Vous êtes sur la page 1sur 31

< Chapter I The design capacity of the

conveyance, regulating, and water


General Requirements and Design measurement structures Civil Engineer,
Considerations Hydraulic Structures Branch, Bureau of
A. J. AISENBREY, JR. Reclamation. Discussed throughout this
publication is limited to 100 cubic feet per
A. GENERAL REQUIREMENTS second.

l-l. Purpose.-To fulfill a project purpose of (a) Conveyance Structures. -In


producing crops or increasing crop addition to the canal itself, it is usually
production, water delivery to the land must necessary, because of topography or existing
be provided by a reliable and efficient manmade features, to use inline canal
irrigation system. A sun-drenched, parched structures to convey water along the canal
soil may need only water to change it from a route. Such structures include: (1) inverted
sparsely vegetated, thirsty desert to a high- siphons to convey canal water under natural
yield crop, farmland oasis as illustrated in channels, (2) road crossings to carry canal
figure 1-l. An increased crop yield of water under roadways, (3) bench flumes to
premium quality is very likely if the proper conduct the water along a steep hillside, and
amount of moisture is made available to the (4) drop or chute structures to safely lower
crop when needed. (See fig. l-2). the canal water down a hillside.

A canal is frequently used to convey water (b) Regulating Structures. -


for farmland irrigation. In addition to Regulation of canal discharge begins at the
transporting irrigation water, a canal may source of water supply. This may be a canal
also transport water to meet requirements headworks structure adjacent to a diversion
for municipal, industrial, and outdoor dam on a stream or river, a turnout from a
recreational uses. A variety of recreation is larger canal, or a pumping plant located on a
provided by reservoirs as shown in figures l-3 reservoir or large canal. Downstream from
and 1-4. the source of water supply, regulation of
canal discharge is primarily controlled by
The conveyance canal and its related
outflow through turnout structures. Where
structures should perform their functions
canal flow is to be divided and directed in
efficiently and competently with minimum
several directions, division structures are
maintenance, ease of operation, and
used to regulate the discharge in each
minimum water loss.
direction. Wasteway structures also are used
l-2. Structures. -Many different types to control flow in a canal; however, they are
of canal structures are required in an more commonly thought of as protective
irrigation system to effectively and efficiently structures as their primary function is to
convey, regulate, and measure the canal discharge excess canal flows and thereby
discharge and also to protect the canal from protect the canal from damage.
storm runoff damage.
Regulating structures are also
capable of raising the canal water surface
higher than would normally exist when the commonly used in conjunction with a
canal is flowing higher than would normally turnout and therefore is discussed in detail
exist when the canal is flowing with regulating structures. Selection of the
type of structure best suited for a particular
installation is discussed in chapter V. (d)
Protective Structures.-Provisions must be
made in an open irrigation system to

GENERAL REQUIREMENTS AND


DESIGN CONSIDERATIONS 3

Figure 1-1. Open canal system


supplying irrigation water to citrus groves,
Gila Project, Arizona. PSO-300-l0S86

At less than design capacity. A check


structure, for example, is used to raise the
canal water surface when the canal is flowing
at partial capacity so that a turnout structure
may still deliver its designed capacity. Check
structures are spaced at appropriate
intervals along a canal to provide this
Figure 1-2. Irrigating corn using
capability

(c) Water Measurement Structures.-


Efficient management of an irrigation system
insists that measurement of the rate-of-flow
and volume delivered be made. Equitable
water distribution to the users is a primary
consideration. Water measurement also
tends to prevent unnecessary wasteful water
management practices, thereby enhancing
the conservation of this great natural
resource. Several types of water
measurement structures or devices are used. siphon tubes, Red Willow Unit, Nebraska.
Parshall flumes, weirs, weir boxes, open-flow P328-701-6140
meters, and constant head orifices are the
more common types. The constant head
orifice, although sometimes used as an inline
Figure 1-3. Boating on the Rogue
canal water measurement structure, is more
River Project, Oregon. C448-100-148
appropriate pipe material is dependent on
several considerations discussed later in
chapter VIII.

(2) Pipe appurtenances. -


Appurtenances include such items as pipe
collars, air vents, blowoffs, manholes, and
are discussed later in chapter VIII.

(3) Transitions. -Transitions connect


a canal or natural channel to a structure inlet
Figure 1-4. Fishing on Hungry Horse or structure outlet. Several different
Reservoir, Montana. C447-100-S0 transition configurations of reinforced
concrete are used. Earth transitions are used
Externally protect from damage by
as required to vary base widths and invert
the canal on the uphill side storm runoff
slopes. See chapter VII for a detailed
water, and internally protect the canal from
discussion of transitions.
excess canal flows caused by storm waters
entering the canal, or by misoperation of the (4) Energy dissipators. -Energy
canal system. Cross-drainage structures and dissipators are used at the outlet ends of
waterways provide this protection. Cross- drop or chute structures to dissipate excess
drainage structures are used to direct storm energy. Energy dissipation may be achieved
runoff flows under the canal through by a hydraulic jump in a stilling pool or by
culverts, over the canal in overchutes, or into impact in a baffled outlet. Excess energy may
the canal by drain inlets. Waterways also be dissipated by a hydraulic jump within
evacuate excess canal flows over side a pipe; by impact in a baffled apron; by
channel spillways. Through radial gated impact and valve losses in a high-head
spillways, or through siphon spillways. vertical energy dissipator; or simply by a
vertical drop of a few feet into a pool of
(e) Structure Components and
water. Energy dissipators are discussed in
Appurtenances. -Nearly all canal structures
detail in chapter VI.
are made of several different structural parts
which together make up the complete (5) Safety features. -Safety features
structure. These parts, (components and are used to prevent humans, livestock, and
appurtenances) include: wildlife from entering a canal and canal
structures, and also to assist in their escape if
(1) Pipe.-Pipe is commonly used for
inadvertently entered. Various types of
that part of a structure placed underground
fencing, guardrail, nets, racks, ladders, and
and which may or may not be subjected to
signs are used as safety precautions. See
internal hydrostatic bursting pressure. Pipe is
chapter IX for a more detailed discussion of
made from one of several different materials
canal safety features.
such as reinforced concrete, asbestos
cement, welded steel, corrugated metal, or 1-3. Other Requirements.-Many
reinforced plastic mortar. Selection of the requirements vital to a complete and
competent design of a canal water-delivery
system are beyond the scope of this
publication. However, the more basic
considerations are briefly discussed in this
section to remind or acquaint the reader of
other essential design data requirements.

(a) Canal.-Design capacity for an


irrigation canal is determined by the
maximum water demand which is primarily
dependent on the following considerations: Figure 1-5. Irrigating sugar beets on
(1) the area to be irrigated, (2) crops to be the Boise Project, Idaho. C4-10o-I88
grown, (3) rotation or demand system for
turnout deliveries, (4) water losses from
evaporation and seepage, and (5) anticipated
efficiency of water application to the crops.
Records of actual water use for conditions
similar to the system to be designed are
valuable guides for estimating the quantity
of water required for each acre. Soil
characteristics and climatic conditions should
also be evaluated. Figure l-5 shows furrow
Figure 1-6. Sprinkler irrigation in the
irrigation of crops from a header ditch, and
Coachella Valley, California. LC830
sprinkler irrigation is shown in figure l-6.

Location of the canal with respect


to the land to be irrigated is primarily
influenced by topography and economic
considerations. If, for example, water
delivery cannot be made by gravity, the
additional cost of pumping would be
included in an economic study. Figure l-7
shows water delivery by gravity from the
canal, through a turnout, to the farmland. Figure J -7. Irrigating frJ.rit on the
Considerations for the selection of the canal Yakima Project, Washington. C-33-IOO-80
hydraulic properties include erosion Operational flexibility and
resistance for the banks and invert of an economics. The need for canal lining and
earth canal, sideslope stability, hydraulic selection of the type of lining are also
efficiency, determinations which must be made.

(b) Other Structures. -Detailed


discussions of structures such as tunnels,
bridges, utility crossings, and fish screens and Soils investigation along a canal and
fish ladders are not included herein. at structure sites is required to: ( I) identify
the soil materials to be excavated, (2)
Tunnels are used where it is more identify the soil for potential use as canal
economical to convey canal water through a embankment, (3) determine the foundation
ridge or hill than to: (I) pump water over the adequacy for canal structures and lining, ( 4)
obstruction, (2) convey the water along the determine the need for canal lining, (5)
hillside or around the ridge, or (3) construct a determine canal sideslope stability, (6) assess
canal section requiring a very deep cut. erosion resistance characteristics, (7)
Bridges for roadway traffic over a determine underdrain requirements for lined
canal are generally used for canals of much canals, and (8) determine water-soluble
greater capacity than 100 cubic feet per sulfate ion concentrations.
second. However, if the monetary value of Soil material to be excavated has one
hydraulic head in the canal system is
of two classifications: rock or common (soil).
particularly high, a cost comparison of a The materials remolded and used for canal
bridge and a road crossing structure may be embankment construction should ideally be
warranted as the head loss through a pipe nonexpansive, possess adequate remolded
road crossing could be significant. shearing strength, be relatively impervious,
Utility crossing structures are and relatively erosion resistant if hard-
provided for existing utilities such as gas, oil, surface canal lining is not used. The soil in its
water, sewage, electricity, and natural state should also possess these
communication lines. Utility lines may cross qualities. It is sometimes necessary to locate
over or under the canal, and frequently a source of borrow material for canal
require special design considerations to embankment, for backfill adjacent to
comply with the utility owner's requirements structures, and for foundation pads under
and the canal design criteria. the structures.

