Vous êtes sur la page 1sur 8

22-1880-05

Product Data
Split System (R-410A)
Air Handler for Multi Split
Inverter System
12,000 to 24,000 BTU/Hr

Cassette Type Indoor Unit:


4MXC8512A10N0A
4MXC8518A10N0A
4MXC8524A10N0A

Cassette Cover:
4MXL8518A10N0A - Sold with 4MXC8512 & 4MXC8518

4MXL8524A10N0A - Sold with 4MXC8524

2015 Trane Pub. No. 22-1880-05


It's Hard to Stop a Trane.
Split System (R-410A, 60Hz) 16 SEER,
Inverter System - 12,000 to 24,000 BTU/Hr

Whatever their specific heating and cooling needs, people trust Trane to provide reliable ef-
ficient solutions. Trane Ductless Systems allow you to create a comfortable indoor environment
in spaces where adding ductwork might be impractical or too expensive, or not as efficient as
a ductless option.
Retrofit a house that doesn't have a ducted system or where the central system is already
at capacity. Bring efficient, economical comfort to new room additions. Provide spot heating
and cooling that operates independently of the central system. Utilize ductless efficiency for
new construction projects where ductless systems make more sense than a traditional ducted
system. .
Easy to install Trane Ductless Systems offer flexibility in design and provide efficiency and
economy with two simple components - an outdoor unit and one or more stylish, low profile,
indoor units. All built with Trane's legendary reliability and innovative thinking.

Introducing the new TRANE Split System Family

Quiet Operation Compact Design


Specially designed air vent effi- The compact construction and
ciently reduces operation noise to simple structure make the cassette
provide quiet comfort, as low as 35 model easy to install and maintain.
dB.
Washable Filter
Built-in Drain Pump To reduce moisture on filter and
Easily drain condensation from the provide fresh, healthy air into the
unit with the built-in drain pump. room, clean filter regularly with
water.

4MXC High Efficiency


Cassette Indoor Unit

2
Contents
Model Nomenclature 3

General Data 4-5

Unit Dimensions 6-7

Mechanical Specifications 8

INDOORUNITMODELNOMENCLATURE

1 2 3 4 5-6 7-8 9 10 11 12 13 14 15
4 M X X 65 12 A 1 0 N 0 B A
Refrigerant ServiceDigit
4=R-410A A=FirstSequence

UnitType MinorDesignSequence
M=IndoorUnit A=FirstDesignSequence
U=ProSeries B=SecondDesignSequence

FunctionalType
X=HeatPumpInverter ReservedforFutureUse
Y=CoolingOnlyInverter 0=NotCurrentlyUsed

ConfigurationIndoorUnit RegionalMarketsServed(1:1Systems)
W=HighWallUnit N=NorthAmericaMarket
D=Concealed(Duct)Unit
C=CassetteUnit ReservedforFutureUse
F=FloorConsoleUnit 0=NotCurrentlyUsed
X=Convertible(Floor/Ceiling)Mount
L=CasssettePanelCover
ElectricPowerSupplyCharacteristics
EfficiencyTier 1=208-230/60/1
65=16+SEER
85=18+SEER MajorDevelompentSequence
20=upto20SEERProSeries A=FirstDevelopmentSequence
27=upto27SEER B=SecondDevelopmentSequence

NominalCapacity(Btu/hx1,000)
09=9,000Btu/h
12=12,000Btu/h
18=18,000Btu/h
24=24,000btu/h
30=30,000btu/h
36=36,000btu/h
42=42,000btu/h
48=48,000btu/h

3
General Data
MODEL - Cassette 4MXC8512A10N0A * 4MXC8518A10N0A *

RATED Volts/PH 208 / 230 / 1 208 / 230 / 1


Frequency (Hz) 60Hz 60Hz
Total Cooling Capacity (Btu/h) 12000 14400
Total Heating Capacity (Btu/h) 13000 16000
Air Flow Volume (CFM) (H/M/L) 353 / 294 / 265 353 / 294 / 265
Sound Power Level dB(A) (H/M/L) 56 / 52 / 47 56 / 52 / 47
Sound PRESSURE Level dB(A) (H/M/L) 1 46 / 42 / 37 46 / 42 / 37
Dehumidifying Volume (pint/h) 2.96 3.8

PCB Fuse Current (A) PCB 3.15A Transformer 0.2A PCB 3.15A Transformer 0.2A
Fan Quantity 1 1
Fan Type Centrifugal Centrifugal
Motor Full Load Amp (FLA) 0.23 0.23
Fan Motor Drive Type Direct Drive Direct Drive
Fan Motor Speed (RPM) (H/M/L) 845 / 700 / 600 845 / 700 / 600

Evaporator Face Area (ft2) 2.05 2.05


Evaporator Fin Type Hydrophilic film-louver fin Hydrophilic film-louver fin
Evaporator Fin Color - Blue/Not Blue Blue Blue
Air Filter Size (L x W / No.) 13.56 x 13.13 / 1 13.56 x 13.13 / 1
Gas Pipe (to indoor unit) (inch) 3/8 1/2
Liquid Pipe (inch) 1/4 1/4
Connection Method Flare Connection Flare Connection
Drain Connection (inner diameter)(inch) 1.0 1.0

Dimension (Uncrated) (W x D x H) 22.44 x 22.44 x 9.06 22.44 x 22.44 x 9.06


Dimension (Crated) (L x W x H) 33.39 x 28.66 x 12.20 33.39 x 28.66 x 12.20
Net Weight (lbs) 39.7 39.7
Gross Weight (lbs) 50.7 50.7
Panel Outline Dimension (W x D x H) 25.59 x 25.59 x 1.97 25.59 x 25.59 x 1.97
Panel Net Weight (lbs) 5.50 5.50

