Subject: 48583 Power Systems Operation and Protection

Assessment Number: 2

Assessment Title: Assignment 2 CB Transient Analysis

Students Name and Number


Student Family Name First Name
Number

Declaration of Originality:
The work contained in this assignment, other than that specifically
Marks
attributed to another source, is that of the author(s). It is recognised that,
should this declaration be found to be false, disciplinary action could be
taken and the assignments of all students involved will be given zero
marks. In the statement below, I have indicated the extent to which I
have collaborated with other students, whom I have named. Circuit /2
Statement of Collaboration:
Equations /2

Algorithm /3

Solution /3

TOTAL /10

Signature(s)
key
Office use only

Assessment Submission Receipt


Assessment Title: Assignment 3 CB Transient Analysis
Students Name:
Date Submitted:
Tutor Signature:
A2.1

Assignment 2 CB Transient Analysis

The diagram shows a 3-phase generator supplying a delta connected load via a
cable.

CB cable
G load

generator

Circuit parameters:

Generator Cable Load

Inductance ( H ) 800 245 600

Cap. to earth ( F ) 0.66 - 0.05

The generator neutral which is not earthed has a capacitance to earth


CN 0.46 F .

The circuit breaker (CB) opens to break balanced load current I 1sin 100t .

Determine the source side and load side voltage transients and hence obtain the
re-striking voltage across the CB when:

(i) the first phase clears.

(ii) the second and third phases clear.

Write a brief report including:

(a) Circuit (and possible reduction). Equations to be solved.

(b) Algorithm used to solve the problem.

(c) Solution graphs of CB voltages versus time.

You will be required to demonstrate your work individually.