Vous êtes sur la page 1sur 2

LIPICO TECHNOLOGIES PTE. LTD.

61, Bukit Batok Crescent


#06-03 to #06-06, Singapore 658078
Tel: +65 6316 7800, Fax: +65 6316 7830, Email: sg.enquiry@lipico.com

COOLING TOWER WATER CIRCULATION RATE

Customer PT. Industri Nabati Lestari


Plant 2,000 MTD PHYSICAL REFINING PLANT
Contract no INL/SPJ/02/2016
Project no. S16249P
Date 19/11/2016
Revision no. 0

PRE-TREATMENT & BLEACHING SECTION


Normal,
S/N Tag Item Description Max, m3/h Remarks Notes
m3/h
1 SE611 Vacuum Condenser 94 105 Recirculated Barometric Water
2 VP611 Vacuum Pump 3 3 Recirculated Barometric Water

DEODORISATION SECTION
Normal,
S/N Tag Item Description Max, m3/h Remarks Notes
m3/h
1 SE731 Vacuum Condenser 600 660 Recirculated Barometric Water
2 VP731 Vacuum Pump 3 3 Recirculated Barometric Water
3 HE751 Fatty Acid Distillate Cooler 105 110 Recirculated Clean Water
4 HE742 Final Oil Cooler 90 260 Recirculated Clean Water
5 PU721 Hot Oil Transfer Pump 2.5 3.0 Recirculated Clean Water
6 PU731 Hot Oil Transfer Pump 2.5 3.0 Recirculated Clean Water

UTILITY SECTION
Normal,
S/N Tag Item Description Max, m3/h Remarks Notes
m3/h
Make-up water rate, 0.005% drift
1 CT781 Clean Cooling Tower - 7.6
loss + 1.5% eveporation loss
Make-up water rate, 0.02% drift loss
2 CT791 Barometric Cooling Tower - 15.5
+ 1.5% eveporation loss

3
Total Recirculated Barometric Water 700 771 m /hr
3
Total Recirculated Clean Water for Process 200 376 m /hr
3
Estimated Make-up Water (for cooling tower) - 23 m /hr

Note :
1. The above circulation rate are actual design data without safety margin.
2. Clean cooling towers should have at least 25% higher margin.
3. Barometric cooling towers should have at least 30% higher margin.
4. Design of clean cooling tower for process: inlet temperature is 42C, outlet temperature 32C.
5. Design of barometric cooling tower: inlet temperature 39C, outlet temperature 32C.
6. Incoming pressure for the clean cooling water should be 3 barg at the plant battery limit.

Page 1 of 2
LIPICO TECHNOLOGIES PTE. LTD.
61, Bukit Batok Crescent
#06-03 to #06-06, Singapore 658078
Tel: +65 6316 7800, Fax: +65 6316 7830, Email: sg.enquiry@lipico.com

COOLING TOWER WATER CIRCULATION RATE

Customer PT. Industri Nabati Lestari


Plant 2,000 MTD PHYSICAL REFINING PLANT
Contract no INL/SPJ/02/2016
Project no. S16249P
Date 19/11/2016
Revision no. 0

7.a) Quality standard of make-up water


pH (25oC) 6.0 ~ 8.0
Electric Conductivity (25oC) (S/cm) 300 or less
Chloride Ions (mgCl-/litre) 25 or less
Sulfate Ions (mgSO2-/litre) 50 or less
Acid Consumption (pH4.8) (mgCaCO3/litre) 50 or less
Total Hardness (mgCaCO3/litre) 70 or less
Calcium Hardness (mgCaCO3/litre) 50 or less
Ionized Silica (mgSiO2/litre) 30 or less

7.b) Quality Standard of Cooling Water


pH (25oC) 6.5 ~ 8.2
Electric Conductivity (25oC) (S/cm) 800 or less
Chloride Ions (mgCl-/litre) 100 or less
Sulfate Ions (mgSO2-/litre) 200 or less
Acid Consumption (pH4.8) (mgCaCO3/litre) 100 or less
Total Hardness (mgCaCO3/litre) 200 or less
Calcium Hardness (mgCaCO3/litre) 150 or less
Ionized Silica (mgSiO2/litre) 50 or less

Page 2 of 2