1 Sound PRESSURE Level @ 3.3 ft. dB(A)

* Order cassette cover 4MXL8518A10N0A (Sold Separately)

4
General Data
MODEL - Cassette 4MXC8524A10N0A **

RATED Volts/PH 208 / 230 / 1


Frequency (Hz) 60Hz
Total Cooling Capacity (Btu/h) 22800
Total Heating Capacity (Btu/h) 27400
Air Flow Volume (CFM) (H/M/L) 694 / 560 / 500
Sound Power Level dB(A) (H/M/L) 49 / 47 / 45
Sound PRESSURE Level dB(A) (H/M/L) 1 39 / 37 / 35
Dehumidifying Volume (pint/h) 5.28

PCB Fuse Current (A) PCB 3.15A Transformer 0.2A


Fan Quantity 1
Fan Type Centrifugal
Motor Full Load Amp (FLA) 0.43
Fan Motor Drive Type Direct Drive
Fan Motor Speed (RPM) (H/M/L) 620 / 570 / 520

Evaporator Face Area (ft2) 3.77


Evaporator Fin Type Hydrophilic film-louver fin
Evaporator Fin Color - Blue/Not Blue Blue
Air Filter Size (L x W / No.) 21.38 x 21.34 / 2
Gas Pipe (to indoor unit) (inch) 5/8
Liquid Pipe (inch) 3/8
Connection Method Flare Connection
Drain Connection (inner diameter)(inch) 1.0

Dimension (Uncrated) (W x D x H) 33.07 x 33.07 x 9.45


Dimension (Crated) (L x W x H) 37.80 x 37.80 x 12.20
Net Weight (lbs) 66.1
Gross Weight (lbs) 83.8
Panel Outline Dimension (W x D x H) 37.40 x 37.40 x 2.36
Panel Net Weight (lbs) 14.33

1 Sound PRESSURE Level @ 3.3 ft. dB(A)

** Order cassette cover 4MXL8524A10N0A (Sold Separately)

5
Unit Dimensions 4MXC8512A-4MXC8518A

25.6 (650mm)(Decorated surface boards)


22.4 (570mm)(Indoor unit)
15.75 (400mm)(Gaps between hoisting screw rods)

Refrigerant pipe

23.8 (604mm)(Gaps between hoisting screw rods)

25.6 (650mm)(Decorated surface boards)


22.4 (570mm)(Indoor unit)
Hoisting screw (X4)

Installation stands for main body of the unit


6.3(160mm)

Ceiling

0.8 (20mm)
0.8 (20mm) or more

0.8 (20mm) or more

Space required for installation and servicing

59 (1500mm) or more 59 (1500mm) or more

Service port
7.9(200mm)

70.9 (1800mm) or more to floor 7.9 (200mm)

6
Unit Dimensions 4MXC8524A

30.7 (780mm)(Gaps between hoisting screw rods)


37.4 (950mm) (Decorated surface boards)

35 (890mm)*(Ceiling opening)

33 (840mm)( Indoor unit) Refrigerant pipe

Hoisting screw (X4)

26.8 (680mm) (Gaps between hoisting screw rods)


33.1 (840mm)(Indoor unit)
35 (890mm)(Ceiling opening)
37.4 (950mm)(Decorated surface boards )

Installation stands for main body of the unit


6.3 (160mm)

Ceiling

0.8 (20mm) or more


0.8 (20mm) or more

0.8 (20mm) or more

Space required for installation and servicing

59 (1500mm) or more 59 (1500mm) or more

Service port
70.9 (1800mm) or more to floor ( 7.9 (200mm))
7.9
(200mm)

7
Mechanical Specifications

Cassette Type Indoor Unit


General Discharge Airflow and Distribution Remote Controller
System
The Cassette type air handler shall be The unit may have an optional wireless
completely factory assembled including Unit shall have auto swing, horizontal infrared remote controller with easy read-
coil, condensate drain pan, built-in con- blades on each of the units four sides to ing digital display panel to start, stop and
densate drain pump, fan motor, washable optimize the aperture outlet for airflow regulate the supplied wired control from
filter, and electric controls to be used with and air distribution. Blades shall close a distance.
a wired controller. Unit shall be matched automatically when the air conditioner is The wireless controller is available for all
with a Trane outdoor unit, rated and tested turned off to minimize dust entering the units. (Sold separately)
in accordance with AHRI standard. Unit unit. Five-Step preset program on the
shall be ETL listed. remote controller shall be available to Washable Filteration
control the blade angle.
Unit Casing Manually adjusted wide-angle louvers
The unit shall have an easy clean, wash-
shall be provided to adjust the coverage
able filter which allows for cleaning when
Casing shall be provided with drain hose and direction of airflow.
needed. Clean filters provide optimum
to facilitate piping and electrical connection efficiency and fresh air into the room.
on the right of the unit. An electrical service Controls
cover shall be provided to permit easy ac-
cess to the electrical terminal strip.
Units shall have the capability to be
controlled with the supplied wired control
unit. The optional wireless remote may
be used to operate the wall mounted
control.

Air Throw for Indoor Units


Max Horizontal Distance
Unit: ft.
Model Cooling Mode Heating Mode
Cassette 9.8 9.8

08/15
Trane The manufacturer has a policy of continuous product and product data improvement and it reserves the right
6200 Troup Highway
to change design and specifications without notice.
Tyler, TX 75707-9010