Vous êtes sur la page 1sur 7

1452 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO.

3, JULY 2006

Evaluating Distributed Generation


Impacts With a Multiobjective Index
Luis F. Ochoa, Student Member, IEEE, Antonio Padilha-Feltrin, Member, IEEE, and Gareth P. Harrison, Member, IEEE

Abstract—Evaluating the technical impacts associated with could be used to enhance distribution network planning and op-
connecting distributed generation to distribution networks is a eration [7]–[16]. Consequently, it is critical to assess the tech-
complex activity requiring a wide range of network operational nical impacts of DG in power systems in order to apply gen-
and security effects to be qualified and quantified. One means of
dealing with such complexity is through the use of indices that erators in a manner that avoids causing degradation of power
indicate the benefit or otherwise of connections at a given location quality and reliability.
and which could be used to shape the nature of the contract In this work, the technical impacts on medium-voltage level
between the utility and distributed generator. This paper presents reliability and power quality will be assessed based on a steady-
a multiobjective performance index for distribution networks state analysis and the application of distribution network impact
with distributed generation which considers a wide range of
technical issues. Distributed generation is extensively located and indices. Then, in order to calculate the multiobjective perfor-
sized within the IEEE-34 test feeder, wherein the multiobjective mance index by relating the different technical issues, relevance
performance index is computed for each configuration. The results (weighting) factors are presented.
are presented and discussed. Although in practice, distribution engineers will present
Index Terms—Distributed generation (DG), distribution net- some limitations in determining DG location, the existence of
works, multiobjective analysis. an index based on technical impacts indicates where DG could
be more beneficial for the distribution network (i.e. for the elec-
tric utility, helping distribution engineers take decisions and
I. INTRODUCTION
even shape the nature of the contract that might be established

D ISTRIBUTED GENERATION (DG) is expected to play


an increasingly important role in the electric power system
infrastructure and market. Defined as the development of a set
between the network operator and the distributed generator
owner [15]).
This paper is structured as follows. Section II presents the
of sources of electric power connected to the distribution net- distribution network impact indices to be considered in the pro-
work or the customer side of the meter [1], DG technologies in- posed methodology, Section III lays out the multiobjective per-
clude photovoltaic, wind turbines, internal combustion engines, formance index, in Section IV, the IEEE-34 test network is de-
combustion turbines, and microturbines and fuel cells, among scribed. Finally, in Section V, results obtained with the multiob-
others. Integration of DG in distribution networks may create jective performance index are analyzed and discussed.
technical and safety problems [2]–[7]. Depending on its loca-
tion, DG may increase fault currents, cause voltage oscillations, II. DISTRIBUTION NETWORK IMPACT INDICES
interfere with voltage-control processes, diminish or increase
losses, etc. There are various technical issues that need to be addressed
As distribution networks with DG are no longer passive, all when considering the presence of generators in distribution net-
questions about planning, maintenance, and operation become works. Reference [17] presented an approach aimed at quanti-
more interesting and demand reassessment. The main issues fying the benefits of DG such as voltage profile, line-loss reduc-
include where to locate and how to operate DG to minimize tion, and environmental impact reduction. However, that pro-
the impact on distribution management. Additionally, it will be posal disregards technical issues that could measure the nega-
necessary to investigate whether DG capability and placement tive impacts of DG, thus showing that some potentially benefi-
cial connection points present various drawbacks. In this work,
several indices will be computed in order to describe the im-
Manuscript received February 3, 2005; revised April 29, 2005. This work pacts on the network due to the presence of distributed genera-
was supported by FEPISA (Ilha Solteira-SP, Brazil) and the Programme Alban, tion during maximum power generation. Maximum network de-
the European Union Programme of High Level Scholarships for Latin America, mand will be used in all indices, including that related to voltage
under scholarship E04D046001BR. Paper no. TPWRD-00062-2005.
L. F. Ochoa is with the Department of Electrical Engineering, Universi- regulation which will also use minimum demand to fully capture
dade Estadual Paulista (UNESP) and with the School of Engineering and the voltage variation between both load scenarios. Since distri-
Electronics, University of Edinburgh, Edinburgh EH9 3JL, U.K. (e-mail: bution networks are inherently unbalanced due to load charac-
luis_ochoa@ieee.org).
A. Padilha-Feltrin is with the Department of Electrical Engineering, Universi- teristics and topology, here the indices will, explicitly, consider
dade Estadual Paulista (UNESP), Ilha Solteira CEP 15385–000, Brazil (e-mail: phases , , and , and the neutral wire . This approach is
padilha@dee.feis.unesp.br). also applicable to balanced systems.
G. P. Harrison is with the School of Engineering and Electronics, University
of Edinburgh, Edinburgh EH9 3JL, U.K. (e-mail: gareth.harrison@ed.ac.uk). For the th distribution network configuration considering
Digital Object Identifier 10.1109/TPWRD.2005.860262 DG, the indices considered are the following.
0885-8977/$20.00 © 2006 IEEE
OCHOA et al.: EVALUATING DISTRIBUTED GENERATION IMPACTS WITH A MULTIOBJECTIVE INDEX 1453

