Académique Documents
Professionnel Documents
Culture Documents
Delivery programme
Doyma Sealing Systems
Curaflex Quadro-Secura
Sealing systems for pipes and cables Multi purpose service ducts
Doyma DL Curaflam
Sealing systems for pipes as link chains Fire protection materials
Curaline CuraInn
Sealing systems for cables Service ducts for in-house installation
Seite R-1-2
Doyma Sealing Systems
Index of contents
Page Page
Curaflex sealing systems for pipes and cables
Glossary of terms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
- Curaflex accessories
Aquagard concrete sealant. . . . . . . . . . . . . . . . . . . . . . . 38
Bonding and other accessories . . . . . . . . . . . . . . . . . . . . . 39
Installation accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Packings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Performance checklist . . . . . . . . . . . . . . . . . . . . . . . . . 42
page 1
Curaflex
PIPE DUCT SYSTEM
on the face
Curaflex 8000, 8000/T 5
of the wall
against pressing
water
Curaflex 4006 6
in the
wall
Curaflex 6000 7
with tanking membrane/
bituminous thick-coating**
on the face
Curaflex 7006 8
of the wall
on the face
Curaflex 8000, 8000/T 5
of the wall
in the
Curaflex 4005 9
wall
on the face
Curaflex 7005 11
of the wall
06.06/MT 26-2
*) white tank
**) black tank
page 2
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Technical details
Curaflex special fibre cement pipe sleeve for installation in Pipe/Cable Pipe sleeve/ Pipe sleeve Standard
external diameter core bore external diameter lengths
walls and ceilings d [mm] D1 [NB in mm] D2 [mm] L1 [mm]
Curaflex pipe sleeve in split version for retrofit installation
(reconstruction) when services are already installed: 3000/T 1 - 40 80 136
can be used in conjunction with all Curaflex gasket inserts 41 - 57 100 156
for buildings without tanking membranes
58 - 77 125 156 200
leak-proof against pressing and non-pressing water
gas-tight when both inside and front faces of the pipe sleeve 78 - 104 150 187 240
are coated 105 - 145 200 238 250
page 3
Curaflex
PIPE DUCT SYSTEM
Technical details
Curaflex pipe sleeve with puddle flange for installation Pipe/Cable Pipe sleeve Puddle Standard
in concrete or brick walls external diameter internal diameter flange lengths
d [mm] D1 [NB in mm] D3 [mm] L1 [mm]
can be used in conjunction with all Curaflex gasket inserts
for buildings without tanking membranes 1 - 40 80 290
leak-proof against pressing and non-pressing water 41 - 57 100 310
gas-tight
58 - 77 125 340
material: steel, electro-galvanized, yellow passivated and
sealant coated 78 - 104 150 360 200
page 4
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Technical details
Curaflex pipe sleeve for installation on the face of walls and Pipe/Cable Pipe sleeve
Fixed flange
ceilings, where the size of the sleeve or core bore is too small external diameter internal diameter
D5 [mm]
d [mm] D1 [NB in mm]
to allow a gasket insert to be fitted around the service to be
ducted 1 - 40 80 260
can be used in conjunction with Curaflex gasket inserts type
41 - 57 100 280
A, A/M, A 40, Quick In A, C, C/M, C 40, Quick In C
(all with DPS*) 58 - 77 125 300
Curaflex pipe sleeve in split version for retrofit installation 78 - 104 150 330
(reconstruction) when services are already installed: 8000/T
105 - 145 2001) 380
leak-proof against pressing and non-pressing water
gas-tight 146 - 190 250 2) 430
Curaflex 8000/T
Subject to technical alteration without notice
page 5
Curaflex
PIPE DUCT SYSTEM
Technical details
Curaflex special fibre cement pipe sleeve for installation in walls Pipe/Cable Pipe sleeve Standard
Fixed flange
external diameter internal diameter lengths
and ceilings with fixed and loose flange made of cast iron D5 [mm]
d [mm] D1 [NB in mm] L1 [mm]
according to DIN 18195
for buildings with tanking membranes or with bituminous thick- 1 - 40 80 440
coating. Thin tanking membranes require two additional
41 - 57 100 460 200/240
elastomeric packings according to DIN 18195-9
(Doyma packings 1775) 58 - 77 125 480 250
leak-proof against pressing water 78 - 104 150 510 300/365
can be used in conjunction with Curaflex gasket inserts type C,
105 - 145 200 560 400
C/M, 2 x A, Quick In C (all with DPS*)
gas-tight when inside face of the pipe sleeve is coated 146 - 190 250 610 500
* DPS Double Profile System up to NB 350 191 - 233 300 660
Curaflex accessories:
Formwork fastener (1701) Further sizes, other materials and tailor-made
specials available on request!
Protective cap (1702)
Aesthetic seal (1708)
Disboxid 444 epoxy resin coating (1745)
2 Elastomer packings (1775)
Accessories for bituminous thick-coating (1776)
Subject to technical alteration without notice
page 6
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Technical details
Curaflex steel pipe sleeve for installation in walls and ceilings Pipe/Cable Pipe sleeve Standard
Fixed flange
with fixed and loose flange made of steel according to external diameter internal diameter lengths
D5 [mm sq]
DIN 18195 d [mm] D1 [NB in mm] L1 [mm]
for buildings with tanking membranes or with bituminous thick-
1 - 40 80 440
coating. Thin tanking membranes require two additional
41 - 57 100 460
elastomeric packings according to DIN 18195
(Doyma packings 1775) 58 - 77 125 480
leak-proof against pressing water 78 - 104 150 510 200
can be used in conjunction with Curaflex gasket inserts type C,
105 - 145 2001) 560 240
C/M, 2 x A, Quick In C (all with DPS*)
Loose flange is bolt-fastened to threaded sockets on the fixed 146 - 190 250 2) 610 250
flange 191 - 233 300 3) 660 300
material: steel, electro-galvanized, yellow passivated and
234 - 288 350 710 365
sealant coated
* DPS Double Profile System up to NB 350 289 - 339 400 760 400
page 7
Curaflex
PIPE DUCT SYSTEM
Technical details
Pipe/Cable Pipe sleeve
Curaflex steel pipe sleeve with fixed and loose flange accord- external diameter internal diameter
Fixed flange
D5 [mm]
ing to DIN 18195 for installation on the face of walls and d [mm] D1 [NB in mm]
ceilings, where the size of the sleeve or core bore is too small to
1 - 40 80 520
allow a gasket insert to be fitted around the service to
