Académique Documents
Professionnel Documents
Culture Documents
Single and multiple burner boilers require two independent control systems. One system
to control steam production and one to control the fuel burning equipment. The Human
Machine Interface (HMI) is accomplished with, off the shelf, PCs using Wonderware
software.
The first of the two required control systems is the Boiler Control System. The national
Fire Protection Association defines a boiler control system as The group of control
systems that regulates the boiler process, including the combustion control system but
not the burner management system. The combustion control system is The control
system that regulates the furnace fuel and air inputs to maintain the air-fuel ratio within
the limits that are required for continuous combustion and stable flame throughout the
operating range of the boiler in accordance with demand.
COMBUSTION CONTROL
Combustion is controlled by adjusting the fuel flow and combustion air flow to meet the
demand for steam while maintaining the proper ratio of air-to-fuel. The steam demand
signal sets the demand for fuel. The combustion air demand signal comes from an air-to-
fuel ratio controller. Therefore, the control scheme essentially sets the fuel flow to meet
the demand for steam and sets the air flow in ratio to the fuel.
This simple control scheme has a rather basic problem, especially when operating the
boiler at the ragged edge where efficiency is highest. The optimum air-to-fuel ratio is one
at which the combustion air rate is just sufficient to provide complete combustion.
Therefore, the slightest negative deviation in the air rate can cause a significant increase
in carbon monoxide and/or unburned hydrocarbons. Larger deviations can even result in
an explosive mixture.
The solution to this problem is a cross-limiting control scheme in which the air rate leads
the fuel on a demand increase, and lags the fuel on a demand decrease. Therefore, air is
never deficient during load changes. Furthermore, the air demand signal is limited to a
minimum air rate to prevent combustion problems at low steam demand.
Since air flow control is so important to efficient boiler operation, the boiler control
system closely monitors the air flow controller mode. If the controller is put into manual,
the control system is essentially disconnected from setting the air flow. Therefore, the
control system switches air-to-fuel ratio control to the fuel flow and forces the steam
demand signal to track the fuel.
The control scheme can also interface with the Burner Management System (BMS). The
BMS sends signals to the combustion controls to pre-position the FD fan damper and the
fuel control valve for various BMS functions, such as shutdown, boiler purge, and burner
light-off.
Depending on the fuels involved the fuel safety control can be made up of the following:
1. Master fuel trip
2. Igniter fuel trip
3. Gas fuel trip
4. Oil fuel trip
PRELIGHT CONTROL
Prelight control is responsible for insuring all predetermined boiler common conditions
are satisfied prior to placing any fuel in service. Once the boiler purge has been
completed and the master fuel trip has been reset, the prelight control insures that
individual fuel and air conditions are satisfactory for igniter and burner operation. Some
examples of prelight permissive conditions are:
1. Master fuel trip relay is reset
2. Igniter fuel pressure is adequate
3. Burner fuel pressure is adequate
BURNER CONTROL
The burner(s) is/are placed in service in a predetermined timed sequence. The operator
may initiate the burner lighting sequence by actuation of a control switch on the operator
interface or in the case of a single burner boiler burner lighting may be initiated
automatically at the completion of the boiler purge and resetting of the master fuel trip
relay. This starts the burner lighting timer, typically twenty five seconds for a gas burner
(oil burner lighting times could be longer). A signal is generated to energize the ignition
transformer or sparking device for five to eight seconds and opens the igniter valves.
Flame must be detected by the end of five to eight second ignition time or the lighting
will be terminated. When ignition is established the burner valves are opened. At the
completion of the burner lighting time the igniter is removed from service unless it is a
class one or class two igniter. The burner will remain in service provided the flame
remains detected and the burner valves remain open as indicated by a limit switch.
Typically the following are displayed to the operator on the operator interface.
1. Igniter in service
2. Flame detected
3. Burner valve position