3F-Canteen C1 Input Data

Project Name: Nahda School 08/20/2017


Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 1 of 178


3F-Canteen C1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 482.9 - - 71.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 2 of 178


3F-Canteen C2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 3 of 178


3F-Canteen C2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 461.4 - - 68.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 4 of 178


3F-Canteen C3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 5 of 178


3F-Canteen C3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 500.1 - - 71.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 6 of 178


3F-Canteen C4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 7 of 178


3F-Canteen C4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 445.6 - - 68.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 8 of 178


3F-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ........................................................................ 3F-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 9 of 178


3F-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 346.5 - - 15.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.5 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 10 of 178


3F-Corridor 2+ Stair 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name .......................................................... 3F-Corridor 2+ Stair 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Corridor 2+Stair 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 11 of 178


3F-Corridor 2+ Stair 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 659.3 - - 33.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 15.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 12 of 178


3F-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ........................................................................ 3F-Corridor 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Corridor 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 13 of 178


3F-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 366.5 - - 16.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 14 of 178


3F-Gym Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................................. 3F-Gym
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Gym x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 27.0 C
Cooling T-stat: Unocc. ................................................................................ 30.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 15 of 178


3F-Gym Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 8058.0 - - 1447.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 90.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 214.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 16 of 178


3F-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ............................................................................. 3F-Library
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Library x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 17 of 178


3F-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1467.6 - - 286.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 18.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 32.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 18 of 178


3F-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ...................................................................... 3F-Staff Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Staff Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 19 of 178


3F-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 249.7 - - 25.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 20 of 178


3F-Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................................ 3F-Store
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Store x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 27.0 C
Cooling T-stat: Unocc. ................................................................................ 35.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 21 of 178


3F-Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 223.7 - - 28.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 22 of 178


3F-Store 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ............................................................................. 3F-Store 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Store 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 27.0 C
Cooling T-stat: Unocc. ................................................................................ 35.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 23 of 178


3F-Store 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 324.7 - - 40.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 24 of 178


3F-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ...................................................................... 3F-Supervisor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Supervisor x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 25 of 178


3F-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 212.3 - - 23.7

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.5 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 26 of 178


FF-Classroom 20,22 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ............................................................ FF-Classroom 20,22
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 20,22 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 27 of 178


FF-Classroom 20,22 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 710.5 - - 210.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 28 of 178


FF-Classroom 21 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 21
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 21 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 29 of 178


FF-Classroom 21 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 568.1 - - 203.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 30 of 178


FF-Classroom 23,24,26 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................... FF-Classroom 23,24,26
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 23,24,26 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 31 of 178


FF-Classroom 23,24,26 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 563.9 - - 199.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 32 of 178


FF-Classroom 25 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 25
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 25 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 33 of 178


FF-Classroom 25 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 585.8 - - 202.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 34 of 178


FF-Classroom 27-33,35-56 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name .................................................. FF-Classroom 27-33,35-56
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Classroom 27-33,35-56 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 35 of 178


FF-Classroom 27-33,35-56 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 593.1 - - 204.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 11.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 36 of 178


FF-Classroom 34 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 34
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Classroom 34 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 37 of 178


FF-Classroom 34 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 662.7 - - 205.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 12.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 38 of 178


FF-Classroom 57 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 57
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 57 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 39 of 178


FF-Classroom 57 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 455.0 - - 155.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 9.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 40 of 178


FF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................................... FF-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 41 of 178


FF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 670.8 - - 35.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 18.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 42 of 178


FF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................................... FF-Corridor 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Corridor 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 43 of 178


FF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1310.7 - - 95.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 6.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 34.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 44 of 178


FF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................................... FF-Corridor 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Corridor 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 45 of 178


FF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1089.9 - - 74.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 28.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 46 of 178


FF-Head of Department Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................... FF-Head of Department
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Head of Department x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 47 of 178


FF-Head of Department Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 376.1 - - 80.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 5.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 48 of 178


FF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ................................................................... FF-Laboratories
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Split Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 49 of 178


FF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 362.9 - - 40.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 50 of 178


FF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ...................................................................... FF-Split Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Split Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 51 of 178


FF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 362.9 - - 40.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 52 of 178


FF-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ...................................................................... FF-Staff Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Staff Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 53 of 178


FF-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 188.3 - - 23.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 54 of 178


FF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ...................................................................... FF-Supervisor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Supervisor x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 55 of 178


FF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 172.1 - - 21.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 3.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 56 of 178