be ducted 41 - 57 100 540
for buildings with tanking membranes or with bituminous 58 - 77 125 560
thick-coating. Thin tanking membranes require two additional 78 - 104 150 590
elastomeric packings according to DIN 18195
105 - 145 2001) 640
(Doyma packings 1775)
146 - 190 250 2) 690
leak-proof against pressing water
can be used in conjunction with Curaflex gasket inserts type C, 191 - 233 300 3) 740
C/M, C 40, 2 x A, Quick In C (all with DPS*) 234 - 288 350 790
gas-tight
289 - 339 400 840
material: steel, electro-galvanized, yellow passivated and
sealant coated 340 - 380 450 890
* DPS Double Profile System up to NB 350 381 - 430 500 940
page 8
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Technical details
Curaflex special fibre cement pipe sleeve for installation in Pipe/Cable Pipe sleeve Standard
Fixed flange
external diameter internal diameter lengths
walls and ceilings D5 [mm]
d [mm] D1 [NB in mm] L1 [mm]
with fixed and loose flange made of cast iron as per DIN
18195 1 - 40 80 270
for buildings with tanking membranes or with bituminous 41 - 57 100 290 200/240
thick-coating. Thin tanking membranes require two additional
58 - 77 125 320 250
elastomeric packings according to DIN 18195 (Doyma
packings 1775) 78 - 104 150 345 300/365
Curaflex accessories:
Formwork fastener (1701)
Protective cap (1702)
Aesthetic seal (1708)
Disboxid 444 epoxy resin coating (1745)
2 Elastomer packings (1775)
Accessories for bituminous thick-coating (1776)
Subject to technical alteration without notice
page 9
Curaflex
PIPE DUCT SYSTEM
Technical details
Pipe/Cable Pipe sleeve Standard
Curaflex steel pipe sleeve for installation in walls and ceilings external diameter internal diameter
Fixed flange
lengths
D5 [mm]
with fixed and loose flange made of steel according to d [mm] D1 [NB in mm] L1 [mm]
DIN 18195
1 - 40 80 260
for buildings with tanking membranes or with bituminous thick-
coating.Thin tanking membranes require two additional elasto- 41 - 57 100 280
page 10
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Technical details
Curaflex steel pipe sleeve with fixed and loose flange according Pipe/Cable Pipe sleeve
Fixed flange
external diameter internal diameter
to DIN 18195 for installation on the face of walls and ceilings, D5 [mm]
d [mm] D1 [NB in mm]
where the size of the sleeve or core bore is too small to allow a
gasket insert to be fitted around the service to be ducted 1 - 40 80 260
for buildings with tanking membranes or with bituminous 41 - 57 100 280
thick-coating. Thin tanking membranes require two additional
58 - 77 125 300
elastomeric-packings according to DIN 18195
78 - 104 150 330
(Doyma packings 1775)
leak-proof against non-pressing water 105 - 145 2001) 380
can be used in conjunction with Curaflex gasket inserts type A, 146 - 190 250 2) 430
A/M, A 40, Quick In A (all with DPS*) 191 - 233 300 3) 480
gas-tight
234 - 288 350 530
material: steel, electro-galvanized, yellow passivated and
sealant coated 289 - 339 400 580
* DPS Double Profile System up to NB 350 340 - 380 450 630
Accessories for bituminous thick-coating (1776) L2 = length of steel pipe sleeve : 80 mm or 120 mm
page 11
Curaflex
PIPE DUCT SYSTEM
Technical details
Pipe/Cable Pipe sleeve Pipe sleeve Flange
Curaflex pipe sleeve with flange, completely made of special external diameter internal diameter external diameter external diameter D5
fibre cement, for installation in concrete or brick walls for d [mm] D1 [NB in mm] D2 [mm] [mm]
page 12
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
core bore/NB
7 - 13
14 - 21 318-322
min.
max.
min.
80
22 - 28 323-327
29 - 35 328-333
36 - 40 334-339
41 - 45 max. 340-344
100 46 - 52
345-350
53 - 57
351-356
58 - 67
125 357-362
68 - 77 450
78 - 85 363-368
150 86 - 94 369-370
95 - 104 371-375
105 - 115 376-380
116 - 124
200 381-386
125 - 135
387-392
136 - 145
393-397
146 - 156
398-403
157 - 165
166 - 172 500 404-409
250
173 - 179 410-415
180 - 186 416-420
187 - 190 421-425
191 - 197 426-430
198 - 207
300 208 - 215
Sealing areas for NB > 500 upon
216 - 224
request.
225 - 233
234 - 240
241 - 249
250 - 259
350
260 - 269
270 -278
279 -288
Nenndurchmesser
Core bore
50 80 100 125 150 200 250 300 350 400 450 500 600 700
Kernbohrung (KB) [mm]
NB [mm]
page 13
Curaflex
PIPE DUCT SYSTEM
Curaflex C, C 40 15, 17
Curaflex Quick In C 16
Curaflex C/M 19
Curaflex C/S 18
against pressing
water Curaflex F, D 22, 23
Curaflex MS/C 26
Curaflex A, A 40 27, 29
Curaflex Quick In A 28
Curaflex A/M 31
Curaflex A/S 30
Subject to technical alteration without notice
against non-
pressing water Curaflex MS/A 36
Curaflex B, B/Ex 33
06.06/MT 26-2
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe/Cable Pipe sleeve/
Curaflex gasket insert with DPS* for pipes and cables external diameter core bore
for installation in pipe sleeves or core bores d [mm] D1 [NB in mm]
double sealing
1 - 24 50
leak-proof against pressing water
1 - 40 80
gas-tight
accepts angular deviations of service duct up to 8 41 - 57 100
page 15
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Hinged Curaflex gasket insert with DPS* for pipes and cables Pipe/Cable Pipe sleeve/
external diameter core bore
quick-closure for retrofit installation d [mm] D1 [NB in mm]
for installation in pipe sleeves or core bores
double sealing 1 - 24 50
leak-proof against pressing water 1 - 40 80
gas-tight
41 - 57 100
accepts angular deviations of service duct up to 8
accepts axial movements 58 - 77 125
Parts: - asymmetrically profiled steel rings: 78 - 104 150
electro-galvanized, yellow passivated
105 - 145 200
and sealant coated
- elastomer: 2 x 27 mm EPDM seal rings (Doyma-Grip) 146 - 190 250
- 3 mm EPDM orange-coloured centre ring 191 - 233 300
* DPS Double Profile System up to NB 350 234 - 288 350
page 16
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe/Cable Pipe sleeve/
Curaflex gasket insert with DPS* includes two 40 mm strong external diameter core bore
EPDM full rubber gaskets. These extra wide and soft d [mm] D1 [NB in mm]
seal rings provide a perfect sealing on smooth medium pipe
58 - 77 125
surfaces. This is ideal for sealing pre-insulated pipes
78 - 104 150
(district-heating).