Fish screens and ladders are special The reaches of a canal which traverse
structures at or near the source of canal low density soils highly susceptible to
water supply. Screens exclude fish from a hydrocompaction should be well delineated.
canal whereas ladders permit migration in In addition, the depth to subsurface water
the natural channel. levels if present in any exploration hole
should be recorded.
(c) Soils Exploration. -The following
very generally and briefly discusses some of Canal structures discussed in this
the more important considerations publication are relatively small and
associated with a soils exploration program. consequently foundation pressures are quite
Methods and procedures for drilling, low. Therefore, structure settlement caused
sampling, and testing are also very important by foundation consolidation will usually be
[ I] .2 small in magnitude. Foundation treatment
however, may be required to protect the
structure from expansive soils or from
undesirable settlement of low-density ( f) Operation md Maintenance. -In a
material. Bureau of Reclamation designed system, a
designers operating criteria (DOC) is usually
Sulfate concentrations in the soil provided to assist operation and
samples and water samples indicate the maintenance (O&M) personnel in adequately
relative degree of potential sulfate attack on protecting the canal system from
concrete [2). Specifying the appropriate type unnecessary damage which could otherwise
of cement used in the concrete mix is usually be caused by misoperation or inadequate
all that is required to safeguard the concrete. maintenance. A rigorous maintenance
Fly ash is also sometimes used in the program should include control of weeds,
concrete mix for sulfate resistance [3). aquatic growths, insects, and pests.
Although a well planned and Experience has shown that a well maintained
executed soils exploration program may be and operated canal system usually has
conducted, an admonishment by the dedicated personnel-people who are justly
eminent soils engineer Karl Terzaghi must proud of their work and take pride in what
always be borne in mind: . . Results of they do---people who curt.
subsurface exploration still leave a wide
B. DESIGN CONSIDERATIONS
margin for interpretation. [4) Sound
judgment is a requisite in all soil exploration 1-4. General. -Canal structures which have
programs. been standardized in this publication, show
concrete dimensions and reinforcement
(d) Hydrology.-The canal system steel, and are appropriately sized to provide
should be reasonably well protected from for hydraulic, structural, and stability design
damage which could occur from storm
considerations.
runoff. The runoff area contributing to a
natural drainage channel, the ground slope Hydraulic design provides: (1) adequate
and vegetative density of the area, and discharge capacity for inline canal structures,
storm frequency to be used for design are all when properly selected and hydraulically set,
influential in determining the design capacity to convey the flow at normal canal water
for cross drainage structures. depths, (2) adequate built-in overflow
capacity for inline canal structures to limit
(e) Sedimentation. -Aggradation and infringement on the canal bank freeboard for
degradation studies for a natural drainage emergency operation or misoperation of the
channel provide the necessary data to canal, (3) adequate structural proportioning
determine earth cover required, for example, and appropriate hydraulic setting of
over the top of the pipe for an inverted structures to permit excess energy
siphon extending under the drainage
dissipation with minimum water turbulence
channel. Degradation, if extensive enough at the downstream ends of the structures,
could cause an empty pipe to float; whereas and (4) structural proportioning of certain
aggradation could create external earth
transitions to minimize hydraulic head loss.
loads great enough to crack or otherwise
damage the pipe.
Structural design provides: appropriate Which are above and below the water level
concrete thicknesses and reinforcement in a soil mass, the terms dry and saturated
steel patterns for structural members to are used. Obviously the soil adjacent to a
resist bending moment, thrust, and shear structure is not ovendry and does possess
stresses imposed by reasonable loads on the certain moisture content.
structure.
1-7. Operating Deck Uniform Live
Stability design provides: adequate structure Loads.
dimensions so that for most soil foundation
materials, the structure will: (1) resist sliding -Operating decks for structures using
and overturning, (2) prevent percolating stoplogs are designed for a uniform live load
water from removing foundation materials, of 150 pounds per square foot; otherwise a
and (3) provide foundation pressures less uniform live load of 100 pounds per square
than the maximum allowable bearing foot is used. Decks for radial gate hoists
require special structural design
pressure.
considerations which are not included
Design examples for structures which have herein.
not been standardized illustrate a
recommended hydraulic design procedure, 1-8. Lateral Pressures.
but exclude structural design and stability -Lateral pressures from several
analysis. different sources are imposed on walls of
1. Loads structures. Resultant forces from these
pressures must be adequately resisted by the
1-5. General.-Loads which canal reinforced concrete.
structures must capably resist include
dead load weights, live loads on (a) Water. -A fluid pressure of 62.4
operating decks, lateral pressures, pounds per square foot (psf) per foot of
bursting and uplift pressures, and wheel depth is caused by water. The pressure
diagram is triangular with the resultant force
loads.
acting at one-third the height above the base
1-6. Dead Load Weights.-Commonly of the pressure diagram.
used dead load weights for small canal
structures are presented in the following (b) earth.-Active earth pressures may
be determined using Rankines solution of
tabulation:
Coulombs equation [5). The pressure
Load Weight, (Ibs./cu. ft.) diagram is assumed to be triangular, the
water 62.4 same as for water, with the resultant force
Backfill Dry 100 acting at one-third the height above the base
Saturated 125 of the pressure diagram. Because of this
Compacted backfill 120
similarity with the fluid pressure of water,
Dry
the pressure caused by earth is sometimes
Saturated 135
Concrete 150 referred to as an equivalent fluid pressure.
Standardized canal structures have and are therefore particularly significant in
been structurally designed to resist moist the stability analysis.
earth active lateral pressure equal to 30 psf
per foot of depth and saturated earth active Stilling pool floors, for example, are
lateral pressure of 85 psf per foot of depth. subjected to uplift pressure from
Unless unusual soil properties exist, these downstream water levels which may
values are considered adequate for design of saturate the soil behind the wall to a
small canal structures. For a detailed significantly higher elevation than the water
discussion of earth pressures on concrete depth in the pool just upstream from the
retaining walls, see bibliography reference hydraulic jump. Weep holes are used to
[5) lower the saturation level.

(C) Construction and Operating (b) Hydraulic Transients. -Pressure


Equipment Wheel Surcharge. -Walls of surges in a pipe and bore waves in a canal
accompany any change of flow in the system.
structures should be designed to withstand
construction and operating equipment wheel These transients are usually of insignificant
loads which are transmitted through the consequence in a small, open irrigation
earth adjacent to the structure. An additional system and are therefore generally omitted
lateral load equivalent to 2 feet of earth from structural design considerations. A
surcharge is usually used. This results in an gradual rate of change of flow minimizes the
additional uniformly distributed lateral magnitude of hydraulic transients.
pressure (rectangular pressure diagram) of (c) Seismic. -Additional earth and
60 psf from the backfill surface to the water pressures imparted to small canal
bottom of the wall. Standardized canal structures by earthquakes are not included in
structures are designed to withstand this the design considerations. The increased
additional load. loads are minor since the earth, water, and
(d) ice.-Ice loads on structures should concrete masses are all small. Temporary
be considered if wintertime canal operation stress increases caused by seismic loads
is required. The magnitudes for ice thrust would therefore be minor.
presented in bibliography reference [ 51 may 1-10. Wheel Loads Transmitted to
be used. Buried Conduit.
(e) Wind.-Wind loads on small -Pipelines crossing under highways
irrigation structures are not included in the and railroads must be designed to withstand
structural and stability analyses. surcharge loads from trucks and locomotives.
Concentrated wheel loads are transmitted
1-9. Other Pressures.
through earth cover and distributed at the
(a) Uplift. -Uplift pressures, which top of pipe where they are considered to be
may be caused by water percolating under or uniform loads. For design convenience, the
along the sides of hydraulic structures, uniform loads are converted to equivalent
reduce the effective weight of a structure heights of compacted earth cover and added
to the actual earth cover. Pipe is selected to
withstand this total equivalent earth cover. through the railroad embankment is a
(a) Highways.-Equivalent earth cover for common requirement. Pipe used to convey
highway wheel loads is based on criteria of the canal water (carrier pipe) is then installed
the American Association of State Highway in the casing pipe.
Officials [6] (AASHO). The following
tabulation shows total equivalent earth The top of pipe installed under a
cover for various heights of earth cover over railroad roadbed is usually at least 3 feet
the top of the pipe with H-15 and H-20 truck below the top of the railroad tie unless
wheel loads. otherwise specified by the railroad.

