Overhead electrical conductors - Formed wire, concentric lay, stranded conductors.

DESIGN Outer Mass DC Rated Modulus of Coefficient


Designation Theoretical Round wires Z wires diameter Linear grease resistance strength elasticity of linear
system area Number of Nominal Number of Number of Nominal conductor at 20C dilatation
wires diameter layers wires heigth
(5) (4) (1) (2) (6) (3) (3)
sq.mm mm mm mm kg/km kg/km ohm/km kN N/sq.mm K-1
177-A2F-165 176.93 1+6 3.3 1 12 3.3 16.5 488 10 0.1879 49.585 56000 23.10-6
242-A2F-189 241.98 1+6 2.7 2 12+18 2.7 18.9 671 10 0.1380 67.815 56000 23.10-6
261-A2F-196 261.34 1+6 2.8 2 12+18 2.8 19.6 724 10 0.1277 73.240 56000 23.10-6
301-A2F-210 301.25 1+6 3 2 12+18 3 21 835 12 0.1108 84.425 56000 23.10-6
346-A2F-224 345.65 1+6 3.2 2 12+18 3.2 22.4 958 14 0.0966 96.865 56000 23.10-6
366-A2F-231 366.13 1+6 3.3 2 12+18 3.3 23.1 1014 15 0.0912 102.600 56000 23.10-6
* 384-A2F-238 384.13 1+6 3.4 2 12+18 3.4 23.8 1065 16 0.0869 107.600 56000 23.10-6
455-A2F-261 455.14 1+6+12 2.9 2 18+24 2.9 26.1 1266 29 0.0736 127.553 54000 23.10-6
504-A2F-275 503.95 1+6+12 3.05 2 18+24 3.05 27.45 1401 32 0.0665 141.230 54000 23.10-6
538-A2F-284 538.03 1+6+12 3.15 2 18+24 3.15 28.35 1496 34 0.0623 150.780 54000 23.10-6
648-A2F-311 648.38 1+6+12 3.45 2 18+24 3.45 31.05 1803 41 0.0518 181.705 54000 23.10-6
* 666-A2F-315 665.92 1+6+12 3.5 2 18+24 3.5 31.5 1852 42 0.0503 186.620 54000 23.10-6
707-A2F-324 706.76 1+6+12 3.6 2 18+24 3.6 32.4 1965 45 0.0474 198.065 54000 23.10-6
928-A2F-369 928.45 1+6+12 3.35 3 18+24+30 3.35 36.85 2593 47 0.0363 260.195 54000 23.10-6

Recommended fench and belgian sizes.


Recommended belgian sizes.
Recommended fench sizes.
Belgian sizes
Example: 666-A2F-315: conductor made of B3F formed aluminium alloy wires. Its area is 666 sq. mm and it is 31,5 mm diameter (315x0,1).

(1) Based on the volumic mass given in the IEC 60104 2,703 kg/dm - linear conductor mass are calculated according the stranding annex.
(2) All the layers are greased except the last one. Tolerancies on the grease weigth 30 % -Weigth calculations are made according the grease annex.
(3) Values given for informative purpose only
(4) Tolerancies 2 %
(5) The ratio between the cross-sectional aera of a conductor and the theorical area shall be between 1,00 and 1,04.
(6) Based on the resistivity given in the IEC 60104 32,53 n ohm.m - Resistances are calculated according the stranding annex.
Stranding
All wires of the conductor shall be concentrically stranded. Adjacent wire layers shal
lay directions. The direction of lay of the external layer shall be "right-hand".

The lay ratio for aluminium alloy layers shall be:

Lay ratio
Round wires Formed wires
Conductor 6 wire layer 12 wire layer 6 wire layer 12 wire layer 18 wire layer
wire number min. max. min. max. min. max. min. max. min. max.

19 10 17 6 15
37 10 17 6 16 6 15
61 10 17 10 16 6 15 6 14
91 10 17 10 16 6 15 6 14

The lay ratio of the formed wires may be less than 10.
ires
24 wire layer
min. max.

6 13

10.
Nominal mass of grease for stranded conductors using formed wires.
The nominal mass of grease is calculated according that sheet and not according annex C of the IEC 62219
because IEC does'nt take in account the mass of grease between layers with formed wires.

Values given in the table are calculated with a grease density of 0,87 g/dm and a fill factor of 0,7.

- Layers with round wires

Vg = 0,87.0,7.. ((De2 - Di2) - nd2) /4


Where:
De: external diameter of the layer
Di: internal diameter of the layer
d diameter of the round wire in the layer
n number of wires in the layer
Vg volume of grease in the layer

- Layers with formed wires

Vg = 0,05.0,87.0,7.. (De2 - Di2) /4


Where:
De: external diameter of the layer
Di: internal diameter of the layer
Vg volume of grease in the layer
sing formed wires.
ding annex C of the IEC 62219
formed wires.

d a fill factor of 0,7.