polarity L3 M ph + L3 neg 0
The complete description of Modbus communication protocol can be found in Modbus Protocol Reference
Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are available from web
site at http://www.modicon.com/openmbus/ .
Modem connection
Modem communication of Inteli controllers, IG-MU and IG-IB is based on full modem cable connection
where all handshaking signal DCD, RTS, CTS are active and connected.
Intelicontrollers and IG-MU, IG-IB automatically detect modem connection via RS232 - DSR (Data Send
Ready) signal. Controller detects modem when is DSR active and direct connection when passive or not
connected.
Make sure all signals are connected and activated in modem when it is not possible to open connection.
Syntax: #XX
XX controller address [1 to 32]
Example: #5
Message is addressed to controller with address 5.
2. Access code
InteliGen / InteliSys Access code is 15 characters length string. Access code is separated from
controller address by column.
Syntax: #5:X
X controller access code up to 15 characters length
Example: #5:accesscode
Message is addressed to controller with address 5 and its access code is set to
value accesscode.
Hint:
Access code cant contain space character. Access code can be changed in WinEdit only.
4. Adjust setpoint
Command for adjusting of selected setpoint. Answer message contains only confirmation of
successful adjusting or appropriate error.
5. Enter password
Password setting command. Password has to be set before adjusting of protected setpoint or calling
protected gen-set control command. Setting password command is not necessary before every
adjusting. Password is four digit number in range 0 to 9999 and is valid for all rest of SMS.
6. Gen-set control
SMS command for invoking gen-set control command as Start, Stop, Fault reset etc.
Syntax: c Y (or cY)
c command
Y type of operation
Syntax: a
a command
Example: #5:accesscode a
Request of actual Alarm list.
Return code: AL=(items of alarm list) comma separated items of Alarm list.
Exclamation mark in front of Alarm list item indicates inverse record (still active
alarm).
8. Time delay
Insert time delay before serving next SMS command.
Syntax: d T
d command
T time delay in sec (in range 1 to 600)
Example: #5:accesscode d 10
Request 10 sec delay before serving next SMS command.
Note: Any other SMS messages are not served during time delay!
Syntax: ?
Example: #5:accesscode ?
Return code: ?=(p passwd,r comm_obj,w com_obj val,c cmd_num,d sec,a,?) list
of supported SMS commands
Note: Return code is not separated to more message.
Hint:
Setpoints Stringlist type (e.g. Controller Mode) is read as string and adjust as index of string
item in string list. e.g. Controller Mode:
Active SMS message is invoked by controller request. Active SMS message is sending to GSM phone
number specified in setpoints group Act. Calls/SMS on InteliGen/InteliSys. Specified phone number must
be in international format +cccyyyxxxxxx where ccc is country code, yyy is operator prefix and xxxxxx is local
phone number. Active message contains items of actual Alarm list (most eight items).
Example of active SMS message:
#Gen-set name:AL=(Wrn PrimWater temp, !Emergency stop)
INTERNET
ETHERNET
LED 1 2
IB CONFIG
iG-CU
DONGLE
MODEM
IG-CU RS232
iG-IB
(iS-CU)
LED 3 4 5 6 LED
CAN POWER
IG-IB interface
Modem / IB config RS232 interface for IG-IB configuration or Modem connection
IG-CU / Dongle RS232 interface for one controller connection or for Dongle for multiple
controllers communication.
CAN bus interface to group of controllers
Ethernet to LAN interface to company net
See IG-IB Internet bridge
Hint:
More details see Communication guide chapter IG-IB Internet communication.
Group Name Value Dimension Password Com. obj. Low limit High limit Data type
Operating conditions
Operating temperature IG-CU -20..+70oC
Operating temperature IG-CU-LT -30..+70oC
Storage temperature -30..+80oC
Flash memory data retention time 10 years
Protection front panel IP65
Humidity 95% without condensation
(From IG serial number xxxx0900)
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
Vibration 5 - 25 Hz, 1,6mm
25 - 100 Hz, a = 4 g
Shocks a = 200 m/s2
IG-MTU
Primary voltage Ph-Ph 3x400 VAC / 50Hz (3x480 VAC / 60 Hz)
Secondary voltage Ph-N 3x 230 V AC ( 3x277 VAC / 60 Hz) , 5 VA
Mechanical dimensions: 155 x 95 x 60 mm , DIN rail (35 mm) mounted
Primary/secondary Phase shift < 1
Operating temperature -30..+70oC
IG-MTU-C
Primary voltage Ph-Ph 3x400 VAC / 50Hz (3x480 VAC / 60 Hz)
Secondary voltage Ph-N 3x 230 V AC ( 3x277 VAC / 60 Hz) , 5 VA
Mechanical dimensions: 155 x 95 x 60 mm , DIN rail (35 mm) mounted
Primary/secondary Phase shift 3
Operating temperature -30..+70oC
Analog inputs
Not electrically separated
Resolution 10 bits
Sensor resistance range 0 -2,4 k
Resistance measurement tolerance 4 % 2 out of measured value
IM-PCLSM
Power supply: 8 36 V DC
Consumption: 100 mA
Binary inputs
Number of inputs 4
Input resistance 4,7 k
Input range 0-36 VDC
Switching voltage level for close contact indication 0-2 V
Max voltage level for open contact indication 8-36 V
IG-IOM
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Connection to IG-CU standard IOM cable 2 meters length, not galvanic separated
Operating temperature -30..+70oC
Binary inputs
Number of inputs 8
Input resistance 4,7 k
Input range 0 - 36 VDC
Switching voltage level for close contact indication 0-2V
Max voltage level for open contact indication 8-36 V
Analog inputs
Not electrically separated
Number of inputs 4
Resolution 10 bits
Sensor resistance range 0 -2,4 k
Resistance measurement tolerance 4 % 2 out of measured value
Analog output
Not electrically separated
Number of outputs 1
IG-MU
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Operating temperature -30..+70oC
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Interface to modem or PC RS232, RS422, RS485
Interface to controller CAN
IG-IB
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Operating temperature -30..+70oC
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Interface to controller RS232 or CAN
Interface to modem RS232
Interface to Ethernet RJ45
IGS-PTM
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Operating temperature -30..+70oC
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Interface to controller CAN
Binary inputs and outputs see IG-IOM
Analog output see IG-IOM
Analog inputs
Not electrically separated
Number of inputs 4
Resolution 10 bits
Maximal resistance range 0 250
Maximal voltage range 0 100 mV
Maximal current range 0 20 mA
Resistance measurement tolerance 1 % 2 out of measured value
Voltage measurement tolerance 1,5 % 1mV out of measured value
Current measurement tolerance 2,5 % 0,5mA out of measured value
IGL-RA15
Power supply
Voltage supply 8-36V DC
Consumption 0,35-0,1A (+1A max horn output)
Depend on supply voltage
Operating conditions
Operating temperature -20..+70oC
Storage temperature -30..+80oC
Protection front panel IP65
Horn output
Maximum current 1A
Maximum switching voltage 36 VDC
Communication interface
CAN bus interface
Galvanically separated
Maximal CAN bus length 200m
Speed 250kBd
Nominal impedance 120
Cable type twisted pair (shielded)
Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length and
32 IS-COM units connected:
Nominal Velocity of Propagation min. 75% (max. 4,4 ns/m)
Wire crosscut min.0,25 mm2
Maximal attenuation (at 1 MHz) 2 dB / 100m
Hint:
When use double pair cable, use data pair for CAN bus and Power supply DC pair for Load sharing line
connection.