Caltech Engineering Services offer rebar corrosion voltmeter kit complete economical kit for
identifying areas of rebar corrosion in concrete as per ASTM C-876.
Rebar corrosion voltmeter kit includes half-cell and voltmeter integrated with a high
impedance and long earth cable and dispensing damp sponge. When rebar corrosion
voltmeter DV-05 is connected between the reinforcing steel, Cu-CuSO4 reference half-cell
electrode (Fontana-101F) and specially made highly electrical conductive dispensing sponge
on the concrete surface where a measurement can be made for the half-cell potential. This
gives measurement of the probability of corrosion activity. By testing at a fixed distance apart,
a grid of half-cell potentials can be developed and areas delineated.
Easy to use
Detachable electrode extension pieces facilitate measurements in hard to reach
locations - Optional
High impedance digital meter is designed for tough field conditions
Electrode is designed for use on horizontal, vertical and inverted positions
Economical
Conforms to ASTM C-876
The reference half cell is copper in a copper sulphate solution. By taking half cell potential
measurements a fixed distance apart a grid of half cell potentials can be quickly made and
thus areas delineated with a high probability of corrosion of the reinforcing steel.
To analyze the results, the measurements made with DV-05 rebar corrosion voltmeter can be
plotted on a grid and lines of equipotential contours drawn, highlighting areas of possible
corrosion activity.
For example the following guide is listed in ASTM C-876 using a copper-
copper sulphate half cell:
For readings of 350mV and greater there is a 95% chance of active steel corrosion
For readings 200 to 350mV there is a 50% chance of active steel corrosion
For readings less than 200mV there is only 5% chance of active steel corrosion
Bridge Decks
Parking Garages
Concrete Piers & Docks
Substructure
Tunnel Lining