Vous êtes sur la page 1sur 15

---lEROY

_SOMER
4010 en - 03.2011 / b

R729

Installation and maintenance


LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

CONTENTS

1. Presentation
1.1. Description
1.2. Characteristics:
1.3. Environment:
1.4. Overall dimensions

2. Definition of potentiometers, jumpers and LEDs:


2.1. Layout
2.2. Definition of potentiometers:
2.3. Definition of jumpers:
2.4. Definition of LEDs:
2.5. Definition of signalling contacts:

3. Operation and settings:


3.1. U=U (3F)
3.2. Power Factor (2F)
3.3. Function kVAr (2F)
3.4. Function 4/20mA
3.4.1. Alternator PF setpoint adjustment:
3.4.2. kVAr setpoint adjustment:
3.4.3. Voltage setpoint adjustment:
3.4.4. Mains PF adjustment:
3.5. External voltage potentiometer:
3.6. Limitation of minimum excitation current
3.7. Limitation of maximum excitation current
3.8. Limitation of stator current
3.9. Overvoltage detection:
3.10. Rotating diode fault detection:
3.10.1. Rotating diode fault detector adjustment:

4. Diagrams
4.1. Block diagram
4.2. Standard diagram
4.2.1. Alternator + R 449 + R 729
4.2.2. Terminal block C:

5. Commissioning

6. Troubleshooting

2 2
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

1. Presentation

1.1. Description
When combined with the R 449 or R 452 or R448, the R 729 has the following functions:

Regulation functions
- Regulates PF or kVAr when the alternator is in parallel with the mains (2F).
- Matches alternator voltage to the mains voltage before connection (3F). The alternator can be installed on
its own or in parallel with other alternators.

4/20mA function
- Receives a 4/20mA current in order to:
- replace the stator voltage, alternator PF or alternator kVAr set point,
- control the PF or kVAr at a precise point of the installation (mains PF).

Limitation
- Limits the no load or full load minimum excitation current.
- Limits the maximum excitation current when the alternator is short-circuited.
- Limits the stator current.

Fault detection
- detects stator over voltage.
- detects a faulty rotating diode.

- LED signalling of functions 3F, 2F(alternator PF), 2F(kVAr), mains PF and 4/20mA
- LED and contact signalling of a rotating diode fault, a stator over voltage, a minimum excitation current, a
maximum excitation current or a maximum stator current
- Absence of 4/20mA current signalled by contact

The board is encapsulated in a box. It can be mounted in the alternator terminal box.
The R 729 will always be mounted in proximity to the R 449 or R 452 or R448 units (Max 5m)

1.2. Characteristics:
- PF regulation
Range: 0.95AV to 0.7AR
Accuracy: +/-0.02 of PF at rated power
- kVAr regulation
- Stator current data input: max 1A
- U=U
Range: +/-15%Un
- Measurement of excitation current: maximum 7A
- Single phase alternator voltage sensing: 0-110-400V 50 or 60Hz
- Single phase mains voltage sensing: 0-110-400V 50 or 60Hz

1.3. Environment:
- Operating temperature: -20'C to +70'C
- Storage temperature: -55'C a +85'C
- Vibrations:
Below 1OHz: 2mm half peak amplitude
Between 1OHz and 1OOHz: 1OOmm/s
Over 1OOHz: 4G
- EMC - emissions:
According to the generic standard: EN 50081-2 (dec93) / EN 55011, Gr1 CLB

3 3
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

1.4. Overall dimensions

140

110

r,h\
\;I:'.)
H::::2:::::::::_:_:::_)ol ~~

~
N
N

R 729

~
~
0

0
N
N

Do s...'.'....
~

niol
;111111111111

4 4
(J1 N N
..a. tot
LzJ
r
SI)
C ~
(I) i<
'< ::::!, I

U=U 2F Gain 2F
Gain
kVAr kVAr 4/20mA
Is
max
IField
IField Load
max min
IField
No
load
min
u Fault
max diode
-
0
C
::::,
2:
0
::::,
0
ti)

i
~
.....
0 C[XIXD ([)([) 0 ([) ([) ([X])([) CDCD 0 --o r--
C
0
P1 P2 P3 P4 P5 P6 P7 PB pg P10 P11 P12 ( I)
::::,
P 17([)