for installation in pipe sleeves or core bores 105 - 145 200
double sealing 146 - 190 250
leak-proof against pressing water 191 - 233 300
gas-tight
234 - 288 350
accepts axial movements
289 - 339 400
Parts: - asymmetrically profiled steel rings:
electro-galvanized, yellow passivated and sealant coated 340 - 380 450
page 17
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Curaflex gasket insert with DPS* for pipes and cables Pipe/Cable Pipe sleeve/
external diameter core bore
outside the standard size range d [mm] D1 [NB in mm]
for installation in pipe sleeves or core bores
double sealing 9 - 40 100
leak-proof against pressing water 58 - 65 100
gas-tight
40 - 57 125
accepts angular deviations of service duct up to 8
58 - 77 130
accepts axial movements
Parts:- asymmetrically profiled steel rings: 57 - 77 150
electro-galvanized, yellow passivated and sealant coated 78 - 104 160
- elastomer: 2 x 27 mm EPDM seal rings (Doyma-Grip)
78 - 104 200
3 mm EPDM orange-coloured centre ring
* DPS Double Profile System up to NB 350 105 - 145 250
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe/Cable Number of Pipe sleeve/
Curaflex gasket insert with DPS* for pipes and cables external diameterr pipes/cables core bore
for installation in pipe sleeves or core bores d [mm] D1[NB in mm]
4 - 36 1 - 10
4 - 26 1 - 15
8 x 13 -41
1 - 12
4 x 4 - 30
4 - 26 1 - 20
Installation as shown above. Tighten nuts diagonally opposite nuts.
12 - 40 1-8 Further sizes, other
Please observe maximum torque values. 250
10 x 16 - 44 materials and tailor-
1 - 15
5 x 4 - 36 made specials available
06.06/MT 26-2
page 19
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe sleeve/
Curaflex gasket insert C/0 with DPS* is a blind gasket insert. core bore
It ensures safe seal for unused core bores or pipe sleeves. D1 [NB in mm]
450
Curaflex accessories: 500
Aquagard primer and special paint
600
Disboxid 444 epoxy resin coating (1745)
700
Socket wrench (1704)
LD max. overall length: 90 mm
Torque wrench (1760)
Sockets (1761)
Further sizes, other materials and tailor-made
specials available on request Subject to technical alteration without notice
page 20
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Curaflex gasket insert with DPS* for pipes and cables Pipe/Cable Pipe sleeve/
external diameter core bore
using 2 units single sealing d [mm] D1 [NB in mm]
for installation in pipe sleeves or core bores
leak-proof against pressing water 1 - 24 50
gas-tight 1 - 40 80
accepts axial movements 41 - 57 100
Parts: - asymmetrically profiled steel rings:
58 - 77 125
electro-galvanized, yellow passivated and sealant coated
- elastomer: 27 mm EPDM seal ring (Doyma-Grip) 78 - 104 150
* DPS Double Profile System up to NB 350 105 - 145 200
page 21
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe/Cable Pipe sleeve/ Large ring
Curaflex gasket insert with DPS* for pipes and cables external diameter core bore diameter
for installation in pipe sleeves or core bores d [mm] D1 [NB in mm] GD [mm]
double sealing
1 - 24 50 70
leak-proof against pressing water
1 - 40 80 98
gas-tight
accepts angular deviations of service duct up to 8 41 - 57 100 120
Disboxid 444 epoxy resin coating (1745) LD max. overall length inside wall: 65 mm
Socket wrench (1704) Further sizes, other materials and tailor-made
Torque wrench (1760) specials available on request
Sockets (1761)
Subject to technical alteration without notice
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Curaflex gasket insert with DPS* for pipes and cables Pipe/Cable Pipe sleeve/ Large ring
external diameter core bore diameter
for installation in pipe sleeves or core bores d [mm] D1 [NB in mm] GD [mm]
double sealing
leak-proof against pressing water 1 - 24 50 70
gas-tight 1 - 40 80 98
accepts angular deviations of service duct up to 8
41 - 57 100 120
accepts axial movements
nuts to be tightened on the large ring (water side) 58 - 77 125 145
tested for civil defence use: F/Z 78 - 104 150 170
suitable for high pressure when installed with the large ring on
105 - 145 200 240
the pressure-exposed side
Parts: - asymmetrically profiled steel rings: 146 - 190 250 290
electro-galvanized, yellow passivated and sealant coated 191 - 233 300 340
- elastomer: 2 x 27 mm EPDM seal ring (Doyma-Grip) 234 - 288 350 390
- 3 mm EPDM middle orange-coloured centre ring
289 - 339 400 440
* DPS Double Profile System up to NB 350
340 - 380 450 490
Curaflex accessories: 381 - 430 500 550
Aquagard primer and special paint
431 - 530 600 650
Disboxid 444 epoxy resin coating (1745)
Socket wrench (1704) 531 - 620 700 750
Torque wrench (1760) LD max. overall length inside wall: 65 mm
Sockets (1761)
with
LD
Technical details
Curaflex gasket insert with DPS* for pipes and cables
Pipe/Cable Pipe sleeve/ Fixed flange
as per DIN 18195
external diameter core bore diameter
for installation in pipe sleeves or core bores d [mm] D1 [NB in mm] D5 [mm]
for buildings with tanking membranes or with bituminous thick-
coating. Thin tanking membranes require two additional 1 - 40 80 400
elastomer packings according to DIN 18195 (Doyma layers 1775) 41 - 57 100 420
leak-proof against pressing water
58 - 77 125 445
gas-tight
accepts angular deviations of service duct up to 8 78 - 104 150 470
page 24
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
LD
Technical details
Curaflex gasket insert with DPS* for pipes and cables
Pipe/Cable Pipe sleeve/ Fixed flange
as per DIN 18195 external diameter core bore diameter
for installation in pipe sleeves or core bores d [mm] D1 [NB in mm] D5 [mm]
for buildings with tanking membranes or with bituminous thick-
1 - 40 80 400
coating. Thin tanking membranes require two additional
elastomer packings according to DIN 18195 (Doyma layers 1775) 41 - 57 100 420
electro-galvanized, yellow passivated and sealet coated 191 - 233 300 620
- elastomer: 2 x 27 mm EPDM seal rings (Doyma-Grip) 234 - 288 350 670
* DPS Double Profile System up to NB 350
289 - 339 400 720
On Curaflex F/2/SD/6 nuts for tightening the gasket insert are
situated on the dry side.If nuts are installed vice versa ( water 340 - 380 450 770
side), the result is Curaflex C/2/SD/6. 381 - 430 500 820
with
Technical details
Pipe/Cable Pipe sleeve/
Curaflex gasket insert with DPS* for flexible cable ducts external diameter core bore
and cables d [mm] D1 [NB in mm]
with cable sheathing and heat shrink sleeve to allow sealing
1 - 50 100
between cable sheathing and cable duct/cable
40 - 50 125
for installation in pipe sleeves or core bores
double sealing 40 - 95 150
Curaflex accessories:
Aquagard primer and special paint
Disboxid 444 epoxy resin coating (1745)
Socket wrench (1704)
Torque wrench (1760)
Sockets (1761)
Subject to technical alteration without notice
Installation as shown above. Tighten nuts diagonally opposite nuts. Heat shrinking
Please observe maximum torque
values.