For an E-72 railroad loading [7),


Height of equivalent earth cover for
earth cover, wheel loads shown, feet usual Reclamation practice is to provide a
feet pipe class to withstand a total equivalent
h-15 loading h-20 loading cover of 20 feet when the top of pipe is 3 to
2 11.8 15.1 15 feet below the top of the railroad tie.
3 7.5 9.1 Additional load caused by impact is included
4 6.9 7.8 in the total equivalent cover previously
5 7.3 8.1
discussed.
6 8.0 8.6
7 8.7 9.2 2. Stability
8 9.4 9.9
1-11. Bearing Capacity.

For earth covers less than 2 feet, -Foundation bearing pressures for
special provisions such as concrete small structures are of small magnitude and
encasement of the pipe or slab covers are will ordinarily be less than allowable bearing
required. Wheel load effect is negligible pressures for the various soil types [5).
when the earth cover is more than 8 feet.
Foundation treatment may be
Wheel load impact factors used for required, however, for low-density or
earth covers less than 3 feet are as follows: expansive foundation soils. Ordinarily,
(1) 10 percent for earth covers of 2 feet 1 hydrocompaction by ponding will sufficiently
inch to 2 feet 11 inches, (2) 20 percent for consolidate soils of low density.
earth covers of 1 foot 1 inch to 2 feet, and (3) Overexcavation of the foundation soil and
30 percent if the earth cover is 1 foot or less. replacement with compacted, nonexpansive
soil is a usual treatment for expansive soil
Special provisions, such as detours foundations. The nonexpansive soil
and safety precautions, as may be required surcharges the underlying expansive soil and
by a highway commission should be included thereby can adequately reduce the
in the design specifications. foundation movement. Overexcavation is
(b) Railroads. -Design and installation also sometimes used for foundation
of pipe under a railroad often requires treatment of low-density soils.
special provisions to comply with the railroad
company requirements. Jacking casing pipe
When installing pipe in rock, the are perhaps the most critically loaded small
foundation should be overexcavated and canal structures subject to overturning.
replaced with a gravel or earth cushion to Maximum upstream and minimum
permit a more uniform bearing pressure for downstream water surfaces subject these
the pipe. This is essential to effectively utilize structures to unsymmetrical loads which
the design strength of the pipe, and to tend to cause overturning.
preclude unequal settlement and resultant
cracking of pipe. The resultant of all forces acting on
the structure should fall within the middle
1-12. Sliding Coefficient. third of the structure base to provide safety
against overturning. This location of the
-Any structure subjected to resultant also provides a more uniform
differential lateral pressures must capably bearing pressure on the foundation.
resist the tendency to slide. Resistance to
sliding is developed by shearing strength 1-14. Percolation.
along the contact surface of the structure
base and the foundation, or by shearing -All standardized canal structures
strength within the foundation material have sufficient cutoff and structural lengths
itself. Shearing strength developed by to provide a percolation factor of 2.5 or
more. This is considered adequate for most
cohesion is omitted and only that developed
by mechanical friction at the base and soils to prevent piping of foundation
foundation interface is used for sliding materials from beneath or adjacent to small
analysis of small structures. An allowable structures. Under ordinary operation, the
sliding coefficient equal to 0.35 is used maximum differential hydraulic head across
unless unusual soil conditions exist. This may the structure causing percolation is of short
duration. For a more detailed discussion of
be expressed as:
percolation, see subchapter VIII C.

= 0.35 3. Hydraulics

Where: 1-15. Hydraulic Control

= summation of lateral forces acting -In the competent hydraulic design of


parallel to the assumed sliding plane, and any hydraulic structure it is necessary to first
determine the location of the water surface
= summation of forces, reduced by control.
uplift, acting normal to the assumed sliding
plane. Hydraulic control is at the
downstream end of a structure if the
1-13. Overturning. downstream water surface influences the
height to which the upstream water surface
-To prevent overturning, the sum of
must rise. If the downstream water surface
the stabilizing moments must exceed the
does not influence the upstream water
sum of the overturning moments on the
structure. Checks and check-drop structures
surface, the control is at the upstream end of two consecutive points, a hydraulic jump
the structure. between the points is indicated and
hydraulic control will be at the inlet. It may
Upstream control for example will then be assumed that the water depth in the
usually exist for a relatively short culvert pipe at the inlet is at critical depth; that is, at
conveying storm runoff under a small canal
minimum energy.
where the outlet channel water surface is
several feet below the upstream pipe invert. 1- 16. Hydraulic Head Losses.
In this instance, the downstream water
surface does not control the upstream water -(a) Friction. -The Manning formula,
1.486 2 1
surface; instead, the upstream water surface [8] V =
3 2, is used to determine
is controlled at the inlet end. The upstream friction losses in a canal system. For all
pipe invert elevation, the size of pipe, and monolithic concrete canal structures, a
the assumed entrance loss are all factors roughness coefficient n = 0.014 is used.
which determine the height to which the Roughness (friction) coefficients used for
upstream water surface must rise to pipe are n = 0.013 for precast concrete,
discharge the flow. asbestos cement, reinforced plastic mortar,
and steel, while n = 0.024 is used for
Downstream hydraulic control exists
corrugated-metal pipe. A 20 percent
for a properly designed inverted siphon
reduction in the n value is used as a safety
when flow is at design capacity. The canal
factor in the hydraulic analysis of excess
water surface at the downstream end of the
energy dissipation for those structures which
siphon controls the upstream canal water
perform this function.
surface. For partial discharges, hydraulic
control is at the siphon inlet if the (b) Trunsitions and Bends. -
downstream water surface is low enough to Transitions are used to geometrically change
permit the water to enter the siphon at the water prism shape and cause
minimum energy, which is at critical depth. acceleration or deceleration of the flow.
Losses associated with convergence and
For many structures, location of the
divergences of the water prism are discussed
hydraulic control may be determined by
in chapter VII.
inspection of the structure profile and the
normal channel or canal water surfaces at A change in the direction of flow
each end of the structure. In other cases the causes bend losses. The magnitude of the
Bernoulli theorem [ 81 should be used to loss is dependent on the water velocity, and
determine the hydraulic control location. the angle for a miter bend or the degree of
Beginning from a known downstream water curvature of a circular curve. Pipe bend
surface, a Bernoulli equation can be written losses are discussed in chapter VIII.
between pairs of consecutive points. If a
Bernoulli balance is attainable between all 1- 17. Discharge Coefficients.
pairs of points from the outlet through the -(a) Orifice.-For a conduit flowing full,
inlet, downstream control exists. If, however, the discharge coefficient, C, used in the
a Bernoulli balance is not attainable between
orifice equation [8], Q = CA2, indicates herein, which show concrete thicknesses and
the magnitude of the assumed entrance loss. size and spacing of reinforcement bars, were
Values of C may be related to an entrance designed by the working stress method
loss coefficient, Ko, in the expression Ko ,hv,, based on a concrete strength of 4,000
1
by the relationship = 2 1 Values pounds per square inch (psi) at 28 days (fc)
and reinforcement steel having specified
commonly used are:
minimum yield strength of 60,000 psi (fv).
c ko Allowable working stresses used were 1,800
0.6 1.78 psi compression (fc) for concrete and 24,000
0.7 1.04 psi tension (fs) for reinforcement steel. For
0.75 0.78 many of the smaller standardized structures,
0.8 0.56 nominal minimum concrete thicknesses and
0.82 0.50 minimal reinforcement steel patterns control
The value for C in the orifice
the design. In these cases the concrete and
equation is primarily dependent on the
steel strengths indicated could be reduced
hydraulic entrance conditions. Subsequent
without jeopardizing structural integrity.
chapters of canal structures using the orifice
equation indicate ar appropriate C value for Reinforced precast concrete pressure
a specific design. (b) Weir. -Weirs are pipe was designed by the ultimate strength
commonly used to measure the rate of flow method using fb = 4,500 psi, FY = 40,000 psi,
of water. The basic weir equation [8] is Q = and an LF = 1.8 as a load factor.
3
CL 2. The appropriate value for the
b) Minimum Reinforcement
discharge coefficient, C, is primarily
Requirements. -The minimum reinforcement
dependent on the geometric shape of the
used for canal structures should be No. 4
weir and contraction of the sheet of water
bars (l/2-inch diameter) at 12-inch spacing
flowing over the weir. Values for C and
when reinforcement is placed in a single
equations for the more commonly used
layer, or where exposed faces of concrete
weirs are:
are reinforced. In unexposed faces of
Weir Weir equation concrete having two-layer reinforcement.
Rectangular 3 the minimum reinforcement should be No. 4
Q = 3.33 L 2
suppressed bars at 18 inches.
Rectangular Q = 3.33 (L - O.2H)
contracted 3 The following criteria should be used
2
Cipolletti 3
Q = 3.367 L 2 to determine the cross-sectional area for
For a comprehensive discussion of temperature or minimum reinforcement.
weirs, see chapter V. The percentages of reinforcement steel areas
listed are percentages of the gross cross-
4. Structural Considerations sectional area of the concrete to be
reinforced:
1-18. Reinforced Concrete.

