Académique Documents
Professionnel Documents
Culture Documents
Regional and international power trans- Fiber optic cable links are the foundation
mission lines require modern network of such communications systems, since they
automation and remote control systems. provide high capacity transmission over
To accomplish this, power utilities started long distances. At the same time they are
very early to equip their lines with reliable not influenced by electromagnetic fields
telecommunications connections. Telecom- and do not exhibit any cross-talk, which
munications deregulation now opens up are important consideration for installation
the opportunity for power utilities to lease on high voltage (HV) lines.
dark fibers or transmission capacity, or to
become telecom operators themselves.
Rev 0, Jan. 02
Metallic Dielectric
Solutions Solutions
Optical Ground Wire Optical Phase Conductor Metallic Aerial Self-Supported All Dielectric Self-Supporting All Dielectric Lashed
OPGW OPPC MASS ADSS ADL
The optimal solution for each project parameters such as the maximum load for
demands a careful evaluation of many towers, possible wind and ice loads, etc.
Rev 0, Jan. 02
A Complete Solution
www.alcatel.com/opticalfiber
Copyright 2002 ALL RIGHTS RESERVED
S ometimes, medium-voltage lines and electrical resistance of the cable must be be installed freely, hanging between the
high-voltage lines up to 150 kV are properly adapted to that of the substituted insulator strings on strong poles, or it
not equipped with a ground wire. phase conductor. can be placed on an insulator itself. At
Consequently, replacement by an both ends of the line, electrical current
Generally, OPPCs are manufactured
OPGW is not feasible. To equip such and optical fibers must be separated.
according to the same basic designs used
a transmission line with optical fibers, This can be done by special separators
for OPGW. However, since optical fibers
an Optical Phase Conductor (OPPC) may consisting of two splice closures placed
are installed on high-voltage lines in the
be used. Here again, the optical cable at the top and bottom of an insulator.
case of the OPPC, the splicing technology
has to provide two different functions. It
is different. Connections in the line must Like the OPGW, the OPPC has the
must carry the permanent current in the
be carried out in a way that the cable, as advantage of combining functions
three-phase system, and it has to house
well as the joint box, do not directly touch without placing additional loads on
and protect the optical fibers. To keep
ground potential. A joint box can either the towers.
the electrical system running well, the
Where the substitution of a ground wire cable. This is a small-sized armored sag requirements only, because the cable
or phase conductor is either impossible cable for additional installation at the does not have any electrical function.
or uneconomical, additional cables can center of towers. To minimize the
be installed on towers. The only function additional load, weight and diameter
that these cables have is to house and are significantly reduced. The typical
protect the optical fibers. A universal diameter range of MASS cables is
solution for all voltage levels is the between 9 and 12 mm. The armoring is
Metallic Aerial Self-Supporting (MASS) optimized according to span length and
Another well-known cable solution for ADSS is a universal solution for a large
additional installation on medium and variety of applications. However, special
high-voltage lines is the All-Dielectric attention must be paid if the cable is to
Self-Supporting (ADSS) cable. ADSS be installed on high-voltage lines, to
does not contain any metallic elements. prevent dry-band arcing. Special
The fibers are placed in several stranded sheathing material and software to
loose plastic tubes which are covered by calculate optimum placement on the
one or two plastic jackets. To make the towers make this technology usable for
cable self-supporting, it contains strength line voltages of up to about 275 kV.
elements made of aramid yarns. The With a capacity of greater than 144
excellent strength-to-weight ratio of this fibers, this cable technology offers a
material ensures the low weight of ADSS good opportunity to equip medium and
and limits additional loads on towers. By high-voltage lines with optical fibers.
Copyright 2002 ALL RIGHTS RESERVED