Académique Documents
Professionnel Documents
Culture Documents
The air distribution aspect of air conditioning and heating systems can often be misunderstood. We all know
that cool or warm air is needed in each room in order to bring that space to a comfortable condition, but to
achieve this correctly takes much more than tying a duct onto an air handler and letting it blow. Before
getting into the air distribution system, there are some basic concepts and terminology that must be
understood to achieve a system that will deliver comfortable conditions throughout the conditioned space.
TOTAL AIR VOLUME - Cubic Feet Per Minute (CFM)
CFM refers to the total volume of air measured in cubic feet that is moved through the system in one minute.
The total CFM that can be delivered through a duct is dependent on the pressure making the air move,
combined with the size of the duct. Naturally the larger the duct is and the more pressure behind the air, the
more air that can be moved. Normally you would expect to have a total air volume of approximately 400
CFM per ton of air conditioning moving through the air handler and duct system.
Example: 3 tons x 400 CFM per ton = 1200 CFM total for a 3-ton unit.
Each area of a building has a specific heat gain and heat loss that determines how much air will be required to
heat or cool that area. Once the required CFM is determined through a load calculation, it is then distributed
proportionally to each area of the structure. It is very important to make sure that the air is delivered where it
will not blow directly on the customer or create noise.