06.06/MT 26-2
page 26
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe/Cable Pipe sleeve/
Curaflex gasket insert with DPS* for pipes and cables
external diameter core bore
for installation in pipe sleeves or core bores d [mm] D1 [NB in mm]
leak-proof against non-pressing water
1 - 24 50
gas-tight
accepts angular deviations of service duct up to 8 1 - 40 80
accepts axial movements 41 - 57 100
Parts: - asymmetrically profiled steel rings:
58 - 77 125
electro-galvanized, yellow passivated and sealant coated
78 - 104 150
- elastomer: 27 mm EPDM seal ring (Doyma-Grip)
* DPS Double Profile System up to NB 350 105 - 145 200
page 27
Curaflex
PIPE DUCT SYSTEM
with
page 28
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Curaflex gasket insert with DPS* includes a 40 mm solid Pipe/Cable Pipe sleeve/
external diameter core bore
EPDM rubber gasket. This extra wide and soft seal ring d [mm] D1 [NB in mm]
provides a perfect sealing on smooth service pipe surfaces.
This is ideal for sealing pre-insulated pipes (district-heating). 58 - 77 125
for installation in pipe sleeves or core bores 78 - 104 150
leak-proof against non-pressing water
105 - 145 200
gas-tight
accepts axial movements 146 - 190 250
Parts: - asymmetrically profiled steel rings: 191 - 233 300
electro-galvanized, yellow passivated and sealant coated
234 - 288 350
- elastomer: 40 mm EPDM seal ring (Doyma-Grip)
* DPS Double Profile System up to NB 350 289 - 339 400
page 29
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe/Cable Pipe sleeve/
Curaflex gasket insert with DPS* for pipes and cables external diameter core bore
outside the standard size range d [mm] D1 [NB in mm]
for installation in pipe sleeves or core bores
9 - 40 100
leak-proof against non pressing water
gas-tight 58 - 65 100
accepts angular deviations of service duct up to 8 40 - 57 125
accepts axial movements
58 - 77 130
Parts: - asymmetrically profiled steel rings:
electro-galvanized, yellow passivated and sealant coated 57 - 77 150
- elastomer: 27 mm EPDM seal ring (Doyma-Grip)* 78 - 104 160
* DPS Double Profile System up to NB 350
78 - 104 200
page 30
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Pipe/Cable Number of Pipe sleeve/
Curaflex gasket insert with DPS* for pipes and cables external diameter pipes/cables core bore
for installation in pipe sleeves or core bores d [mm] D1[NB in mm]
page 31
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Curaflex gasket insert A/0 with DPS* is a blind gasket insert. Pipe/Cable Pipe sleeve/
external diameter core bore
It ensures safe seal for unused core bores or pipe sleeves and d [mm] D1 [NB in mm]
is also recommended when services are installed later.
for installation in pipe sleeves or core bores 1 - 24 50
leak-proof against non pressing water 1 - 40 80
gas-tight
41 - 57 100
Parts: - asymmetrically profiled steel rings:
58 - 77 125
electro-galvanized, yellow passivated and sealant coated
- elastomer: 27 mm EPDM seal ring (Doyma-Grip) 78 - 104 150
* DPS Double Profile System up to NB 350 105 - 145 200
page 32
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
Technical details
Curaflex gasket insert with DPS* for pipes and cables Pipe/Cable Pipe sleeve/ Large ring
external diameter core bore diameter
Curaflex B/Ex: explosion-proof version. To find appropriate d [mm] D1 [NB in mm] GD [mm]
materials, please fill in check-list and return.
for installation in pipe sleeves or core bores 1 - 24 50 70
page 33
Curaflex
PIPE DUCT SYSTEM
with
LD
Technical details
Curaflex gasket insert with DPS* for pipes and cables Pipe/Cable Pipe sleeve/ Fixed flange
external diameter core bore diameter
as per DIN 18195 d [mm] D1 [NB in mm] D5 [mm]
for installation in pipe sleeves or core bores
for buildings with tanking membranes or with bituminous thick- 1 - 40 80 220
coating. Thin tanking membranes require two additional 41 - 57 100 240
elastomer packings according to DIN 18195 (Doyma layers 1775)
58 - 77 125 265
leak-proof against non-pressing water
gas-tight 78 - 104 150 290
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
with
LD
Technical details
Curaflex gasket insert with DPS* for pipes and cables Pipe/Cable Pipe sleeve/ Fixed flange
as per DIN 18195 external diameter core bore diameter
for installation in pipe sleeves or core bores d [mm] D1 [NB in mm] D5 [mm]
for buildings with tanking membranes or with bituminous thick-
1 - 40 80 220
coating. Thin tanking membranes require two additional
elastomer packings according to DIN 18195 (Doyma layers 1775) 41 - 57 100 240
leak-proof against non-pressing water 58 - 77 125 265
gas-tight
78 - 104 150 290
accepts angular deviations of service duct up to 8
accepts axial movements 105 - 145 200 340
Parts: - asymmetrically profiled steel rings: 146 - 190 250 390
electro-galvanized, yellow passivated and sealant coated
191 - 233 300 440
- elastomer: 2 x 27 mm EPDM seal rings (Doyma-Grip)
* DPS Double Profile System up to NB 350 234 - 288 350 490
with
Technical details
Curaflex gasket insert with DPS* for flexible cable Pipe/Cable Pipe sleeve/
external diameter core bore
ducts and cables
d [mm] D1 [NB in mm]
with cable sheathing and warm shrink sleeve to allow sealing
between cable sheathing and cable duct/cable 1 - 50 100
for installation in pipe sleeves or core bores
40 - 50 125
single sealing
leak-proof against non pressing water 40 - 95 150
gas-tight 64 - 121 200
accepts angular deviations of service duct up to 8
64 - 150 250
accepts axial movements
Parts: - asymmetrically profiled steel rings: 90 - 204 300
electro-galvanized, yellow passivated and sealant coated 205 - 280 300
- elastomer: 27 mm EPDM seal ring (Doyma-Grip)
* DPS Double Profile System up to NB 350 LD max. overall length: 55 mm
Thermisches Verschrumpfen
Subject to technical alteration without notice
Installation as shown above. Tighten nuts diagonally opposite nuts. Thermal shrinking
Please observe maximum torque values.
page 36
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Glossary of terms
Doyma-Grip
"Doyma Grip" is a highly non-slip and non-ageing elastomer compound specially developed for Doyma. It prevents friction-
reducing substances, e.g. mineral oils used as softeners, from compromising the slip-resistance of the gasket insert.
DPS
DPS "Double Profile System" refers to the two-sided, internal asymmetrical profiling of the steel rings developed by Doyma for their
gasket inserts.
Pressing water
"Pressing water is that which creates hydrostatic pressure on the gasket insert.
Gas-tight
"Gas-tight" means tight against all gases that do not attack the material (e.g. air, nitrogen, inert gases, etc.)