IField -
J1
1
(')
~
(')
?;;
(')
~
;:o
m.
(')
)>
"'
.,;s::~- -
3
(I)

..,(I)
t/1
~~
I
] I excitation ;:o ;:o J4

~
(J)
Fault
IField +

S2
2
!!l.
0
!i!
\SI
m.
~
-I
CD
:,
(J)
g
(')
!i!
\SI Led1 e diodes
detector
c~
3 ] CT II
Umax
Cl~

l
Led1 .
9:1"'"5 S1 4
1 ul l:'4~
ov --
5 on[ ;;~~
off[ 0 0 0 ~ Led1 e IField min 1DJ
::::,
lzJ QO

-6- M,;os C.
s::
)>
110V voltage C
P13 P14 P15
"' IField max Ir
~~
380V

ov
7
-8-
888 4/20mA
CA1
+/-4/20mA ([)
P18
,.,. 3c,]
Led .

ls max
m
C
I!'! ....J ~
I\) ~
-9- ] Gooera<o, [QQQ]
110V
voltage
off ..2,
36 -
35 -
C9] No
4/20
\0 ~
380V ....1ll.. ,...., P16 ,.j,
on
,....,
Green LB>S
CAB IField max!OOO!
CA7 lsator max! 000!
CD
Stabilite
CA10 IField mi{QQQJ
Q91 Q 9 2 ~ 3 ~ ~ r--
0
ExternaPotentiometers GND
~
4/20 0
U=U 2F kVAr Cos R - +
,---, ,---, KVAr ,------,
V~e Cos AT ,------, 4/20mA -terminals
......

0 0
0
(f>1 I Ill I I I LL HJJ IDJ JS (1)
:::J
I
0
c,J
N
0
......
......
O"
(J1
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

2.2. Definition of potentiometers:


Representation of a potentiometer

IDefinition of potentiometers I Potentiometer actions


Position 0 Position 5 Position 10
P1 = U=U . +
P2=PF 0.95 leading 0.9 laaaing 0,7 lagging
P3 = PF gain . +
P4 = kVAr Capacitive kVAr Equivalent to Inductive kVAr
PF = 0.9 laaaing
P5 = kVAr gain (Slow) + (Fast)
P6 = 4/20mA reference
P7 = I stator max Limited Not limited
PB= lex max Limited Not limited
P9 = On load lex min. Not limited Limited
P10 = No load lex min Not limited Limited
P11 = Overvoltage Min voltage Max voltage
P12 = Rotatina diode fault threshold No action
P13 = 4/20mA adjustment (OV)
P13 = 4/20mA adjustment (Range)
P6 = 4/20mA gain . +
P16 = Stability . +
P17 = lex measurement adjustment Factory adjusted
P18 = Pulse adjustment Factory adjusted

2.3. Definition of jumpers:


- Jumpers CA1 to CA5 are on the 4/20mA function
CA 1 = Sign inversion CA4 = Uvoltage
CA2 = Ucoscp CA5 = Mains PF
CA3 = UkVAr
From CA2 to CA5, only one of these functions can be selected at a time.
- Validation of protections
CAB = lexc max CA7 = lstator max CA10 = lexc min

2.4. Definition of LEDs:


LED 1 = U=U LED 7 = lstator max
LED 2 = 2F (coscp AT) LED 8 = lexc max
LED 3 = kVAr LED 10 = lexc min
LED 4 = Mains PF LED 11 = Um max
LED 5 = 4/20mA present LED 12 = Rotating diode fault

2.5. Definition of signalling contacts:


C7: I stator max C10: lexc min
C8: lexc max C11: Overvoltage
C9: 4/20mA absent C12: Rotating diode fault detector
Characteristics of contacts: 220vAC, 0.2A

6 6
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

3. Operation and settings:

Regulation functions

3.1. U=U (3F)

This function matches the alternator voltage to the mains voltage during a mains connection request. It
works with an alternator on its own or in parallel with other alternators.
To operate this function, close contact J2-11/12, the green LED 1 will light. This voltage is adjusted by
potentiometer P1. When the alternator is connected to the mains, open contact J2-11/12