- (a) Allowable Stresses. -


Standardized canal structures included
(1) Single-layer reinforcement.-For If a slab is fixed along any line, the
slabs with joint spacing not exceeding 30 feet dimension from the line of fixity to the free
and: end is doubled to determine if the
reinforcement requirement should bc based
Not exposed to freezing on a length not exceeding 30 feet or a length
temperatures or direct sun . . . . . . . . . . . . . . .
greater than 30 feet.
. . 0.25 percent
Reinforcement spacing should not
Exposed to freezing temperatures or
exceed three times the thickness of the
direct sun . . . . . .._......... 0.30 percent member for temperature reinforcement and
For slabs with joint spacing greater twice the thickness of the member for stress
than 30 feet and: bars.

Not exposed to freezing Other minimum requirements and


temperatures or direct sun . . . . . . . . . . . . . . . general notes for designing, showing, and
. . 0.35 percent detailing reinforcement steel are indicated
on figure l-8. When using the illustrations of
Exposed to freezing temperatures or standardized canal structures presented
direct sun . . . . . . . . . . . . . . . . . 0.40 percent herein as construction drawings, figure l-8
should be used for general notes and
Walls and other structural members
minimum requirements for detailing
should have a total percentage of horizontal
reinforcement.
reinforcement equal to the sum of the
percentages required for both faces as (c) Minimum Wall Thickness.--To
determined for double-layer reinforcement. provide ease of concrete placement and
insure good bond between the
(2) Douhle-layer reinforcement.-For
reinforcement and concrete, the minimum
joint spacing not exceeding 30 feet and with:
concrete thickness of cantilever walls should
Face adjacent to earth . . . . 0.10 be 1 inch per foot of height (5 inches
percent minimum) for walls up to 8 feet high. For
walls exceeding 8 feet in height, the
Face not adjacent to earth nor minimum concrete thickness should be 8
exposed to freezing temperatures or direct inches plus 3/4 inch for each foot of wall
sun . . . . . . . . . . 0.15 percent height greater than 8 feet.

Face not adjacent to earth but (d) Fillets.


exposed to freezing temperatures or direct
sun . . . . . . . . . . . . . 0.20 percent ~Fillets are used to relieve stress
concentrations, provide increased strength,
If a structural member exceeds 30 facilitate concrete placement, and to
feet in any direction parallel to the accommodate removal of forms. For small
reinforcement, an additional 0.05 percent of canal structures, fillets are not ordinarily
reinforcement steel area is required in that required for these purposes. However, 6inch
direction. fillets which may be formed by excavation
lines for the structure are commonly used at canal structures are included on the
the junctions of cutoff walls and floor slabs. illustrations.
Fillets used at the base of cantilever walls are
usually 3 inches for walls up to 8 feet tall. Many illustrations in subsequent
chapters show welding requirements for
(e) Cutoffs. metal parts. Explanations of the welding
symbols and required welding procedures
-- The primary purpose of cutoff
are included in bibliography reference [ 91)
walls is to increase the percolation path to
prevent piping of foundation material and 5. Canal
reduce percolation. Cutoffs should be used
for structures in a concrete-lined canal as 1-20. Freeboard.
well as earth canals. Cutoffs also protect a Canal lining and canal banks are
structure from undermining, if excessive extended above the canal normal water
erosion should occur in an earth canal. surface as a safety measure to protect the
Erosion protection of coarse gravel or riprap conveyance system from overtopping.
is frequently required at the ends of Freeboard provides for a canal water surface
structures in an earth channel to control higher than normal which may be caused by
erosion. Criteria to determine if erosion sedimentation in the canal, temporary
protection is required, and the type of misoperation of the canal system, excess
protection required, are discussed later in flows caused by storm runoff entering the
subchapter VII B and shown on figure 7-8. canal through drain inlets, additional water
These criteria should be used where depth resulting from a rougher friction
protection is indicated on structure coefficient than used for design, and waves
illustrations. The passive resistance of earth produced by wind or surges which
behind a cutoff increases the resistance of accompany sudden changes in flow.
the structure to sliding, although this
resistance is usually omitted in the stability Figure l-9 shows the vertical distance
analysis. Criteria for lengths and thicknesses which canal lining and canal banks should be
of cutoffs are also included in subchapter VII extended above the canal normal water
B. surface to provide adequate freeboard.
Special requirements for canal bank
1- 19. Structural Steel and Welding. freeboard at structures such as inverted
-Structural steel used with small siphons and drain inlets are discussed in the
canal structures is primarily for stoplog and appropriate subchapters for each particular
gate frame guides. Nominal size members structure. Freeboard requirements for the
are used to provide sufficient rigidity. canal structures are also discussed with each
Strength requirements for steel shapes used structure.
to fabricate safety devices such as handrail 1-21. Winter Operation.
and ladders are also nominal. All dimensions
and strengths of metalwork used in standard --Winter operation of a canal system
where temperatures are subfreezing may
require additional canal and structure 1-22. Profile Sheet.
freeboard to permit wintertime design
capacity to flow under an ice cover. At -Many design examples of structures
subfreezing temperatures an ice cover in this publication refer to a canal profile
readily forms when velocities are less than sheet. The development of the canal profile
2.2 feet per second. If velocities are fast requires close coordination of data obtained
enough to prevent formation of an ice cover, from several different studies including: (1)
frazil ice may form, and if allowed to canal design capacity, (2) canal water surface
accumulate on racks at inlets to structures requirements for turnout deliveries, (3) canal
will cause backwater. Additional forces location with respect to topography within
caused by expansion of the ice cover or by and adjacent to the canal prism, (4) canal
ice lenses in clayey foundation materials location to minimize disturbance or
relocation of existing features, and (5) the
should be considered.
canal cross section. Data from canal plan and
profile sheets are essential for design of the
canal structures.

6. Forms tor Structures

1-23. Monolithic Concrete.

-It is sometimes advantageous to use


"knock-down," reusable steel forms for
monolithic concrete construction of small
irrigation structures. A construction
procedure that has been used successfully is
to assemble the specially designed forms in
an area remote from the construction site,
place and tie the reinforcement steel in the
forms, and then haul the unit to the jobsite.
After carefully placing the structure-form
into position, concrete is placed for the
entire structure.

1-24. Precast Concrete.

-If a sufficient number of structures


for a small canal system are identical, it may
be economically advantageous to precast
them in a yard and haul them to the jobsite
for installation. Figure 1-10 shows concrete
being placed for a transition, and completed
transitions in the precasting yard. Slings are
frequently used to lower precast concrete
structures into position at the jobsite, as
shown in figure 1-11, for placing a precast
concrete transition. Figure 1-12 shows an
inplace, broken-back transition as a
component part of a road crossing structure.
To provide a uniform bearing surface for
precast concrete structures, a thin layer of
mortar at least an inch thick should be
placed on the foundation surfaces just prior Figure 1-11. Placing precast concrete
to placing the structure. A mortar bedding transition. P-707-729-2134
for a precast concrete inlet to a turnout
structure is shown in figure 1-13.

Standard structures discussed in this


publication which require a deck for
operational purposes, show either precast
walk planks or a precast deck. Precast decks
are used for the longer spans and are not
mechanically connected to the basic
structure. The bearing area at one end
should have a very smooth surface to permit Figure 1-12. In-place precast concrete
temperature-induced elongation or transition, partially backfilled. PX-D-72830
contraction of the deck without causing
additional shear and bending moment
stresses on the structure. Two asbestos
sheets each having graphite on one side only
and with the graphite surfaces in contact are
sometimes used to provide such a
surface.Figure

Figure 1-13. Precast concrete turnout


inlet being lowered into position on mortar
pad. p- 707- 729-1769
1.10. Precast concrete transitions in
various stages of completion. P-707-729-
1763
[7] "Manual for Railway Engineering,"
American Railway Engineering Association,
Vol. 1, Current to March 13, 1971.

[8] King, H. W. and Brater, E. F ., "Handbook


of Hydraulics," Fifth Edition, McGraw-Hill
Book Co., N.V., 1963.

[9] "Structural Welding Code," American


Welding Society, lQ7.'

Figure 1-14. Slide gate being operated to


control flow through turnout. P(F)-200-5717
NA.

c. BIBLIOGRAPHY

1-25. Bibliography.