Electro-galvanized, yellow passivated and sealant coated (standard)
Whilst the chromating process provides almost double the corrosion protection compared to a surface that has only been galvani-
zed, the sealant doubles again the corrosion protection a four-fold improvement over simple electro galvanized steel.
Drinking water approval (KTW)
Health evaluation of plastics and other non-metallic materials in the context of the food and consumer article law for the drinking
water regulations.
Wet rooms
Wet rooms are those in which process or cleaning water or other liquids are used.
Nominal bore
Nominal bore (NB) is the nominal inside diameter; it is also the actual inside diameter of Doyma sleeves.
Non-pressing water
"Non-pressing water" puts no or temporarily only little hydrostatic pressure on the gasket insert, e.g. rain, leakage or water for
domestic or industrial use.
Black tank
"Black tank" refers to an outside wall with tanking membranes or bituminous thick-coating which seals the whole area against
water or other liquids.
Special fibre cement pipe sleeve (SFZ)
Special fibre cement pipe sleeves are made of cement reinforced with synthetic fibres. Special characteristics: virtually the same
coefficient of expansion as concrete results in perfect bonding.
White tank
"White tank" refers to a wall constructed using waterproof concrete.
Civil protection regulations
Include shock testing of technical installations, equipment and installation components.
Shock safety must be proven by appropriate test results. Operational reliability of the installation components may not be
impaired.
Subject to technical alteration without notice
Packings
According to German regulations, tanking membranes must be sandwiched between steel fixed and loose flanges protected
by durable, pliant packings. The packings must be made from the same material as the membrane or from pliant elastomers.
Packings are not included with the standard gasket insert. Accessory order no. 1775
06.06/MT 26-2
page 37
Curaflex
PIPE DUCT SYSTEM
The product
Aquagard comprises a colourless base primer and a concrete-
grey special paint top coat having a coverage of 3.5 4 m per
litre; both products can be brush or roller applied. The primer
requires about 1 hour ventilation time at room temperature and
the top coat will be touch dry within two hours at room tempera-
ture and fully cured within five to six hours.
page 38
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
page 39
Curaflex
PIPE DUCT SYSTEM
200 268 25
250 340 25
300 408 22
350 455 21
400 510 32
100 110 30
125 135 30
150 159.5 33
200 214 38
250 264 46
300 314 23
350 364 28
400 420 33
23 - 38 97 - 102
39 - 64 97 - 102
54 - 77 122 - 128
torque range 5 50 Nm
page 40
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Packings Accessories
Packings for pipe sleeves with fixed and loose flange systems (Curaflex 1775)
According to German regulations, tanking membranes must be sandwiched between durable, pliant packings.
The packings must be made from the same material as the membrane or from pliant elastomers.
In the case of fixed and loose flange systems, a perfect seal is only guaranteed when the thickness and
elasticity of the bituminous tanking membrane is great enough to ensure that it is uniformly clamped
between the flanges. In the case of tanking membranes made from very thin and/or very hard materials, com-
pression by the flanges alone is often inadequate. From our experience, we recommend the use of
elastomer packings in conjunction with tanking membranes made from ECB, PIB, PVC-P, EPDM, EVA as
well as PE mod., PE-HD and PVC.
Doyma elastomer packings are made from EPDM or CR (Chloroprene = Neoprene). They are supplied ready
for installation with pre-punched holes which align with the tapped bosses in the fixed flange.
One packing is installed by placing it on the fixed flange, then the tanking membrane is trimmed to
suit and the second packing is then laid in place over the membrane and, finally, the loose flange is installed
and tightened.
Elastomer packings are available as an extra accessory. If required, please order Curaflex 1775.
Accessories for thick bituminous compound membranes against non-pressing water Curaflex 1776/5
Accessories for thick bituminous compound membranes against pressing water Curaflex 1776/6
Installation tool for fixed/loose flange systems against pressing water suitable for multiple installations
06.06/MT 26-2
page 41
Curaflex
PIPE DUCT SYSTEM
page 42
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
1. What ma -
tact with
attach the safety data sheets or material/chemical analysis to this checklist.
2. Is the component concerned continuously exposed or exposed for a limited period (e.g. cleaning or accident) to the materials mentioned?
continuously: for a limited period: Please state:
maximum duration (h, min):
frequency (e.g. 1 x /week):................
4. What materials were previously or will be used in future for pipe lines or adjacent components?
This will enable us to make material recommendations for our gasket inserts.
.....................................................
.....................................................
.....................................................
5.Is there any additional information on how the plant is operated (e.g. alternating loading acid-alkali, service life with/without
rest periods)?
....................................................
....................................................
....................................................
..................................................
Assessment: .....................................................................................................................................................
.....................................................................................................................................................
06.06/MT 26-2
.....................................................................................................................................................
page 43
Doyma DL LINK CHAINS
Technical details
Annular Overall
Doyma DL link chains consist of individual sealing modules whose Sealing Pipe-
space length
module d [mm]
number and size are designed according to the annular space rs [mm] Lt [mm]
between the media pipe/cable and the core bore/pipe sleeve/ DL 200 21.3 - 323.9 12.5 - 17.0 70
service duct to be sealed. The link chain is therefore also suitable
DL 250 20.0 - 323.9 15.5 - 21.0 70
for retrofit installations.
DL 275 4.0 - 63.9 15.5 - 21.0 70
DL sealing module B with broad design for high hydrostatic loads DL 300 32.0 - 406.4 17.5 - 24.0 90
consists of two adjoining rubber sealing elements between the
DL 325 88.9 - 711.0 23.0 - 32.0 110
pressure elements.
DL 350 14.0 - 323.9 23.5 - 33.0 110
The range of sealing modules B is from DL 200, for annular DL 375 16.0 - 323.9 31.0 - 40.0 110
space widths of 12.5 - 17.0 mm, to DL 650, for annular space DL 400 139.7 - 1220.0 36.0 - 46.0 140
widths of 71.0 - 85.0 mm (see table).
DL 415 44.5 - 323.9 36.0 - 46.0 140
DL sealing modules are available in different variations: DL 425 133.0 - 1220.0 28.0 - 38.0 140
- with galvanized screws or screws in stainless steel DL 475 33.7 - 1220.0 40.0 - 50.0 140
- with modules made of EPDM, EPDM for drinking water or NBR DL 500 82.5 - 1220.0 58.0 - 72.0 150
DL 525 133.0 - 1220.0 53.0 - 64.0 150
Please use our calculating program to find the exact specification
for the link chain required. DL 575 80.0 - 1220.0 47.0 - 60.0 140
DL 600 219.1 - 3000.0 80.0 - 98.0 190
Advantages
DL 650 180.0 - 1220.0 71.0 - 85.0 160
Expansion-free Y-connection technology
Continuous AquaStop safety groove
Distortion-resistant pressure elements
Subject to technical alteration without notice
Connect link chain components Connect both ends Push link chain into final position Tighten screws
06.06/MT 26-2
page 44
Seite R-1-2
Doyma DL LINK CHAINS
The range of sealing modules S is from DL 200, for annular DL 375 16.0 - 323.9 31.0 - 36.5 70
space widths of 12.5 - 15.9 mm, to DL 650, for annular space DL 400 139.7 - 1220.0 36.0 - 43.5 90
widths of 71.0 - 81.5 mm (see table).