3.2. Power Factor (2F)

This function controls the alternator PF when it is in parallel with the mains.
To activate this function, close contact J2-13/14, the green LED 2 will light. The PF is adjusted by
potentiometer P2 and its gain by P3
An external (10kQ-3W) setpoint potentiometer can be added to terminals J3-26/27/28, (place the cursor at
J3-27). It is connected to the regulator by a shielded cable with its shielding connected to terminal J3-23
(maximum length 50m)

3.3. Function kVAr (2F)

This function regulates the alternator kVAr when it is in parallel with the mains.
To activate this function, close contacts J2-13/14 the J2-15/16, the green LEDs 2 and 3 will light. The kVAr is
adjusted by potentiometer P4 and its gain by P5.
An external (10kQ-3W) setpoint potentiometer can be added to terminals J3-26/27/28, (place the cursor at
J3-30). It is connected to the regulator by a shielded cable with its shielding connected to terminal J3-23
(Maximum length 50m).

3.4. Function 4/20mA

Using a 4/20 mA current supplied by the user, this function can replace the stator voltage, PF or kVAr
setpoint. When this current is the matches the PF (or kVAr) at a particular point of the installation (mains PF),
it can be used to control it.
Each of these functions is activated by setting a jumper to the ON position.
Jumper CA1 inverts the 4/20mA signal.
Only one of these 4 functions can be selected at a time.
- The PF function is selected with jumper CA2
- The kVAr function is selected with jumper CA3
- The voltage function is selected with jumper CA4
- The copy mains PF function is selected with jumper CA5
P6 is the setpoint potentiometer for the selected function.
An external (10kQ-3W) setpoint potentiometer can be added to terminals J3-32/33/34, (place the cursor at
J3-33). It is connected to the regulator by a shielded cable with its shielding connected to terminal J3-23
(Maximum length 50m).

7 7
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

3.4.1. Alternator PF setpoint adjustment:

Do not apply the 4/20mA current


Set CA1 to position 1, CA2 to the ON position, P15 = 5
Connect the alternator to the mains and select alternator PF adjustment (2F)
Adjust the PF using P2 to give the upper value of the range (E.g.: cos q> = 1)
Apply the 4/20mA current - Adjust to obtain 4mA
LED 5 should light.
Adjust with P6 to obtain the same setpoint as before (e.g.: cos q> = 1)
If this is not possible, set jumper CA 1 to 2, then repeat the same tests. (CA 1 inverses the 4/20mA signal)
Apply20mA
Adjust with P15 to obtain an inductive PF (e.g.: PF= 0.8 lagging)
With this setting, when the current varies from 4 to 20mA, the PF varies from 1 to 0.8.
In the event that there is no 4/20mA current, the setpoint automatically returns to the internal setpoint value
for the function concerned and contact C9 is closed.

3.4.2. kVAr setpoint adjustment:

Do not apply the 4/20mA current


Set CA1 to position 1, CA3 to position ON, P15 = 5
Connect the alternator to the mains and select alternator PF adjustment (2F), then kVAr adjustment.
Adjust the kVAr values using P4 to give the minimum kVAr or capacitive kVAr values (e.g.: kVAr = 0 or cos
q> = 1)
Apply the 4/20mA current - Adjust to obtain 4mA
LED 5 should light.
Adjust with P6 to obtain the same setpoint as before (e.g.: kVAr = 0)
If this is not possible, set jumper CA 1 to 2, then repeat the same tests.
Apply20mA
Adjust with P15 to obtain the maximum inductive kVAr.
With this setting, when the current varies from 4 to 20mA, kVAr varies from Oto the specified inductive kVAr
values.
In the absence of a 4/20mA current, the setpoint automatically returns to the internal setpoint value for the
function concerned and contact C9 is closed.

3.4.3. Voltage setpoint adjustment:

Do not apply the 4/20mA current


Set CA1 to position 2, CA4 to the ON position, P15 = 5
Run the alternator at no load with Un -5%Un.
Apply the 4/20mA current - Adjust to obtain 4mA
LED 5 should light.
Adjust with P6 to obtain Un -5%Un
If this is not possible, set jumper CA 1 to 2, then repeat the same tests.
Apply20mA
Adjust with P15 to obtain Un + 5%Un.
With this setting, when the current varies from 4 to 20mA, the voltage varies by +/ -5%Un.
In the absence of a 4/20mA current, the setpoint automatically returns to the internal setpoint value for the
function concerned and contact C9 is closed.