FF-Supervisor SV7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .............................................................. FF-Supervisor SV7
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Supervisor SV7 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 57 of 178


FF-Supervisor SV7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 265.8 - - 39.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 58 of 178


FF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ............................................................. FF-Teacher's Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Teacher's Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 59 of 178


FF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 339.6 - - 38.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 60 of 178


GF-Ablution Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .......................................................................... GF-Ablution
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Ablution x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 61 of 178


GF-Ablution Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.0 - - 19.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 3.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 62 of 178


GF-Book Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ..................................................................... GF-Book Store
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Book Store x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 63 of 178


GF-Book Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 308.3 - - 66.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 64 of 178


GF-CCC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ................................................................................ GF-CCC
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-CCC x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 65 of 178


GF-CCC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 66 of 178


GF-Class Room 1-18 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ........................................................... GF-Class Room 1-18
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Class Rooms 1-18 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 46.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 67 of 178


GF-Class Room 1-18 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 629.2 - - 207.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 68 of 178


GF-Class Room 19 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .............................................................. GF-Class Room 19
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Class Room 19 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 69 of 178


GF-Class Room 19 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 477.1 - - 155.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 9.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 70 of 178


GF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 71 of 178


GF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 670.8 - - 35.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 18.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 72 of 178


GF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 73 of 178


GF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 978.0 - - 63.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 25.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 74 of 178


GF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 75 of 178


GF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 523.7 - - 21.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 14.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 76 of 178


GF-Corridor 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 77 of 178


GF-Corridor 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 632.4 - - 31.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 17.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 78 of 178


GF-Corridor 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 5
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 5 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 79 of 178


GF-Corridor 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 405.3 - - 10.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 80 of 178


GF-Corridor 6 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 6
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 6 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 81 of 178


GF-Corridor 6 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 405.3 - - 10.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 82 of 178


GF-Corridor 7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 7
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 7 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 83 of 178


GF-Corridor 7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 405.3 - - 10.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 84 of 178


GF-CTM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ................................................................................ GF-CTM
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-CTM x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 85 of 178


GF-CTM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 86 of 178


GF-Files Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ..................................................................... GF-Files Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Files Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 87 of 178


GF-Files Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 195.5 - - 16.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 88 of 178


GF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .................................................................. GF-Laboratories
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Laboratories x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 89 of 178


GF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 626.7 - - 218.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 90 of 178


GF-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ............................................................................ GF-Library
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Library x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 91 of 178


GF-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1334.3 - - 275.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 17.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 29.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 92 of 178


GF-Manager Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ......................................................................... GF-Manager
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Manager x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 93 of 178


GF-Manager Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 361.6 - - 35.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 94 of 178


GF-Manager Waiting Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ........................................................... GF-Manager Waiting
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Manager Waiting x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 95 of 178


GF-Manager Waiting Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 96 of 178


GF-Meeting RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name .................................................................. GF-Meeting RHS
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Meeting RHS x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 97 of 178


GF-Meeting RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 223.0 - - 20.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 98 of 178


GF-Mosque Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ........................................................................... GF-Mosque
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Mosque x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 99 of 178 99


GF-Mosque Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1363.0 - - 289.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 18.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 30.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 100 of 178 100


GF-Music Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................................... GF-Music Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Music Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 101 of 178


GF-Music Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 732.7 - - 196.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 16.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 102 of 178


GF-Office RHS NE Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ............................................................... GF-Office RHS NE
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Office-RHS NE x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 103 of 178


GF-Office RHS NE Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 385.1 - - 48.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 3.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 104 of 178


GF-Office Small RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ........................................................... GF-Office Small RHS
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Office Small RHS x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 105 of 178


GF-Office Small RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 69.4 - - 7.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 1.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 106 of 178


GF-Pantry Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ............................................................................. GF-Pantry
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Pantry x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 107 of 178


GF-Pantry Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 82.0 - - 6.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 1.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 108 of 178


GF-PM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................................................... GF-PM
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-PM x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 109 of 178


GF-PM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 110 of 178


GF-PTC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................................................. GF-PTC
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-PTC x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 111 of 178


GF-PTC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 235.2 - - 27.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 112 of 178


GF-Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ....................................................................... GF-Reception
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Reception x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 113 of 178


GF-Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 674.6 - - 88.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 5.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 16.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 114 of 178


GF-Reception Lower Right Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................. GF-Reception Lower Right
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Reception Lower RHS x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 115 of 178


GF-Reception Lower Right Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 400.0 - - 69.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 116 of 178