DL 415 44.5 - 323.9 36.0 - 43.5 90
DL sealing modules are available in different variations: DL 425 133.0 - 1220.0 28.0 - 35.5 90
- with galvanized screws or screws in stainless steel DL 475 33.7 - 1220.0 40.0 - 47.5 90
- with modules made of EPDM, EPDM-KTW or NBR DL 500 82.5 - 1220.0 58.0 - 68.5 110
DL 525 133.0 - 1220.0 53.0 - 61.3 110
Please use our calculating program to find the exact specification
for the link chain required. DL 575 80.0 - 1220.0 47.0 - 56.8 90
DL 600 219.1 - 3000.0 80.0 - 90.0 140
Advantages
DL 650 180.0 - 1220.0 71.0 - 81.5 110
Expansion-free Y-connection technology
Continuous AquaStop safety groove
Distortion-resistant pressure elements
Subject to technical alteration without notice
page 45
Doyma DL LINK CHAINS
Technical details
In order to accommodate your requirements, we supply the NB of core bore Core bore -
Media tube-
or pipe sleeve tolerances (mm)
complete DL link chain pre-assembled in the DL sealing box.
for core bore or pipe sleeve diameters from 50 mm to min. 49 11-19
50
350 mm max. 53 20-25
chain around the service pipe/ nut, washer and pressure plates) min. 347 239-253
350
cable (if necessary, compress or are reconnected in the correct max. 354 265-275
expand the sealing elements) sequence and lightly screwed to- 276-286
and connect the ends together. gether. Push the assembled link
chain into position and tighten
the screws.
06.06/MT 26-2
page 46
Seite R-1-2
Doyma DL LINK CHAINS
Technical details
Core bore -
In order to accommodate your requirements, we supply the NB of core bore
tolerances (mm) Media tube-
or pipe sleeve
complete DL link chain pre-assembled in the DL sealing box.
for core bore or pipe sleeve diameters from 50 mm to 350 mm min. 49 11-19
50
for media pipe diameters from 11 mm to 286 mm max. 53 20-25
and connect the ends together. gether. Push the assembled link min. 347 239-253
350
chain into position and tighten max. 354 265-275
the screws. 276-286
06.06/MT 26-2
page 47
Curaline
CABLE DUCT SYSTEM
Curaline BKD 150 Cable duct system with bayonet action lock
BKD 150
Dichtungseinsatz A
Technical details
No. of spigots Inside of spigot cable-
leakproof cable entry for installation in walls and floors (system cap) [mm] [mm]
bayonet action lock for connecting system caps to sleeve flange 1 80 26 - 78
suitable for cables 2 - 108 mm diameter 1 110 34 - 108
cables are sealed to system cap spigots using heat shrink 3 60 21 - 56
sleeves as standard 4 x 25 7 - 23
8
durable seal between sleeve and building structure assured by 4 x 35 12 - 33
page 48
Seite 1
Seite R-1-2
Curaline
CABLE DUCT SYSTEM
Wall thickness in mm
Sleeve with a flange on one end
System identification
BKD 150-2x3-K2/(L)
Ordering example:
Double flange sleeve with bayonet action lock
assembled in a battery of 2 x 3 units
BKD 150 - 2 x 3 - K 2 / L
Wall thickness in mm
Sleeve with a flange on both ends
3 sleeves in a row
2 sleeves one above the other
System identification
Angled sleeve
Installation sketch for sleeve at 45 angle
Ordering example:
Angled double flange sleeve in 45 position with bayonet
action lock
BKD 150 - S45 - K 2 / L
45
Wall thickness in mm
Sleeve with a flange on both ends
Sleeve in 45 position
Polystyrene System identification
wedge
Installation form
with holes for
nail-fixing
Subject to technical alteration without notice
06.06/MT 26-2
Lab = 250 mm
page 49
Curaline
CABLE DUCT SYSTEM
Aluminium flange AF System cap with spigot coupling System cap with duct connection socket
suitable for sealing in front of core bores to adapt smooth-faced cable ducts with for connecting smooth-faced cable ducts
in walls and floors. Supplied with flange 110, 125, 140 or 160 mm outside dia- with 125, 140 or 160 mm outside diameter.
packing, protection cap and installation meter. An O-ring on the inside of the Accompanying heat-shrink sleeve provides
accessories. coupling provides the seal. the seal.
For use with system caps or KSS system. Order No.: BKD 150-DSM 110 Order No.: BKD 150-DM 125
Max. core bore diameter 150 mm. BKD 150-DSM 125 BKD 150-DM 140
Flange size: 235 x 235 mm BKD 150-DSM 140 BKD 150-DM 160
Order No.: BKD 150-AF 235 BKD 150-DSM 160 Subject to technical alteration without notice
System cap with one spigot System cap with three spigots System cap with eight spigots
and accompanying heat-shrink sleeve, and accompanying heat-shrink four are open with accompanying heat-shrink
suitable for one cable 34 - 108 mm sleeves, suitable for three cables sleeves and four are blanked off, suitable for
diameter. 21 - 56 mm diameter. 4 cables 7-23 mm diameter and 4 cables
Order No.:BKD 150-D1/110 Order No.: BKD 150-D3/60 12 - 33 mm diameter.
suitable for one cable 26-78 mm Various finger shrouds AK or blind Order No.: BKD 150-D8/35/25
06.06/MT 26-2
page 50
Seite R-1-2
Curaline
CABLE DUCT SYSTEM
Melt tape SKB Articulated spanner - GSS Square socket key VMS
a self-fusing tape with excellent with adjustable arm for removal for rapid removal and
adhesive properties and assembly of sleeve protection replacement of BKD 150 slee-
tape thickness 1 mm, plugs, system caps and KSS duct ve protection plugs.
tape width 50 mm, adaptors. Order ref.: VMS
roll length 3.30 m Order ref.: GSS
Order ref.: SKB
page 51
Curaline
CABLE DUCT SYSTEM
Technical details
leakproof cable entry for installation in walls and floors
No. of spigots inside of spigots cable-
screw thread for connecting system caps to sleeve flange
(system cap) [mm] [mm]
suitable for cables 2 - 73 mm diameter
cables are sealed to system cap spigots using heat shrink 1 75 26 - 73
sleeves as standard 3 30 12 - 28
durable seal between sleeve and building structure assured by 5 20 7 - 18
the expanding seal system Ld : 140 mm min.
