Vous êtes sur la page 1sur 4

GX-20/FM-200

Fire Extinguishing System

GX20/FM-200 is a clean agent fire suppression system that protects high-


value assets from fire and the effects of fire-fighting, allowing normal
operations to be resumed quickly with no collateral damage and clean-up
costs. Kidde Fire Protection is at the forefront of new technologies in fire
safety, offering a range of state-of-the-art fire extinguishing systems.

GX-20 systems utilise FM-200, a Benefits


gaseous extinguishing agent Fast and effective against a wide
manufactured by Great Lakes range of Class A, B and electrical
Chemical Corporation, which has fires
emerged as the most viable Safe for occupied areas
alternative to Halon 1301 on the basis Non-corrosive and electrically
of extensive trials. FM-200 is fast and non-conductive
effective with a low space/weight No post-discharge residue, no
characteristic which is also clean-up required
environmentally-acceptable and safe Environmentally acceptable
for human exposure. 25 bar system
Engineered and pre-engineered
Halon fire extinguishants were systems available
regarded for many years as the most Range of system release options
effective fire suppressants for a wide Low installation and maintenance
range of applications. Amendments to costs
the Montreal Protocol of 1987 focused Computer design maximises
on the manufacture of Halons, effectiveness of system
however, and their production has FM Global and LPCB approved
now ceased in recognition of their components with ULI listed
virulent destruction of the ozone systems available on request
layer. In addition, European legislation Marine systems available
requires that Halon systems within the
EU must have been decommissioned
by the end of 2003.

FM-200 has been adopted by the


majority of the world's fire protection
companies and is the most widely used
clean agent fire suppressant, with tens
of thousands of systems installed
across the globe.
2

What is FM-200? The environment


FM-200 is a colourless, odourless gas FM-200 has a zero ozone-depletion
containing only carbon, hydrogen and potential and a short atmospheric
fluorine, thereby lacking the ozone- lifetime. When used in a fire event,
depleting presence of bromine atoms. FM-200 mitigates the effects of an
Highly penetrative and achieving an uncontrolled fire and at the end of
homogeneous dispersion in the hazard the lifetime of the system, the gas can
zone, it acts on fires largely by be readily recovered and recycled.
physical means, lowering the
temperature of the flame and fuel to System design
a point at which combustion reactions The GX-20 system comprises a versatile
cannot be sustained. There is no range of cylinders, valves and related
significant obscuration on discharge components which have been selected
and this non-corrosive and electrically for use with FM-200 and have been
non-conductive agent causes no subject to stringent testing
damage to sensitive equipment with procedures. Flexibility, quality and
no post-discharge clean-up required. reliability make the Kidde Fire
Protection GX-20 range the world's
finest in fire safety and the equipment
carries third party listing through FM
Global and the Loss Prevention
Pressure Operated Control Head
Certification Board, plus Lloyds
Register of Shipping and DNV for
marine applications. Systems are
UL2166 compliant.

Electric Control Head Electric & Cable Operated Control Head Lever Operated Control Head Lever & Pressure Operated Control Head

Safety to personnel Both engineered and pre-engineered


A significant body of toxicity data has systems are available. The pre--
been obtained for FM-200 from over engineered systems offer a low
70 studies. The US Environmental engineering/design cost option with
Protection Agency and the UK Halon defined maximum design parameters.
Alternatives Group accepts the use of Engineered systems offer optimum
FM-200 in occupied spaces up to 9% designs for the defined risks with
concentration without mandated reduced pipe sizes, unbalanced flows
egress times and at up to 10.5% with and common room and void
mandated evacuation times. Since the protection possible.
agent does not act by oxygen-
Electric Control Head (Stackable) depletion in the hazard zone, it poses
no human asphyxiation threat.
3

GX-20 cylinders System space requirements Assured reliability


A wide range of sizes is available, System space and weight are usually Kidde Fire Protection systems are
offering a choice of fill capacities to at a premium in industrial and designed to conform to NFPA 2001
meet specific requirements and ensure commercial premises. FM-200 is stored and ISO 14520 requirements. An
maximum economy in installation. as a liquid in nitrogen-pressurised empirically-verified Windows based
Each cylinder is manufactured from containers at 25 bar, leading to computer program is used to model
high strength alloy steel. minimal storage requirements two-phase agent flow and ensure that
The larger cylinders have an optional comparing favourably with all other the correct concentration of agent is
liquid level device for ease of contents viable gaseous agents. achieved within 10 seconds
monitoring and improved system throughout the protected zones as
maintenance. Approvals required by the NFPA and ISO
Kidde FM-200 systems are FM Global Standards.
GX-20 valves listed, meet the criteria of UL2166 and
GX-20 valves are designed for carry LPCB design manual and
optimum system performance, component approval.
allowing the most economical pipe
sizes to be selected, thus lowering Applications
installation costs. The fast-opening GX-20 systems are ideally suited to the
valves are available in a range of sizes protection of high value assets from
and are manufactured from tough, both loss by fire damage and the
corrosion-resistant brass under accompanying catastrophic plant
stringent quality control standards. down-time. Applications include:
The valve design enables the Kidde
worldwide network of factory-trained Computer suites
distributors to recharge the cylinders Telecommunications
without the need for replacement facilities
parts. An easy-to-read gauge on the Internet Service Providers
valve permits the convenient visual Control rooms
inspection of the cylinder pressure. Railway signalling
GX-20 valves are actuated by one of centres
the following means: Air traffic control centres
Stores & Archives
Electric solenoid Heritage sites - art
Pneumatic diaphragm galleries and museums
Local manual release at the Medical and laboratory
control head equipment
Manual release at a remote pull Petrochemical plant
station Offshore oil and gas
All related components from discharge installations
nozzles to control heads are designed Pipeline pumping
to be compatible, allowing a complete stations
system to be configured using FM Ships engine rooms
Global and LPCB approved Kidde Fire
Protection equipment.

Nozzles
A range of custom-designed nozzles is
available, including 180 wall-mounted
and 360 ceiling-mounted types.
BS EN ISO9001
FM00215

Kidde Fire Protection operates a continuous programme of product development. The right is therefore reserved to modify any
specification without prior notice and Kidde Fire Protection should be contacted to ensure that the current issues of all technical
data sheets are used.