[1] "Earth Manual," Bureau of Reclamation,


Second Edition, 1974.

[2] "Concrete Manual," Bureau of


Reclamation, Eighth Edition,1975.

[3] "Fly Ash Increases Resistance of Concrete


to Sulfate Attack," Report No. C-1224,
Bureau of Reclamation, January 1967.

[4] Terzaghi, Karl, "Does Foundation


Technology Really Lag?" Engineering News-
Record, February 15,1962, p. 59.

[5] "Design Criteria for Concrete Retaining


Walls," Bureau of Reclamation, August 1971.

[6] "Standard Specifications for Highway


Bridges," American Association of State
Highway Officials, Tenth Edition, 1969.
Chapter II the road crossing conduit may have a
straight line profile (see fig. 2-2), as discussed
A. GENERAL in these sections, or a profile like that shown
2-1. Purpose. in figure 2-4 with vertical bends as discussed
later in subchapters II C, II E, and II F. Road
-Conveyance structures are those crossings which have vertical bends in their
structures such as road crossings, profile function either as inverted siphons,
inverted siphons, drops, chutes, flumes, drops, or chutes.
canals, and pipelines that are used to
safely transport water from one location The straight line profile conduit (road
to another traversing various existing crossing) is designed for flow with little or no
natural and manmade topographic internal hydrostatic pressure; that is, the
features along the way. Canals and hydraulic gradient is near or below the top of
pipelines will not be discussed in detail in the pipe.
this publication and the technical 2-3. Application.
dissertation of the other conveyance
structures will be restricted to those -Available hydraulic head and cost
having a capacity of 100 cfs or less. considerations usually determine the
feasibility of using pipe for conveying water
under a roadway or using a bridge over the
waterway. Generally, for capacities up to 100
cfs, it is more economical to use pipe rather
than a bridge. Bridge design is beyond the
scope of this publication and consequently is
not included.

2-4. Advantages.

-Pipe road crossings are relatively


economical, easily designed and built, and
have proven a reliable means of conveying
Figure 2-1. Road crossing.
water under a roadway. Normally, canal
erosion at the ends of the road crossing in
earth canals is minor and can be controlled
B. ROAD CROSSINGS by transitions and rip rap or gravel
R. B. YOUNG protection. Road crossings usually cause less
roadway interference than a bridge both
2-2. Purpose and Description.
during and after construction. Pipe
-Road crossings are used to convey installation is sometimes accomplished by
canal water under roads or railroads (fig. 2-1 jacking the pipe through the roadway
). Pipe conduit is generally used for these foundation (fig. 2-3). A road crossing permits
purposes. In accomplishing these objectives both continuous roadbed and continuous
side drain ditches which otherwise might All pipe subjected to internal
drain into the canal. pressure should have rubber gasket joints to
insure positive watertightness. Under some
2-5. Design Considerations. roadways, watertight joints may be
-(a) Pipe.- The pipe may be steel necessary irrespective of internal pressure.
corrugated-metal pipe (CMP), precast Precast concrete pressure pipe with type R
reinforced concrete culvert pipe (RCCP), joints (rubber gasket joints) or asbestos-
asbestos-cement pressure pipe (AC), or cement pressure pipe with rubber gasket
precast reinforced concrete pressure pipe joints is used to insure watertightness. The
(PCP). Where watertightness of the pipe is of minimum pressure pipe class permitted for
m in or concern, the selection of either each is B 25 [ 4] [ 5] .Selection of the
corrugated-metal pipe, asbestos-cement, or appropriate pipe class is explained later in
concrete pipe is often established by past the discussion of Inverted Siphons,
experience. However, considerations subchapter II C. The hydraulic design of a
involved with the selection include hydraulic road crossing pipe consists of selecting a pipe
efficiency, corrosion environment, and cost diameter that will result in either: (1) a
considerations. The required gage (wall maximum allowable velocity of 3.5 feet per
thickness) of CMP for a given height of earth second for a pipe with earth transitions or,
cover and surcharge load from vehicles can (2) a maximum allowable velocity of 5 feet
be determined from manufacturers' tables. A per second for a pipe with concrete
typical set of tables is provided in transitions or other concrete inlet and outlet
bibliography reference [ I] .2 If RCCP is used, structures. The maximum upstream invert
this pipe design may also be determined elevation of the pipe is then determined by
from manufacturers' tables. A typical set of subtracting the pipe diameter and 1.5 times
tables is provided in bibliography reference the velocity head of the pipe flowing full
[2] .In Reclamation RCCP pipe is used for (diameter + 1.5 hvp) from the upstream
roadway crossings having little or no internal normal water surface elevation in the canal.
water pressure. Type B pipe joints (fig. 8-15) The pipe is set on a minimum slope of 0.005
are generally used where RCCP pipe is from this upstream invert elevation. This
permitted. However, type F joints may be provides a low point at the end of the pipe to
substituted for type B joints. Type F joint facilitate draining should it become
design and gaskets for type F joints should be necessary. The pipe hydraulic design should
in accordance with the American Society for be examined to determine if the resulting
earth cover from the top of the roadway to
Testing and Materials [ 3] provided the top of the pipe meets the following
that the design of the joints in the pipe is minimum requirements: (1) At all railroad
such that the taper on the tongue and and road crossings (except farm roads) a
groove is not more than 3-1/2 measured minimum of 3 feet of earth cover should be
from a longitudinal trace on the inside provided. If roadway ditches exist and are
surface of the pipe. extended over the pipe, the minimum
distance from the ditch invert to the top of
the pipe should be 2 feet. (2) At farm road
crossings a minimum earth cover of 2 feet Standardization of concrete transitions is a
should be provided for both the roadway and means of reducing costs. This is
the ditches. Farm roads are frequently accomplished by a transition being designed
ramped using 10 to 1 slopes (10 percent for a range of canal and structure conditions.
grade) when necessary to provide minimum As might be expected, if concrete transitions
earth cover requirements. Another are standardized, the base width and invert
alternative available to the designer for will seldom match that of the canal.
achieving minimum cover requirements is to Therefore, additional transitioning is then
set the upstream pipe invert a distance accomplished by an earth transition for an
greater than the pipe diameter plus 1.5 11, P earth canal and by transitioning concrete
below the upstream normal water surface lining for a concrete-lined canal. For
elevation. However, the maximum vertical relatively short structures, such as road
distance from the canal invert to the pipe crossings, it is generally more economical to
invert should not exceed one-half the pipe omit concrete transitions if established
diameter, except where a control structure is design criteria will permit the omission. For
required. Pipe with bends in its profile to the design of transitions see the discussion
provide the required earth cover, or sagged on Transitions, subchapter VII A. If there is a
for any other reason, is discussed with need for controlling the water surface
Inverted Siphons, subchapter Ii C. Roadway elevation upstream from the road crossing, a
widths and side slopes at the crossings check inlet or a control inlet is used. (See
should match existing roadway widths and discussion of Check and Pipe Inlet and
side slopes, or as otherwise specified. Side Control and Pipe Inlet subchapters III F and III
slopes should not be steeper than l-1/2 to 1. G.) If one of these structures is required, it is
usually economically desirable to also use a
(b) Tmuifiom. -Transitions are
concrete outlet structure and size the pipe
generally used both at the inlet and outlet of based on a maximum velocity of 5 feet per
structures. An accelerating water velocity second. (c) Pi/w Colluvs. -~Pipc collars may
usually occurs at the inlet of a structure and be required to reduce the velocity of the
a decclcrating velocity at the outlet.
water moving along the outside of the pipe
Transitions reduce head losses and prcvcnt or through the surrounding earth thcrcby
canal erosion by making the velocity changes preventing removal of soil particles at the
less abrupt. Concrete, earth, and point of cmcrgence. Any road crossing where
combination concrete-earth transitions are the canal water surface is significantly higher
used for this purpose. The following road than a potential point of relief for the
crossings require either a concrete transition
percolating water, should be examined to
or some type of concrete control structure at determine if collars are required. Pipe collars
the inlet and a concrete transition at the may also be necessary to discourage rodents
outlet: All railroad and state highway from burrowing along the pipe. A detailed
crossings. All crossings with 36inch-diameter discussion of the design of pipe collars and
pipe or larger. All pipe crossings with cutoffs as related to percolation may be
velocities in excess of 3.5 feet per second found in subchapter VIII C. (d) Cutd Erosiorl
discharging in to an earth canal. Protectors. -Protection is often used adjacent
to structures in earth canals where erosion (2) Need for concrete transitions.
may occur. For design of protection see the
(3) Pipe type: CMP, RCCP, or PCP.
discussion on Protection, subchapter VII B.
For a pipe discharge of 1.5 cfs, the
2-6. Design Example (see fig. 2-2). table shows that either a 24-inch-
diameter pipe with concrete
-(a) Giver1 : transitions (max. V = 5 fps) or a 30-
(1) Type of waterway = earth canal. inch-diameter pipe with earth
transitions (max. V = 3.5 fps) will be
(2) Type of roadway = farm road. hydraulically acceptable. Since the
(3) Canal Q = 15 cfs. crossing is for a farm road and both
diameters are less than 36 inches,
(4) El. A = 5406.52 (from a profile either the 24-inch-diameter pipe
sheet). with concrete transitions or the 30-
(5) d, = 1.58 ft. (normal depth at Sta. inch-diameter pipe with earth
A). transitions may be used. Material
costs and other considerations
(6) NWS at Sta. A= El. A+ d, = 5406.52
previously discussed will determine
+ 1.58 = 5408.10.
which pipe diameter to select, and in
(7) El. D = 5406.22 (from a profile addition whether the pipe should be
sheet). CMP, RCCP, or PCP. In this example
the 30-inch-diameter concrete
(8) dz = 1.58 ft. (normal depth at Sta.
D>. culvert pipe, class III with type B
joints, and with earth transitions will
(9) NWS at Sta. D = El. D + d, = be used.
5406.22 + 1.58 = 5407.80.
(4) Hydraulic properties of 30-inch-diameter
(10) F (water surface differential) =
pipe for Q of 15 cfs:
Upstream canal NWS El. - Downstream canal
NWS El. = 5408.10 - 5407.80 = 0.30 ft. A = area of pipe = 0.785 x dia2