8 8
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

3.4.4. Mains PF adjustment:

Do not apply the 4/20mA current


Set CA1 to position 1, CA5 to the ON position, P15 = 5
Connect the alternator to the mains and select the alternator PF adjustment function (2F)
Apply the 4/20mA current-Adjust to obtain 12mA
LED 5 should light.
Set P6 to the centre position.
Close the mains PF contact connected to terminals J2-17/18
LED 4 should light.
If the adjustment differs, set jumper CA 1 to 2.
Adjust the gain, if required, with P15 (position 10 = maximum gain)
In the absence of a 4/20mA current, the setpoint automatically returns to the internal setpoint value for the
function used and contact C9 is closed.

3.5. External voltage potentiometer:

The external voltage potentiometer of the R 449 or R 452 (470n for +/-5%Un and 1kn for +/-10%Un) is
transferred to terminals J3-24/25 of the R 729 when these are combined with the R729.

Limiting functions

3.6. Limitation of minimum excitation current

This function only acts when the alternator is in parallel with the mains.
It controls the excitation current to adjust the amount of reactive power that the alternator can absorb at very
low load and at full load.
Potentiometer P10 adjusts the amount of reactive power that the alternator can absorb at very low load.
Potentiometer P9 adjusts the amount of reactive power that the alternator can absorb at full load.
The function is activated by setting jumper CA10 to the ON position and deactivated by setting it to the OFF
position
While the excitation current is limited, LED 10 (red) is lit and contact C10 is closed (terminals J4-41/42 ).

3. 7. Limitation of maximum excitation current

This function controls the excitation current to limit the alternator's stator current when in over-load or in the
event of repeated load surges. This limitation takes effect after a time delay of 10 seconds and at 110% of
the excitation current.
This threshold is adjusted with potentiometer P8.
The function is activated by setting jumper CAB to the ON position and deactivated by setting it to the OFF
position
While the excitation current is limited, LED 8 (red) is lit and contact CB is closed (terminals J4-39/40).

Note: When the alternator is short-circuited, the maximum excitation current is controlled with potentiometer
P5 on the R 449 or R 452 unit.

9 9
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

3.8. Limitation of stator current

This function limits the stator current (such as when starting-up large motors), by lowering the voltage (e.g.:
1.5xln).
This threshold is adjusted with potentiometer P7.
The function is activated by setting jumper CA7 to the ON position and deactivated by setting it to the OFF
position
While the stator current is limited, LED 7 (red) is lit and contact C7 is closed (terminals J4-37/38 ).

Fault detection

3.9. Overvoltage detection:

This function detects when the voltage exceeds a preset threshold value.
The threshold is adjusted with potentiometer P11.
When overvoltage occurs, LED 11 (red) is lit and contact C11 is closed (terminals J4-43/44 ).

3.10. Rotating diode fault detection:

This function detects rotating diodes that have cut-out or short-circuited


The fault threshold is adjusted with potentiometer P12
When a faulty rotating diode is detected, LED 12 (red) is lit and contact C12 is closed (terminals J4-45/46).

3.10.1. Rotating diode fault detector adjustment:

Disconnect the stem of a diode from the rotating rectifier bridge and mechanically attach it to another
part of the bridge in such a way that the anode and the cathode of the diode are at the same potential.
Disconnect the wires from terminals J4-45/46 in order to avoid a fault tripping the unit. Run the
alternator at its rated speed and voltage. The alternator must remain at no-load. It can operate at no-
load with one branch of the rectifier bridge open. Adjust P12 so that LED 12 just lights. The detector is
now set.
Note: As the diode fault detector is powered by the alternator, the fault will no longer be indicated
when the alternator shuts down.

Note: Generally speaking, as the contacts and the LEDs are powered by the alternator, signalling will no
longer be maintained when the alternator shuts down.