A. Real and Reactive Power Losses where are voltages at node for the th distribution
Although reliability is the primary concern for utilities, net- network configuration considering minimum demand.
work losses are a key consideration particularly given the twin
C. Current Capacity of Conductors
drivers for efficiency given environmental and economic con-
cerns. While DG may unload lines and reduce losses, the re- As a consequence of supplying power near to loads, current
verse power flows from larger DG can give rise to excessive flows may diminish in some sections of the network, thus re-
losses. Consequently, the first and second indices ( and ) leasing more capacity, but they could also increase to levels be-
express real and reactive line power losses, respectively. Thus, yond distribution line limits. The fifth index gives impor-
a beneficial DG location would decrease total network losses, tant information about the level of currents through the network
which means near unity values of and regarding the maximum capacity of conductors. Since recon-
ductoring is out of the scope of this work, only configurations
(1) with positive values (calculated currents values greater than
current capacity) will be analyzed. Within those configurations,
close to unity values for this index mean reserve capacity for
(2) demand growth

where is the total complex power losses for the th dis- (5)
tribution network configuration, and is the total com-
plex power losses for the distribution network without DG.
where and are the currents through branch for
the th distribution network configuration, and
B. Voltage
are the current capacity of conductors, and is the number of
One advantage of careful location and sizing of DG is the lines.
enhancement of the voltage profile. Therefore, the third index
is related to the maximum voltage drop which, in this D. Three-Phase and Single-Phase-to-Ground Short Circuit
three-phase approach, will consider the maximum drop between The sixth and seventh indices ( and ) are related to
each phase of each node and the root node. This index could be the protection and selectivity issues since they evaluate the max-
also used to find prohibitive locations for DG considering pre- imum short-circuit current variation between the scenarios with
established voltage drop limits. In this way, according to (3), the and without DG. These indices give the power engineer a no-
closer to unity index is, the better the network performance tion of how the DG impacts on the protection devices that were
planned for a network without such generation units. Hence,
(3) a low impact on this concern means close-to-unity values for
and indices
where are the phases , , and ; are the voltages at the
root node (equal in magnitude for the three phases); are the (6)
voltages at node for the th distribution network configuration;
and is the number of nodes.
This maximum voltage drop approach is suitable for (7)
single-feeder analysis. In multiple-feeder systems, DG relieves
the load demand and modifies the voltage profile in the feeder(s)
where is the three-phase fault current value in node
in which it is located. Therefore, must first consider the
for the th distribution network configuration, is the
maximum improvement of the voltage drop in the feeder(s)
with DG and then normalize those values with respect to the three-phase fault current value in node for the distribution net-
largest . In this way, a DG configuration that presents work without DG, and are the largest three-
phase fault current value in the network for the th distribution
the largest improvement will receive an equal to unity
network configuration and its correspondent for the distribution
whereas the others will have proportional values (Appendix A).
In order to ensure that network voltages will not be adversely network without DG, is the single-phase fault current
affected, the case of minimum demand during maximum power value in node for the th distribution network configuration,
is the single-phase fault current value in node for the
generation is also considered, since it represents a critical oper-
distribution network without DG, and are the largest
ating case [16]. Thus, the fourth index, related to voltage regula-
tion, shows the difference between nodal voltages during max- single-phase fault current value in the network for the th distri-
imum and minimum demand. It is desirable to have this vari- bution network configuration and its correspondent for the dis-
tribution network without DG.
ation as small as possible (i.e., close to unity values for index
The indices described above are signals of the network per-
)
formance, where values that are close to unity indicate better
network performance. However, these indices are not related in
such a way that would allow a unique index to indicate the extent
(4) of the DG impact, in a global manner, on a distribution network.
1454 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 3, JULY 2006