(11) Width of roadway = 18 ft. A = 4.91 ft.2

(12) Side slopes of roadway = l-1/2: V = velocity in pipe =Q/A = 15/ 491
1.
V = 3.06 f.p.s.
(13) El. top of roadway = El. F = 5411
2 3.062
.oo. hvP=velocity head in pipe = 2 + 64.4!

(14) Control structure at inlet not hvP= 0.15 ft.


required.
Where g = gravitational acceleration
(b) Determine:
wp = wetted perimeter = 71 x dia.
(1) Pipe size (see table on fig. 2-2).
= 7.85 ft. = 1.14ft.
4.91 Downstream = El. D - El. C
R = hydraulic radius = + 7.85!

= 5406.22 - 5405.21
= 0.63 ft.
=-1.01 ft.
n = assumed roughness coefficient 3
(1 1) Assume losses in road crossing
= 0.013
are 1.5 pipe velocity heads for inlet and
sf = friction slope of pipe outlet loss combined plus pipe friction loss,
or
1
=( 2 2 )= 0.00133
2.24/3
1.5 hvp + hf= 0.22 + 35 x 0.00133
(from Mannings equation [ 61) = 0.27 ft.

Pipe hydraulic properties may also Where hf = length of pipe x friction


be taken from table 8- 1. slope. (12) protection.-Use figure 7-8 to
determine if protection is required. If
(5) El. B = NWS El. at A - (pipe required, select type, length, and height of
diameter + 1.5 hvp) = 5408.10 ~ (2.50 + 0.22) protection.
= 5405.38.
For d1 or d2 = 1.58 ft. and for road
(6) Approximate length of pipe (see crossings without concrete transitions:
fig. 2-2) = 1.5 (El. F - El. B) x 2 + roadway
Inlet protection = none
Width = 3(541 1.00 - 5405.38) + 18 =
34.9 ft. The 1.5 represents a l-1/2 to 1 side Outlet protection = 12-m. coarse
slope. If the side slope is 2 to 1 use 2 instead gravel (type 2)
of 1.5 in the previous equation.
Length = 4d or 5 ft. min. = 4 x 1.58 ft.
(7) Drop in pipe = length of pipe x = 6.3 ft.
slope of pipe = 34.9 x 0.005 = 0.17 ft
Because the transition length of 7.5
(8) El. C = El. B - drop in pipe feet is not much greater than the required
protection length, extend protection for full
= 5405.38 - 0.17 = 5405.21. length of transition. Extend protection to 12
inches above canal water surface.
(9) Length of earth transitions = 3 x
dia. of pipe (c) Check of Design
= 3 x 2.5 = 7.5 ft. . ~ (1) Compare computed losses
with the loss provided on profile sheet.
(10) Drop in transitions
Computed losses = 0.27 foot. Loss provided,
Upstream = El. A - El. B F = 0.30 foot. The excess head of 0.03 foot
(0.30 - 0.27) provided on the profile sheet is
= 5406.52 - 5405.38
inconsequential and the hydraulic design is Closed conduits with excess head are
considered adequate. discussed in subchapters II E Drops and II F
Chutes.
(2) Transition slopes. -To reduce
turbulence and provide for relatively smooth Closed conduits with straight profiles under
transitioning of the water prism, the roadways and railroads may also function as
maximum length to drop ratio of 4 to 1 is inverted siphons with internal pressure.
used. The design ratio of the upstream
transition is 7.5 to 1.14 or 6.6 to 1. This is 2-8 Application.
flatter than 4 to 1 and therefore within the -Economics and other considerations
criteria limits. By inspection, the slope of the determine the feasibility of using a siphon or
downstream transition is also satisfactory. another type of structure to accomplish the
(3) Cover on pipe.-Minimum earth previous objectives. The use of an elevated
cover for farm road crossing is 2 feet. flume would be an alternative to a siphon
Approximate cover on pipe = El. F - (El. B + crossing a depression, drain channel or
dia. of pipe) = 5411.00 ~ (5405.38 + 2.50) = another manmade channel. The use of a
3.12 feet. As 3.12 feet is greater than the bridge over a canal would be an alternative
minimum required 2.0 feet the cover is to a siphon under a road or a railroad.
Generally, for capacities up to 100 cfs, it is
satisfactory.
more economical to use a siphon rather than
If concrete transitions are required a bridge. Bridge design is beyond the scope
for a road crossing the inlet and outlet of this publication and consequently is not
transitions will usually be identical. Refer to included.
subchapter VII A and design example of
inverted siphons subchapter II C for 2-9. Advantages and Disadvantages
procedure used in design of type 1 concrete of Inverted Siphons.
transitions. -Inverted siphons are economical, easily
C. INVERTED SIPHONS designed and built, and have proven a
R. B. YOUNG reliable means of water conveyance.
Normally, canal erosion at the ends of the
2-7. Purpose and Description. siphon is inconsequential if the structures in
earth waterways have properly designed and
Inverted siphons figures 2-4, 2-5, and 2-6 constructed transitions and erosion
(sometimes called sag pipes or sag lines) are protection. Costs of design, construction, and
used to convey canal water by gravity under maintenance are factors that may make an
roads, railroads, other structures, various inverted siphon more feasible than another
types of drainage channels, and depressions. structure that might be used for the same
A siphon is a closed conduit designed to run purpose. There may be, however, instances
full and under pressure. The structure should where the value of the head required to
operate without excess head when flowing operate a siphon may justify the use of
at design capacity. another structure such as a bridge. An
inverted siphon may present a hazard to life,
especially in high population density areas. crossing under railroads, a minimum of 3
See chapter IX for safety features feet of earth cover should be provided. Farm
roads require only 2 feet of earth cover and
2-10. Structure Components. are frequently ramped using 10 to 1 slopes (
-(a) Pipe 10 percent grade) when necessary to provide
minimum cover requirements. If roadway
.- The closed conduits discussed in this ditches exist and are extended over the pipe,
publication are generally pipe. All pipe the minimum distance from the ditch to the
subjected to internal pressure should have top of the pipe should be 2 feet.
watertight joints. Precast reinforced concrete
pressure pipe (PCP), asbestos-cement (2) At siphons crossing under cross-
pressure pipe (AC), or reinforced plastic drainage channels, a minimum of 3 feet of
mortar pressure pipe (RPM), all with rubber earth cover should be provided unless
gasket joints, are used to insure studies indicate more cover is required
watertightness. For heads up to 150 feet because of projected future retrogressions of
precast reinforced concrete pressure pipe is the channel.
most frequently used but any of the above (3) At siphons crossing under an
types may be used depending on their earth canal, a minimum of 24 inches of earth
availability and cost considerations. cover should be provided.
These pressure pipes are classed as to their
(4) At siphons crossing under a lined
capacity to withstand external loads of cover canal, a minimum of 6 inches of earth cover
and wheel (equivalent earth cover) and should be provided between the canal lining
internal hydrostatic head measured to the
and the top of pipe.
centerline of the pipe. Designations of A, B,
C, and D represent 5, 10, 15, and 20 feet of Roadway widths and side slopes at
cover respectively, while the associated road and railroad siphon crossings should
number such as 25, 50, 75, 100, 125, and 150 match existing roadway widths and side
represents feet of hydrostatic head. As an slopes, or as otherwise specified. Side slopes
example, C 50 would be pressure pipe for 15- should not be steeper than l-1/2 to 1.
foot maximum cover and 50-foot maximum
head. Additional information regarding pipe, Pipe slopes should not be steeper
pipe joints, pipe bends, and other pipe than 2 to 1 and should not be flatter than a
appurtenances may be found in chapter VIII. slope of 0.005.