compatible with existing duct systems
additional protection for buried cable runs between buildings is
provided by the Curaline KSS duct system
materials are ecologically friendly and highly resistant against
chemicals
page 52
Seite R-1-2
Curaline
CABLE DUCT SYSTEM
Wall thickness in mm
Sleeve with a flange on one end
System identification
KD 85-2x3-K2/(L)
Ordering example:
Double flange sleeve
assembled in a battery of 2 x 3 units
KD 85 - 2 x 3 - K 2 / L
Wall thickness in mm
Sleeve with a flange on both ends
3 sleeves in a row
2 sleeves one above the other
System identification
Angled sleeve
Installation sketch for sleeve at 45 angle
Ordering example:
Angled double flange sleeve in 45 position
KD 85 - S45 - K 2 / L
45
Wall thickness in mm
Sleeve with a flange on both ends
Sleeve in 45 position
Polystyrene System identification
wedge
Installation form
with holes for
nail-fixing
Subject to technical alteration without notice
06.06/MT 26-2
Lab = 200 mm
page 53
Curaline
CABLE DUCT SYSTEM
Aluminium flange AF System cap with spigot coupling System cap with duct connection socket
suitable for sealing in front of core bores to adapt smooth-faced cable ducts for connecting smooth-faced cable ducts
in walls and floors. Supplied with flange with 75 or 110 mm outside diameter. with 85 or 110 mm outside diameter.
packing, protection cap and installation An O-ring on the inside of the coupling Accompanying heat-shrink sleeve provides
accessories. provides the seal. the seal.
For use with system caps or KSS system. Order No.: KD 85-DSM 75 Order No.: KD 85-DM 85
Max. core bore diameter 85 mm. KD 85-DSM 110 KD 85-DM 110
Flange size: 150 x 150 mm
Order No.: KD 85-AF 150 Subject to technical alteration without notice
System cap with one spigot System cap with three spigots System cap with five spigots
and accompanying heat-shrink sleeve, and accompanying heat-shrink and accompanying heat-shrink sleeves,
suitable for one cable with diameter sleeves, suitable for three cables suitable for five cables with max. 7 - 18 mm
26 - 73 mm. with diameter 12 - 28 mm. diameter.
Order No.: KD 85-D1/75 Order No.: KD 85-D3/30 Order No.: KD 85-D5/20
Various finger shrouds AK or blind plugs
06.06/MT 26-2
page 54
Seite R-1-2
Curaline
CABLE DUCT SYSTEM
Curaline KD 85 Accessories
page 55
Curaline
CABLE DUCT SYSTEM
KSS
D i c h t u n g sein s a t z A
KSS Variations:
- KSS B150: for connection to Curaline cable entry BKD 150
- KSS 85: for connection to Curaline cable entry KD 85
page 56
Seite R-1-2
Curaline
CABLE DUCT SYSTEM
System components
System connector D (for BKD 150) System connector D (for KD 85) Leakproof sleeve with combiframe K
allows gas- and watertight bayonet allows gas- and watertight screw for connecting system connector or
connection to leakproof sleeve. connection to leakproof sleeve. system caps.
Supplied for system KSS B150 Supplied for system KSS 85 Supplied for system KSS B150, KSS 85
page 57
Curaline
CABLE DUCT SYSTEM
Order. No Order. No
Order. No Order. No
Order. No Order. No
Order. No Order. No
page 58
Seite R-1-2
Curaline
CABLE DUCT SYSTEM
Properties
suitable for potential balancing
great safety from the connecting fasteners eg M12 bolts
gas- and water-tight
delivered ready to suit floor and wall shuttering
durable identification of the earthing
available in zinc plated mild steel and stainless steel Earthing insulator GE-A/L
virtually any length supplied Rigid earthing anchor for welding connection to a reinforcement
and for flush casting in with M12 connecting thread at one end.
Order No. GE-A/L (L = wall thickness in mm)
Subject to technical alteration without notice
page 59
Curaline
CABLE DUCT SYSTEM
page 60
Seite R-1-2
Curaline
CABLE DUCT SYSTEM
Curaflex MS/C Curaflex gasket insert for flexible cable ducts and
cables
with cable sheathing and heat shrink sleeve to
allow sealing between cable sheathing and cable
duct/cable
for installation in pipe sleeves or core bores
double sealing with 3 mm EPDM orange coloured
centre ring
leak-proof against pressing water
with DPS Double Profile System up to NB 350
Parts: - asymmetrically profiled steel rings:
electro-galvanized, yellow passivated and
sealant coated
- elastomer: EPDM-seal rings Doyma-Grip
Curaflex MS/A Curaflex gasket insert for flexible cable ducts and
cables
with cable sheathing and heat shrink sleeve to
allow sealing between cable sheathing and cable
Subject to technical alteration without notice
duct/cable
for installation in pipe sleeves or core bores
single sealing
leak-proof against non-pressing water
with DPS Double Profile System up to NB 350
Parts: - asymmetrically profiled steel rings:
electro-galvanized, yellow passivated and
06.06/MT 26-2
sealant coated
- elastomer: EPDM-seal ring Doyma-Grip
page 61
Curaflex
PIPE DUCT SYSTEM
Materials
The sleeves are manufactured, in accordance with the numerous constructional requirements, from special fibrous cement and/or
steel for the commonly encountered conditions of pressing and non-pressing water and ground moisture.
Please note: If Curaflex special fibre cement sleeves will be in constant contact with pressing water, a preventive coating with
Aquagard primer and special paint is recommended.
Surface treatment
Electro-galvanized mild steel (DIN 50961), yellow passivated and sealant coated.
Passivating approximately doubles the corrosion resistance of electro-galvanized steel;
Coating doubles the resistance yet again a four-fold improvement over simple electro-galvanized steel.
Stainless steel grades 304 and 316 are supplied in pickled condition.
page 62
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Technical information
Products
Special fibre cement pipe sleeves:
Curaflex 3000: Sleeve with grooved outer face
Curaflex 3001: Sleeve with additional flange suitable for structures with bituminous thick-coating
Special fibre cement pipe sleeves with fixed and loose flange made of cast iron:
The Curaflex 4000 sleeve combines the advantages of the special fibre cement sleeve with the durability of cast iron.
Curaflex 4006: Sleeve with bonded cast iron fixed flange for sealings on buildings with tanking membranes,
leak-proof against pressing water.
Curaflex 4005: Sleeve with bonded cast iron fixed flange for sealings on buildings with tanking
membranes, leak-proof against non-pressing water.
Doyma service
The depth of our experience is your assurance: Whether you require a sleeve with a mitred cut to suit a tunnel
penetration, for example, or a sleeve with a fixed and loose flange set at an angle whatever site condition
needs to be met, we will provide the optimum solution.
Subject to technical alteration without notice
06.06/MT 26-2
page 63
Curaflex
PIPE DUCT SYSTEM
Doyma develops and produces gasket inserts for sealing service ducts through walls, ceilings and floors for the
widest variety of demands.
