220KV 17 Meter
400KV 27 Meter
Low High
11KV 1300 mm
33KV 1300 mm
66KV 2200 mm
132KV 3000 mm
220KV 4500 mm
400KV 7000 mm
Insulator String:
Voltage No of Suspension Length (mm) No of Disc for Tension Length in (mm)
String String
Nominal Span:
Voltage Normal Span (Meter)
66KV 240-250-275
132KV 315-325-335
220KV 315-325-335
400KV 315-325-335
66KV 5.5
132KV 6.1
220KV 7.0
400KV 8.0
800KV 12.4
Distance Descriptions
0.9 Meter Horizontally between any item of equipment and thesubstation wall
132/33/11KV up to 8 3 O/L relays + 1 E/L 2 O/L relays + 1 E/L Buchholz, OLTC Buchholz, OT, WT
MVA relay relay
132/33/11KV above 8 3 O/L relays + 1 dir. 3 O/L relays + 1 E/L Differential, Buchholz,
MVA and below 31.5 E/L relay relay OLTC Buchholz, OT, WT
MVA
132/33KV, 31.5 MVA & 3 O/L relays + 1 dir. 3 O/L relays + 1 E/L Differential, Over flux,Buchholz,
above E/L relay relay OLTC PRV, OT, WT
220/33 KV, 31.5MVA & 3 O/L relays + 1 dir. 3 O/L relays + 1 dir. Differential, Over flux,Buchholz,
50MVA 220/132KV, 100 E/L relay relay OLTC PRV, OT, WT
MVA
400/220KV 315MVA 3 directional O/L 3 directional O/L Differential, Over flux,Buchholz,
relays (with dir. relays (with dir. OLTC PRV, OT, WT and overload
High set) +1 High set)+1 (alarm) relay
directional E/L directional E/L
relays. Restricted relays. Restricted
E/F relay + 3 E/F relay
Directional O/L
relays for action
The bottom most portion of any insulator or bushing in service should be at a minimum height of 2500 mm above ground
level.
Location of L.A (From T.C Bushing):
Voltage BIL KV Peak Distance (Mt)
11KV 75 12
33KV 200 15
66KV 325 24
132KV 550 35