Académique Documents
Professionnel Documents
Culture Documents
GmbH
Information & Communication Systems
IEC 61850 & IEC 61400-25 SCC
Motivation: The standards IEC 61850 Communication networks and systems for power utility automation and IEC 61400-25
sustainable Communications for monitoring and control of wind power plants provide support for sustainable interopera-
bility: Information Models, Information Exchange Methods, Protocol Mappings, and System Configu-
interoperability
ration Language (SCL) for Power Systems (Generation, Transmission, and Distribution for HV, MV, and LV, ).
Data Models Logical Nodes (LN) represent real-world Inputs, Outputs, Ratings, and Settings of functions or equipment.
A LN provides a list of named data objects (DO). The LN XCBR represents a real circuit breaker with the data
object (DO) Pos (Position). IEC 61850-7-2 defines Information Exchange Methods, e.g., for the position
IEC 61850-7-4xx (with Client/Server services, GOOSE, SMV). Data flow is specified by a SCL file (IEC 61850-6).
Substations (7-4) Logical device
160 LN CC CIM 61850-7-2
services
IEC 61968/70
900 DO IED Description (online)
Virtual World
virtualization
GOOSE/SMV Layer 2
IED Description (off-line)
WTUR
63 LN
XCBR Network
What ?
350 DO
Confiruration file (SCL); part 6
XCBR
Information Logical node, data OpCnt
SCSM, e.g.
Models objects, and common data 61850-8-1 Pos
classes; parts IEC 61850- ...
Decentralized 7-4 and 7-3, 61400-25-2
or 9-2
QE3
QC1 Real
Energy Res. (420) Information exchange 61850-7-4 logical
QE2
QA1
devices in
substation
50 LN Abstract communication QE1
node (circuit breaker) 61850-7-4 data
(publ./subscr., get, set, T1 or wind
service interface (ACSI); (position) QB1
turbines
450 DO control, ... reporting,
logging, get IED
part 7-2 and 61400-25-3
description) When ?
61850-6 SCL configuration file
in IEC 61400-25-4
Communication real world diagram
Objects (topology)
16 LN Client/ Mappings
messages
messages
subscriber
How ?
250 DO Communication
Information
Exchange
Mapping
real world
Network Services to models
Example see reverse side
Example: Measurement LN MMXU represents power, voltages, currents, impedances, in a three-phase electrical system. The values
can be communicated by various services. The LN MMXU comprises values for measurements, monitoring, configuration, set-
tings, description, and substitution. These values can be communicated by various services like read (polling), reporting, GOOSE,
logging and log query. Recording and logging are build upon monitored value changes. The SCL configuration file .SCD (System
Configuration Description) specifies the single line diagram of the substation, the information model, the parameters of the con-
trol blocks for reporting and logging, GOOSE, SV, the binding to the process and the data flow.
Mapping
Report TotVA Total Apparent Power (Total S)
phsB.cVal
TotPF Average Power factor (Total PF) MMS TCP/IP MMS LN
Hz
phsC.cVal
Frequency
Network LN LN
SV
QE3 (Status
samples/sec Value)
QC1
QA1 FALSE
tn tn+1 tn+2 tn+3 Time
QE1
current / voltage samples from instrument
T1 transformers by sampled value exchange
QB1
services of IEC 61850-7-2 / IEC 61850-9-2
(e.g., from Merging Unit)