Vous êtes sur la page 1sur 5

UNDERGROUND SUMP (WSM)

INPUT
Capacity of fire sump 75 m3 CONCRETE
Capacity of drinking sump 15 m 3 Grade of concrete, fck
Free board 0.3 m Grade of steel, fy
Size of sump Combined bending and tensile stress in
Length of fire sump 8.4 m resistance, bt
Width of fire sump 4.4 m Direct tensile stress in resistance, ct
Depth required for sump(with FB) 2.33 m Permissible bending stress in concrete, cbc
Depth provided 2.4 m
Permissible stress in steel, st
Length of drinking sump required 1.62 m
Length provided for drinking sump 1.65 m

Calculations
VERTICAL WALL

Max BM at the bottom of vertical walls 19.768 kNm /m


( From STAAD)

Thickness of wall required 243.52 mm


Cover,c 40 mm
Overall thickness required 288.52 mm
Overall thickness Provided 300 mm

Design
Modular ratio,m 9.33
Vertical Ast required 692.83 mm2 /m Check for uncracked section
Min Ast required as per IS 3370 360 mm2 /m
Diameter of bar 10 mm
Spacing required 127.85 mm /m
Spacing provided 120 mm /m

Horizontal reinforcement
Max BM at the edges of vertical walls ( 5.831 kNm /m
From STAAD)
Max shear stress of vertical plate 0.51 N/mm2
element (From STAAD)
Length of plate element,Lp (STAAD) 0.86 m
Horizontal Ast required 912.43 mm2 /m
Diameter of bar 12 mm
Spacing required 122.95 mm /m
Spacing provided 120 mm /m

TOP SLAB

Max BM (From STAAD) 16.62 kNm /m

Thickness of wall required 223.29 mm


Cover,c 40 mm
Overall thickness required 268.29 mm
Overall thickness Provided 300 mm

Design
Modular ratio,m 9.33
Vertical Ast required 582.50 mm2 /m
Min Ast required as per IS 456 360 mm2 /m
Diameter of bar 10 mm
Spacing required 155.84 mm /m
Spacing provided 150 mm /m

BASE SLAB

i) Uplift by water 20 kN/m2


ii) Water pressure on slab when tank is 24 kN/m2
full

Max BM (From STAAD) 29.54 kNm /m

Thickness of wall required 297.69 mm


Cover,c 40 mm
Overall thickness required 342.69 mm
Overall thickness Provided 350 mm

Design
Modular ratio,m 9.33
Vertical Ast required 865.60 mm2 /m
Min Ast required as per IS 456 420 mm2 /m
Diameter of bar 12 mm
Spacing required 150.29 mm /m
Spacing provided 140 mm /m
MP (WSM)

SOIL
Grade of concrete, fck 30 N/mm 2
Angle of internal friction, 34 degrees
Grade of steel, fy 500 N/mm 2
Density of soil, 22 kN/m3
Density ofwater,w 10 kN/m3
ned bending and tensile stress in 2 N/mm2
resistance, bt Surcharge,sur 20 kN/m3
tensile stress in resistance, ct 1.5 N/mm2 Coefficient of pressure,Ka 0.28
ble bending stress in concrete, cbc 10 N/mm2 Depth of soil 2m

rmissible stress in steel, st 130 N/mm2

Case i
Tank full of water with no earth pressure

Lateral pressure
At top of vertical wall 0 kN/m2
24 kN/m
2
Check for uncracked section At bottom of vertical wall

Case ii
Tank empty with earth pressure and surcharge (Water Table below base sla

Lateral pressure
At ground level in vertical wall 5.65 kN/m2
At bottom of vertical wall 18.09 kN/m2

Case ii
Tank empty with earth pressure and surcharge (Water Table at ground leve

Lateral pressure
At ground level in vertical wall 5.65 kN/m2
At bottom of vertical wall 32.44 kN/m2
ater Table below base slab)

Water Table at ground level)