The Curaflex gasket inserts fulfil the following construction engineering requirements:
sealing against pressing and non-pressing water
for installation in pipe sleeves or core bores
with fixed and loose flange according to DIN 18195 T9
split versions for retrofit installations
angular deviation of service duct up to 8 accepted
fire protection: With intumescent systems from Doyma, tested and approved to DIN 4102 of the Building
regulations, fire compartments can be penetrated with confidence
explosion protection
gas-tight to seal against all gases that do not attack the material (e.g. air, nitrogen, inert gases, etc.)
The spectrum of applications for gasket inserts encompasses structural and civil engineering, especially water
lines, heating and district heating. Other applications include, for example, service ducts in swimming pools,
tank installations, gas pipes and shelters.
Further uses occur in manholes, sewage works and in constructions with or without tanking membranes and
thick-coating renders.
Function principles
The assembly comprises rubber gaskets between profiled steel rings, which fit over
the service pipe/cable inside the sleeve or core bore. Tightening the nuts compres-
ses the gaskets between the steel rings and thereby securely closes off the annular
void between the building service and the sleeve or core bore.
Doyma DPS
The profiling of the steel rings (DPS* = Double Profile System) features a more intel-
ligent method of pressure distribution: gently in the direction of the service, strongly
in the direction of the sleeve/core bore.
*) DPS up to NB 350 mm
Materials used
The standard gasket insert comprises minimum 6 mm thick, asymmetrically profiled
steel rings. The steel rings are electro-galvanized, yellow passivated and sealant
coated as standard (ggv).
To these are added according to the sealing requirement for pressing or non-
pressing water one or two 27 mm thick elastomeric rings which, as standard, are
made of fatigue-proof special EPDM compound "Doyma-Grip". Gasket inserts with
two elastomeric rings have an additional 3 mm thick orange-coloured EPDM centre
DPS = Double Profile System
ring. This centre ring causes homogenous and uniform distribution of the compres-
sion pressure on the service pipe or cable and sleeve/core bore.
high low
06.06/MT 26-2
pressure pressure
page 64
Seite R-1-2
Curaflex
PIPE DUCT SYSTEM
Technical information
Surface treatment
Electro-galvanized mild steel (DIN 50961), yellow passivated and sealant coated.
Passivating approximately doubles the corrosion resistance of electro-galvanized steel;
Coating doubles the resistance yet again a four-fold improvement over simple electro-galvanized steel.
stainless steel grades 304 and 316 are supplied in pickled condition.
Additional properties:
Excellent chemical resistance, resistant to almost all acids and alkalis as well as brine.
Suitable for potable water (copy of KTW approval upon request).
High thermal and mechanical properties.
Not suitable for oils, fats, fuels and solvents.
Temperature range: from - 40 C to + 140 C.
NB:
1: Curaflex gasket inserts against pressing water are suitable for sealing against pressing ground water. If there is continuous
water pressure in high rise buildings, e.g. in tanks or similar containers the design of the gasket insert needs to be checked
to see that it meets the requirements of pressure tightness.
2: Gasket inserts are not fixed points and are not designed for load bearing. If settlement of pipelines is expected, centering
Subject to technical alteration without notice
rings or spacers should be fitted in the sleeve or core bore during installation.
06.06/MT 26-2
page 65
Doyma DL LINK CHAINS
This modular system, comprising just 16 sizes of sealing module, enables pipes and cables from
21 mm to 1220 mm dia. to be successfully sealed.
The choice of the sealing module required for the seal depends on the pipe diameter and is cal-
culated using the formula overleaf or by computer progamme. This software can be downloaded
from the internet (www.doyma.de).
The benefits
Doyma DL sealing modules have specific advantages which make this sealing system secure.
- Expansion-free Y-connection technology
The unique geometry of the rubber sealing elements ensures their sealing efficiency no leak path is possible.
- Continuous AquaStop safety groove
The continuous AquaStop safety groove effects a more efficient compression of the sealing elements and
therefore provides a greater sealing performance.
- Distortion-resistant pressure elements
The inside perimeter profile of the pressure elements ensures they bed positively into the body of the rubber
elements during tightening; this ensures they maintain their designed, relative position during installation.
Models
Doyma supply sealing modules for different hydrostatic loading cases. There is a broad version DL Sealing
module B for high loads and a slim version DL Sealing module S for low loads.
The components of the DL sealing modules can be supplied in various materials, depending on the performance
requirements:
- Screws: galvanized or stainless steel
- Elastomer: EPDM, EPDM-KTW, NBR
Please note:
- Doyma DL link chains are suitable for sealing in the ground. If used for heavy loads in high rise
buildings, e.g. in tanks or similar containers, movement of the DL link chain, which might be
caused by excessive maximum pressure, has to be prevented.
- Doyma DL link chains are not fixed points and are not designed for load bearing. If settlement of
pipelines is expected, centering rings or spacers should be fitted in the sleeve or core bore during
Subject to technical alteration without notice
installation.
06.06/MT 26-2
page 66
Seite R-1-2
Doyma DL LINK CHAINS
D+d
No. of sealing modules n = x 1.57
BL
Example:
Bow length value BL of sealing module 475 B = 68,0
500 + 406
x 1.57 = 20.91 n = 20.91 21 units of sealing module DL 475 B
68.0
If the number after the decimal point is smaller than 0.5, it will be
rounded down, otherwise round up to the next full number of links.
Sleeves
With a flange on one or both ends, sleeves are set flush in the shuttering and cast in either individually or as a multiple
battery. The innovative combination of expanding seal system and sleeve construction ensures a perfect bonding to the
concrete.
Curaline BKD- and KD-systems are delivered to site in the length to suit wall thickness.
System caps
System caps offer a multiplicity of possibilities for sealing cables and cable ducts. Curaline BKD system caps have a
bayonet action lock to allow quick and easy installation. Curaline KD system caps with screw thread offer the same opti-
mum possibilities and solutions. System caps accept cables with different diameters to be ducted and sealed. Heat shrink
sleeves are delivered as standard with the system. Cold shrink sleeves are available as an option.
Materials
Curaline BKD- and KD-Systems consist of PC (Polycarbonate), ABS (Acrylonitrile-Butadiene-Styrene-Polymer) and PVC-U
(Polyvinylchloride), the solid rubber gasket is made of EPDM (Ethylene-Propylene-Di-monomer).
page 68
Seite R-1-2
Doyma Sealing Systems
Pipes and cables are used to supply industrial plant, along with it is too late and structural damage has already occurred. Doyma
commercial and residential buildings. All too often the focus of offers top quality, tried and tested ducting systems which ensure last-
attention is restricted to the function of water, gas, electricity or ing protection against water and insulation against noise and fire.
data supply. Little attention is given to the sealing and housing of Doyma therefore provides excellent preventative measures against
the pipes and cables passing through the walls or ceilings until structural damage.
Seite R-1-2
DOYMA sealing systems for pipes and cables