10 10
::::1 P11 ~ 1~ I It"'

I Excitatiai I 11 I I I ,IE,cc

~
......, ........... I '>-, I/ I
I/

I/
'-"

-
-- -
-
--
~,
0
n
~
9: 3
m en
CQ
SI)

iil
LzJ
~
i<
I
[/l

i
~
iil
3

~
P4 z
en

I Cos0/kVAr
P16 -11- ~
C r
r
Cl ~
~
Cmd

P2 t"' 0z
I'-.. Cos0
lzJ s::
~

:t>
~ -I z
....J m
z
lmpulsia, I .............
Cmd I\) :t>
z

."'"""'.~n I 1~ ;..,sion ale-reteur


V I I \0 ()
m

~mi""-~~~ Potertiometre
"ext6rieur 4/20nA
CM~
R6f Cos0/kVAr
AIBence
4/20mA C9 .i=,.
,,.., 0
......
ws~e -- 0
0

~
CA'l kVAr
4/20mA - -,1, .. CD
::::,
CA2 CorBi!J)e Cos0
- -41 4/20mA ., I
0
(,J
C~ -, ~~~Re T111sion
N
0
......

.......
......
~
-
......
C"
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

4.2. Standard diagram r-------------------------------------,I


4.2.1. Alternator + R 449 + R 729 ~-------------. I
I I

J5 t1l1
I
I
I
I Termlnal C
I
I
I
IMR01
J3
2ll
I
s1
38
r 112
81
R729 24 J8
25 ;l8
28 40
27 41
211 42
29 4,ll
llO 44
J1 411
J2 411
M 47
MAINS 4 :54
I 49 411
48
50
51

----~
52
Termina C 5'
<4(]QV I27 27 54
5!i
58
110V 126 26 57
P2
58
1511
1 25 25 80
P1
I

~----27_--,---~7
241,-----~2~4--+2'1
.. I

I
- I
I
~---------~:~:--+i--~I 8
I 151~2
1
I
I
I
- _ _ ..J
Em I
I ___
74~__.1,___1 111 I 28 211
z !JII JO JO I T 12 I Llf 121
0 ..... ::::==============:::;;:;::::au::==========:t:===::.-.r:,==i:::===1t==::~
T .. ,
I l 1 ~ - - - - - -If l ' - - - 3I2
~
::J
I
I ---~0~7-+-----<0T 4:~
I
:
5 I 11 I
. - + - - ~ ~ ~ I- ~
1
... J19
111
I
35
J8
I
I I I 20 37
I 2 I
o----~,1-~T
l I
I
II
- - - . . . l ED4
Terminal A
3 ,
.----t~-~1-- 8
I
II II
- 1P05 ~11,
._ __ 1_:n-------' 73
82 S2 2 2
I
22-~---~
72
P2 2
T
SJ P1 ~~ S1 J 3 J

p2 S2 8 rl11,8 II 8 r------------,
2 I J~1 IRT01
TID4
I S1 7 7 7 7
~ -...
l--1>1;:i(110V'J R449
p1
Pt~P2 I ?1(38CN)
3 i 14(0V'J

,11r D
Tl~r
S1 S2
14 iI IT e(E+)

9
J2
>
~
::, ;i: .___ _7_1_...._---;_ _ _...
J.4(S1)

11 11 11 11 I I
----.-+-----LI'---+'-'-----+-------+---1> 9(Z1) I 72
1
"' :::
r-~, x,-~ 2(Pu1Jl:r>------<'----<
;:i(Pu1)III>-----;'--~
; 73

A01
X1

X2
Z1

Z2 iII H-h I
08 I I
f 11(5:2)

-
0 ~ L-f~ ~-J 12
I

12
7(22
I
ll(X1)e
I
I
I
I
I
22
21
.L
fiii'-1 22
:.L 1
liil'.J,
f'Ol I
I I I
'--------~____,,.1_0
10 _ _10
_ _ _ _ _ _ _1_0_+-__.,i 10(lC2) I I

Derr. ma ,. . :-;. _. .
R20 CROO 6 8 8
_+=-----------'~---_.C,~5(~:>______
8
I T
I
1
:
I

J
1 ,11H
:
I

I
0

+ 5 -6---~---------------------------------J:!ll

12 12
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729
4.2.2. Terminal block C:

r----------------,

Terminal C
IPR01
at
e1

eo --l-+-l----11 ~ Diode faijlt detector


SI

811

57
.._-+-+,------ ~ U max.
511

55
-e--+-+---1-------a ! I Ex. min.

54

53
--l-+-l----11 ~ I Ex. max.