The pipe profile is determined in such a way Changes in PCP pipe grade and alinement
as to satisfy certain requirements of cover, (bends) may be made with precast elbows,
pipe slopes, bend angles, and submergence with beveled end pipe, by miter cutting pipe,
of inlet and outlet. Pipe cover requirements or by pulling joints. Changes in AC and RPM
are: pipe grade and alinement may be made by
miter cutting pipe or by pulling joints. See
(1) At all siphons crossing under chapter VIII for further information on
roads other than farm roads and siphons bends.
(b) Transitions may also increase. For further discussion on
Transitions see chapter VII.
-Transitions are nearly always used at the
inlet and outlet of a siphon to reduce head If there is a need for controlling the water
losses and prevent canal erosion in unlined surface elevation upstream from the siphon,
canals by causing the velocity change a check and pipe inlet or a control and pipe
between the canal and pipe to be less inlet is used. (See discussion of Check and
abrupt. Concrete, earth, or combinations of Pipe Inlet and Control and Pipe Inlet,
concrete and earth transitions are used for subchapters III F and III G.)
this purpose.
(c) Pipe Collars.-Pipe collars are not
The following siphons require either a normally required on siphons but they may
concrete inlet transition or some type of be needed to reduce the velocity of the
concrete inlet control structure, and a water moving along the outside of the pipe
concrete outlet transition: or through the surrounding earth thereby
preventing removal of soil particles (piping)
All siphons crossing railroads and at the point of emergence. Pipe collars may
state highways. also be necessary to discourage rodents from
All 36-inch-diameter and larger burrowing along the pipe. A detailed
siphons crossing roads. discussion for design of pipe collars and
cutoffs as related to percolation may be
All siphons in unlined canals with found in chapter VIII.
water velocities in excess of 3.5 feet per
second in the pipe. (d) Blowoff Structures.

Standardization of concrete -Blowoff structures are provided at


transitions is a means of reducing costs. This or near the low point of relatively long
is accomplished by having a single transition inverted siphons to permit draining the pipe
cover a range of canal and structure for inspection and maintenance or
conditions. The base width and invert of wintertime shutdown. Essentially the
standardized transitions will seldom match blowoff structure consists of a valved steel
those of the canal. Additional transitioning is pipe tapped into the siphon barrel. Blowoffs
then accomplished with an earth transition may also be used in an emergency in
where earth canals are involved and with a conjunction with wasteways for evacuating
concrete lining transition where concrete- water from canals. Short siphons are usually
lined canals are involved. dewatered when necessary by pumping from
either end of the siphon. If annual
For relatively short structures, such wintertime draining is not required, breaking
as siphons crossing roads, it is frequently into pipe smaller than 24-inch diameter for
more economical to omit concrete emergency draining is an economical
transitions even though the length of pipe alternative to providing a blowoff.
will increase and size of pipe and protection
A manhole is often included with a blowoff
on long siphons 36 inches and larger in
diameter to provide an intermediate access assume internal dimensions for the siphon
point for inspection and maintenance. and compute head losses such as entrance,
pipe friction, pipe bend, and exit. The sum of
A detailed discussion for design of blowoff all the computed losses should approximate
structures and manholes may be found in the difference in energy grade elevation
chapter VIII. between the upstream and downstream
(e) CanaI Freeboard und Erosion ends of the siphon (available head)
Protection In general, siphon velocities should
-The canal bank freeboard upstream range from 3.5 to 10 feet per second,
from siphons should be increased 50 percent depending on available head and economic
(1.0 foot maximum) to prevent washouts at considerations.
these locations due to more storm runoff The following velocity criteria may be
being taken into the canal than anticipated used in determining the diameter of the
or by improper operation. The increased siphon:
freeboard should extend a distance from the
structure such that damage caused by (1) 3.5 feet per second or less for a
overtopping the canal banks would be relatively short siphon with only earth
minimal; but in any event a minimum transitions provided at entrance and exit.
distance of 50 feet from the structure.
(2) 5 feet per second or less for a
Erosion protection is often used relatively short siphon with either a concrete
adjacent to siphons in earth canals. A transition or a control structure provided at
discussion of Protection is presented in the inlet and a concrete transition provided
chapter VII. at the outlet.

(f) Wasteways. --Wasteways are (3) 10 feet per second or less for a
often placed upstream from a siphon for the relatively long siphon with either a concrete
purpose of diverting the canal flow in case of transition or a control structure provided at
emergency. For design of wasteways see the the inlet and a concrete transition provided
discussion on Wasteways, subchapter IV B. at the outlet.

(g) Safety Features. -Safety measures The velocity or pipe size of a long
must be taken near siphons to protect siphon is of particular importance.
persons and animals from injury and loss of Economically, because a slight change in pipe
life. Safety features are discussed in chapter size can make a great change in the structure
IX. cost.

2-11. Hydraulic Design Head losses which should be


Considerations. considered are as follows:

- Available head, economy, and (1) Convergence loss in the inlet


allowable pipe velocities determine the size transition.
of the siphon pipe. Thus, it is necessary to
(2) Check structure losses when a for the inlet and l.OAh, for the outlet
check is installed in the inlet. transitions.

(3) Control structure losses when a For minimum hydraulic loss, it is


control is installed in the inlet. desirable to provide a seal of 1.5Ah, with 3-
inch minimum at pipe inlet and no
(4) Friction and bend losses in the submergence at the pipe outlet. The seal is
pipe. equal in height to the vertical drop from the
(5) Divergence loss in the outlet normal canal water surface to the top of the
transition. siphon opening. If the siphon has both
upstream and downstream concrete
(6) Transition friction losses are transitions it may be economically desirable
usually ignored for the size of structures in to construct the downstream transition the
this publication. same as the upstream transition. If the outlet
seal is greater than one-sixth the height of
(7) Convergence and divergence
opening at the outlet, the head loss should
head losses in earth transitions when
be computed on the basis of a sudden
required between the canal and concrete
enlargement and the loss for both earth and
transition are usually small and are usually
concrete outlet transitions would be 1 .OAhv
ignored.
. For additional discussion on
The total computed head loss is
Transitions SW chapter VII.
usually increased by 10 percent as a safety
factor to insure against the possibility of the If there is a check and pipe inlet or a
siphon causing backwater in the canal control and pipe inlet for the siphon see
upstream from the siphon. subchapters III F and III G for their hydraulic
design.
The hydraulic head loss in a
transition is dependent on the difference of Pipe friction losses arc determined
the velocity heads in the canal and the by using Mannings formula as is explained in
normal to centerline section of the closed section 2- 13 or by using table 8- 1.
conduit. Coefficients of velocity head
considered adequate for determining head Pipe bend losses are determined by
losses in a broken-back type of transition are using figure 8-l as is explained in chapter VIII.
0.4 for the inlet and 0.7 for the outlet, Special hydraulic considerations
therefore the losses would be 0.4Ah, for inlet must be given to the inlets on long siphons
and 0.7Ah, for the outlet transitions. where, under certain conditions, the inlet
Coefficients of velocity head will not be come sealed. On long siphons,
considered adequate for determining head such conditions may result when the canal is
losses in earth transitions from the canal to a being operated at partial flows (flows less
pipe are 0.5 for the inlet and 1.0 for the than design flow) or at full design flow when
outlet. Therefore, the losses would be 0.5Ah, the actual coefficient of friction is less than
assumed in design. Under such conditions, a
hydraulic jump occurs in the pipe and may If the computed losses are greater
cause blowback and very unsatisfactory than the difference in upstream and
operating conditions. Figure 2-7, which is downstream canal water surface, the siphon
self-explanatory, should be used to will probably cause backwater in the canal
determine proper performance of inlets to upstream from the siphon. If backwater
long siphons. Pipe slope or diameter should exists, the pipe size should be increased or
be changed to meet the requirements noted the canal profile revised to provide adequate
on the figure. head.

Another way of solving the air If the computed losses are


problem is to place properly designed air appreciably less than the difference in
vents at locations where air might upstream and downstream canal water
accumulate. This procedure is ordinarily used surface it may be possible to decrease the
only as a remedial measure for an existing size of pipe, or the canal profile may be
siphon with blowback problems. See revised so the available head is
discussion on Air Vents in chapter VIII. approximately the same as the head losses.