GF-Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name .............................................. GF-Room Across Reception
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Room Across Reception x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 117 of 178


GF-Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 266.9 - - 43.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 118 of 178


GF-Security Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name .......................................................................... GF-Security
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Security x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 119 of 178


GF-Security Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 227.1 - - 16.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 120 of 178


GF-Sm. Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ....................................... GF-Sm. Room Across Reception
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Sm. Room Across Rec. x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 121 of 178


GF-Sm. Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 130.8 - - 20.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 122 of 178


GF-Social Councillor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ........................................................... GF-Social Councillor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Social Councillor x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 123 of 178


GF-Social Councillor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 124 of 178


GF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Split Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Split Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 125 of 178


GF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 362.9 - - 40.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 126 of 178


GF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 127 of 178


GF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 256.7 - - 10.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 128 of 178


GF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 129 of 178


GF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 328.1 - - 16.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 130 of 178


GF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 131 of 178


GF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 223.0 - - 12.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 132 of 178


GF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 133 of 178


GF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 281.7 - - 11.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 134 of 178


GF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 5
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 5 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 135 of 178


GF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 342.3 - - 14.7

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 136 of 178


GF-Student Affairs Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name .............................................................. GF-Student Affairs
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Student Affairs x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 137 of 178


GF-Student Affairs Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 138 of 178


GF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Supervisor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Supervisor SV1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 139 of 178


GF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 104.7 - - 17.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 140 of 178


GF-Supervisor SV1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name .............................................................. GF-Supervisor SV1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Supervisor SV1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 141 of 178


GF-Supervisor SV1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 104.7 - - 17.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 142 of 178


GF-Supervisor SV2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name .............................................................. GF-Supervisor SV2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Supervisor SV2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 143 of 178


GF-Supervisor SV2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 265.8 - - 39.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 144 of 178


GF-SW Entrance Low Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name .......................................................... GF-SW Entrance Low
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-SW Entrance Lower x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 145 of 178


GF-SW Entrance Low Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 862.4 - - 123.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 7.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 21.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 146 of 178


GF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ............................................................ GF-Teacher's Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Teacher's Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 147 of 178


GF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 339.6 - - 38.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 148 of 178


GF-Uniform Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name .......................................................................... GF-Uniform
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Uniform x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 149 of 178


GF-Uniform Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 194.9 - - 57.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 3.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 150 of 178


RF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 151 of 178


RF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 285.3 - - 10.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 152 of 178


RF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 153 of 178


RF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 368.6 - - 16.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.5 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 154 of 178


RF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 155 of 178


RF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 256.7 - - 12.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 156 of 178


RF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 157 of 178


RF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 308.5 - - 11.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 158 of 178


RF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 5
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 5 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 159 of 178


RF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 380.3 - - 14.7

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 160 of 178


SF-Classroom 71 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ................................................................. SF-Classroom 71
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Classroom 71 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 161 of 178


SF-Classroom 71 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 662.7 - - 205.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 12.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 162 of 178


SF-Classrooms 58,60 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name .......................................................... SF-Classrooms 58,60
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Class Rooms 58,60 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 163 of 178


SF-Classrooms 58,60 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 710.5 - - 210.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 164 of 178


SF-Classrooms 59 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ............................................................... SF-Classrooms 59
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Class Rooms 59 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 165 of 178


SF-Classrooms 59 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 568.1 - - 203.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 166 of 178


SF-Classrooms 61,62 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name .......................................................... SF-Classrooms 61,62
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Class Rooms 61,62 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 167 of 178


SF-Classrooms 61,62 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 563.9 - - 199.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 168 of 178


SF-Classrooms 63-70, 72-84 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ............................................... SF-Classrooms 63-70, 72-84
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Classroom 63-70,72-84 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 169 of 178


SF-Classrooms 63-70, 72-84 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 593.1 - - 204.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 11.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 170 of 178


SF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ....................................................................... SF-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 171 of 178


SF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1310.7 - - 95.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 6.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 34.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 172 of 178


SF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ....................................................................... SF-Corridor 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Corridor 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 173 of 178


SF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1089.9 - - 74.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 28.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 174 of 178


SF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ................................................................... SF-Laboratories
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Laboratories x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 175 of 178


SF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 626.7 - - 218.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 176 of 178


SF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 01:00AM

1. General Details:
Air System Name ............................................................. SF-Teacher's Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Teacher's Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 177 of 178


SF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 01:00AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 368.9 - - 40.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 178 of 178