112

51
.._-+-+,------ ~ I Stator max.
50
.._-+-+,------ ! No 4/20mA
"'I

:j Pot. 4/20mA

411 '~1-+---.i"-'>t----,
44 f I Pot. KVAR
4.lf ~I1-+-------'\;;;;;;I--L__l==!e.J
42 +~...!::::=~-----,
41 T Pot. Pf
40y~------',nf-l

:ti? .~. .
JII~
I

:
10_ _
. ~H:e'=+=<~
.

.. _
Voluiga Pol.

4/20mA

:: I ,--~, ~~. m,ai:.eau


33+: ---~I KVAR
n + I .
I
31 (
"",.._+--------5 2F
29
I E05 I U=U

,~-t-------::~--~ "
211 ~

27
It
,. t-+------------ ..,a,ns vo age
211 I OV
I

: ~ ST7 Excitation current measure

F01

Terminal A
ST9 :]~2 E01
---+----' De energizing
u
8
I
_ _......__ __.

L----- -----------

13 13
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729
5. Commissioning

- Case of a regulator mounted in the terminal box:


It is recommended to perform initial tests in the as-delivered state. Once these tests are completed, any
external potentiometers and/or contacts can be connected in accordance with the wiring diagrams provided
with the machine.

- Case of a cabinet-mounted regulator tested with the alternator:


Connections to the machine must be checked, and in particular the voltage, stator current and excitation
current detection inputs.

- Case of a replacement regulator not tested with the alternator:


- Set the potentiometers to the same positions as on the original regulator.
- The initial tests will be performed without the limitations or the 4/20mA function. Jumpers CA2, CA3,
CA4, CA5, CA7, CA8, CA10 must therefore be set to the Off position

- Run at no-load and full load, then connect to the mains.


-Adjust the functions U=U, cos<p, kVAr and stability
- Stop the alternator

- Set limit adjustments

- Setting the minimum no-load excitation current:


- Set jumper CA 10 to the ON position, run the alternator at no-load then adjust P10 until LED 10
just goes out.

- Setting the minimum full load excitation current:


- Connect the alternator to the mains and set to PF=0.95 leading, then adjust P9 until LED 10
just goes out.
- Stop the alternator.

- Setting the maximum full load excitation current:


- Set jumper CAB to the ON position
- The threshold is set at 110% of the excitation current.
- Connect to the mains and run the alternator at its rated power with a PF giving 110% of the
excitation current, then adjust P8 until LED 8 just goes out.
- Stop the alternator.

- Setting the maximum stator current:


- Set jumper CA7 to the ON position
- The current threshold will be set according to the load to be started-up (e.g.: 1.51n).

- Activation of the 4/20mA function


See paragraph 34

14 14
LEROY-SOMER I INSTALLATION & MAINTENANCE I4010 en - 03.2011 / b

MODULE R729

6. Troubleshooting

SYMPTOM PROBABLE CAUSES SOLUTIONS


- Cannot adjust U=U function - Input voltages - Check input voltages and connections to
voltages the terminals of the R729

- Cannot obtain the requested -Limits - Remove jumpers CAB, CA?, CA10 and
value of PF (no 4/20mA perform the tests as indicated in paragraph
function) 36,37,38
- Poor vectorial composition - Check the voltage and current connection

- Direction of change of PF, - Terminals J2-21/22 reversed - Change over terminals J2-21/22
kVAr or voltage reversed

- Incorrect voltage, PF or kVAr - Potentiometers of this function - Review potentiometer P6 and P15
setpoints with 4/20mA function out-of-adjustment settings
activated

- Incorrect setpoint with an - Potentiometer setting or poor - check the value of the potentiometer and
external potentiometer connection especially the connection of the cursor.
- Unable to obtain excitation - Excitation current connected the - Reverse the connections to terminals J1-
current limitation wrong way around 1/2
- Instability of setting - Revise settings. - To correct general instability: adjust
potentiometer P16
- To correct PF instability: adjust
potentiometer P3
- To correct kVAr instability: adjust
potentiometer P5
- Alternator PF cannot be - Mains PF contact closed - Disconnect the mains PF contact
adjusted (terminals 17/18 of J2) (terminals 17/18 of J2)

- 4/20mA current present in the - Incorrect 4/20mA connection - Change-over the incoming wires to
customer cabinet, but R 729 terminals 19/20 of J2
LED 5 remains unlit.

15 15

Vous aimerez peut-être aussi