2-12. Design Procedure. (4) On long siphons where the inlet


may not be sealed there is the possibility of
Steps required for design of a siphon
blowback and unsatisfactory operating
include the following: conditions. The inlet should be checked for
(1) Determine what inlet and outlet proper performance and adjustments made
structures are required, and the type and if necessary.
approximate size of pipe. (5) Determine the pipe class. The
(2) make a preliminary layout of the pipe class can be determined from the
siphon profile (siphon and required inlet and amount of external load and internal head
outlet structures) using the existing ground shown on the pipe profile.
line, the canal properties, and the canal
2- 13. Design Example (see fig. 2-4.)
stations and elevations at the siphon ends
(fig. 2-8). This layout should provide pipe -Assume that an earth canal crosses
requirements of cover, slope, bend angles, a state highway and an inverted siphon is the
and provide pipe submergence requirements most feasible type of structure for conveying
at transitions, check and pipe inlets, or water past the highway.
control and pipe inlets.
(a) Giwn; (Refer to preliminary
(3) Compute the siphon head losses layout, fig. 2-8.)
in this preliminary layout. If the head losses
as computed arc in disagreement t with the (1) Type of waterway = earth canal.
available head, it may be necessary to make (2) Feature being crossed = state
some adjustment such as pipe size or even highway at right angles with canal E.
the canal profile.
(3) Q = 15 cfs.
(4) Sta. A = 149 + 47 and Canal Invert concrete inlet and outlet structures are
El. A = 5406.52 (from a canal profile sheet). required. Since a control structure is not
needed at the inlet, use a concrete transition
(5) d, = 1.25 feet (d,, normal depth in for both the inlet and the outlet. Use type 1
canal). V, = 2.1 f.p.s., hvl = 0.07 ft. transitions (fig. 7-2, Chapter VII) and use the
(6) NWS El. at Sta. A = El. A + d, = same transition for both inlet and outlet.
5406.52 + 1.25 = 5407.77. (2) Tvpc o,t pipe. -This pipe will have
(7) Sta. H = 150 + 49 and Canal Invert internal pressure and will be passing under a
El. H = 5405.50 (from a canal profile sheet). state highway, therefore, it should be either
precast reinforced concrete pressure pipe
(8) d, = 1.25 ft. (dn normal depth in (PCP), asbestos-cement pressure pipe (AC),
canal). v2 = 2.1 f.p.s.. h,Z = 0.07 ft. or reinforced plastic mortar pressure pipe
(RPM) each having rubber gasket joints. In
(9) NWS El. at Sta. H = El. H + d, =
this example assume that because of
5405.50 + 1.25 = 5406.75.
availability and costs it is advantageous to
(10) Width of roadway = 26 ft. use PCP.

(11) Side slopes of roadway ditch (3) Pipe size. (SW tuble on fig. 2-4.)-
and canal embankment = l-1/2 to 1. For a relatively short siphon having concrete
inlet and outlet transitions, the pipe would
(12) El. top of roadway = El. J = be sized for velocity of about 5 feet per
5407.26. second. Then for a discharge of 15 cfs the
table suggests that a 24-inch-diameter pipe
(13) El. edge of roadway shoulders =
may he used.
5407.00.
(4) Hydraulic properties of 24-inch-
(14) Control structure at inlet not
diameter pipe for Q of 15 cfs.
required for turnout delivery.
A = area of pipe = 0.785 x (dia.)2
(15) 18-inch-deep roadway ditches.
= 3.14 ft.
(16) Canal Sta. J at CL roadway = Sta.
150+00.
V = velocity in pipe= =
15
3.14
(17) Canal bank width = 10.0 ft.
= 4.77 f.p.s.
(18) Canal bank freeboard at outlet =
2 4.772
normal canal bank freeboard = 1.3 ft. = = =
2 64.4

(b) Determine. = 0.35 ft.

(1) Inlet and outlet structure where g = gravitacional aceleracin.


requirements.-The siphon crosses under a
state highway; therefore, some kind of wp = wetted perimeter = da.
= 6.28 ft. error in 1 will not significantly affect Ht. The
scaled value of, 1 is 120
3.14
r = hydraulic radius= = 6.28
2.00 2.00
. = cos 12 = 0.978 = 2.04
= 0.5 ft.
Hydraulic seal required = 1.5 h, = 1 .5( -
n=assumed roughness 3
1 ) = 1.5 (0.35 - 0.07) = 0.42 ft. which is
= 0.013 greater than 3 inches (0.25 ft.) minimum seal
required, therefore, 0.42 foot should be
=friction slope of pipe used. Transition invert El. C = NWS El. at Sta.
1 A - (1.5 hv + Ht) = 5407.77 - (0.42 + 2.04) =
=( ) 2 2 5405.31
2.24/3

=0.0044 If the transition invert at the cutoff (Sta. B) is


set at the canal invert, the difference in
Hydraulic properties of pipe may also
invert elevations of the transition (p) is
be taken from table 8-l in chapter VIII. (5)
5406.52 - 5405.31 = 1.21 ft. = p. See figure 7-
Additional canal bank freeboard at upstream
2 for p. The maximum p value for the inlet is-
end of siphon.-Additional canal bank 3
freeboard = 0.5 of normal freeboard = 0.5 x 4
D and the maximum p value for the outlet is
1
1.3 = 0.65 ft., use 0.7 ft. D. Therefore, by making the inlet and outlet
2
1 1
(6) Canal bank El. at Sta. A = NWS El. identical, p cannot exceed 2D which is 2 of 2
+ regular freeboard + additional freeboard = or 1 .O ft. (see subchapter VII A)
5407.77 + 1.3 ft. + 0.7 ft. = 5409.77. Extend
Use a p value of 1.0 foot, then the inlet
the bank at this elevation a distance of 50
transition invert El. B will not be the same as
feet upstream from the siphon to minimize
the canal but will be El. C + p or 5405.31 +
damage which coul be caused by
1.00 foot = 5406.3 1 which is 0.21 foot lower
overtopping.
than the canal invert at Sta. A. The invert
(7) Canal bank El. at Sta. H = NWS El. slope for a 10-foot-long earth transition
+ freeboard = 5406.75 + 1.3 ft. = 5408.05. resulting from the use of p = 1.0 foot should
not be steeper than 4 to 1 (see sec. 7-11).
(8) Inlet transition hydraulic setting. - The actual slope = 10 to Inv. of earth
The transition invert elevation at the transition = 10 to 0.2 1 = 48 to 1 which is
headwall (Sta. C) is based on the hydraulic flatter than 4 to 1 and therefore permissible.
seal required at the top of the headwall
opening and the vertical height of the (9) Outlet trausitiorz hydraulic setting.
opening, Ht. Pipe slope affects this D vertical
-To minimize headwall submergence, set the
dimension since Ht = downstream invert elevation (Sta. G) of the
1

transition at canal invert. Then the transition


Where D = pipe diameter and 01~ =
invert El. G = canal invert El. H = 5405.50. For
angle of pipe slope at headwall. The scaled
the inlet and outlet transitions to be
value of cy, is usually adequate since a small
identical, p = 1.0 foot. Then transition invert where hi is inlet loss, h, is pipe friction loss,
El. F = El. G - p = 5405.50 - 1.00 = 5404.50. h, is pipe bend loss, and h, is outlet loss.

The height of headwall opening (Ht) at H, = I. I[ 0.4 , + pipe length x sf + C, x 2 +


station F is, 0.7 ]

2.00 2.00 H, = 1.1,0.:(0.35 ~ 0.07) + 72 x 0.0044 + (0.04


= = = = 2.04
1 12 0.978 x 0.35) 2 + 0.7(0.35 ~ 0.07)]

Submergence of top of opening = = 1.1 [0.1 1 + 0.32 + 0.03 + 0.20]


= 1. 1 (0.66) = 0.73 foot
(2 + ) = = (1.25 + 1.00)
2
= 0.21 Head provided by canal profile = 1.02 feet
which is 0.29 foot more than the 0.73 foot
This submergence should not exceed one-
required for this preliminary layout. This
sixth Ht for minimum head loss. One-sixth Ht
excess head will cause a slight drawdown in
2.04
= = 0.34 foot which is greater than the the canal upstream from the siphon and will
6
submergence of 0.21 foot. Therefore, the result in faster than normal velocities for a
loss for the outlet transition is minimum and short distance. For this design example
may be calculated using the equation 0.7h. assume that this velocity is noneroding so it
is not necessary that the profile of the canal
(10) Drop in water surface elevation
or the size of pipe be revised.
(available head) = NWS El. Sta. A - NWS El.
Sta. H = 5407.77 - 5406.75 = 1.02 ft. (1 1)
Before establishing detailed siphon
elevations and dimensions, use a preliminary
siphon layout (fig. 2-8) and determine
approximate total head loss and compare
with head provided. Scale the dimensions
and angles as required. This study will
indicate if the pipe diameter or canal profile
should be revised. Total siphon head loss
with 10 percent safety factor = 1.1 (inlet
transition convergence loss + pipe friction
loss + bend losses + outlet transition
divergence loss)

Pipe length scaled = about 72 feet.

Pipe bend angles scaled = about 12

(assume single angle bends). Approximate


total head loss H1 = 1.1 (hi + hf- + hb + ho)

Vous aimerez peut-être aussi