TABLE I
RELEVANCE FACTORS

III. MULTIOBJECTIVE INDEX


The multiobjective index for the performance calculation of
networks with DG considers all previously mentioned indices
by strategically giving a relevance (weighting) factor to each
one. This can be performed since all impact indices were nor- Fig. 1. IEEE-34 test feeder.
malized (i.e., present nondimensional values from zero to one).
The multiobjective performance index is given by
are concentrated 56 km away from the root node (the most dis-
tant node is 59 km from the substation). X/R ranges from 0.91
to 2.25. Line-to-line base voltage is 24.9 kV. This feeder
(8) presents ACSR 1/0, two and four conductors.
where The network is simplified by replacing the 24.9-kV/4.16-kV
inline transformer in the original IEEE-34 test feeder with a line
and modeling the entire feeder at a single voltage level. The
automatic voltage regulator is also not represented.
These relevance factors are intended to give the corre-
sponding importance to each technical issue (impact indices) V. APPLICATIONS
due to the presence of DG and depend on the required analysis The three-phase four-wire power-flow algorithm, based on
(e.g., planning, regular operation, emergency operation). the current summation backward–forward technique, described
In general, it is difficult to determine suitable values for the in [20], was adopted. Loads were modeled as constant power
relevance factors. Therefore, the experience of distribution en- and represent the maximum demand. Here, total losses consider
gineers should be harnessed in order to obtain adequate values. only line losses based on a three-phase four-wire approach. It
Furthermore, the relevance factors should be flexible since elec- is important to recall the role of the neutral wire in the total
tric utilities present different concerns about losses, voltages, line losses computation [18]. Nevertheless, total losses should
protection schemes, etc. This flexibility makes the proposed be computed according to the procedures adopted by the utility
methodology even more suitable as a tool for finding the most (e.g., three-phase three-wire approach, considering transformer
beneficial places where DGs may be inserted, regarding the losses, etc.).
electric utilities’ technical perspective and, consequently, re- The impact indices presented in Section II were calculated
garding the DG owner’s economic perspective since utilities by extensively locating and sizing DG in the above described
may incentivize (or even disincentivize) connections points that distribution network in order to illustrate how these indices vary
are more beneficial based on the technical impacts. regarding the insertion point and capability of a generation unit.
Table I shows the values for the relevance factors utilized in Figs. 2 and 3 show the impact indices for the IEEE-34 test
this work, considering a normal operation stage analysis. Those feeder considering two different generation power outputs: 300
values may vary according to the network operator’s concerns. and 1200 kW, respectively (operating at unity power factor).
For the analysis in this paper, the active power losses received Those values represent 16.9% and 67.8% of the network total
a significant relevance factor (0.33) since it can be important in demand, respectively. Each figure was obtained by computing
many applications of DG. The behavior of the voltage profile the impact indices considering a generator located in each fea-
( and ), as a consequence of total loss reduction, also sible node (three-phase node).
receives a major weighting (0.25) due to its considerable power- Short-circuit analysis was performed based on symmetrical
quality impacts. Protection and selectivity impacts ( and components. The system zero- and positive-sequence imped-
) received weightings of 0.22 since they evaluate important ances at the high-voltage (HV)/MV substation are
reliability problems that DG presents in distribution networks. and , respectively; the gener-
The multiobjective index will numerically describe the im- ator’s zero-, positive-, and negative-sequence impedances are
pact of DG, considering a given location and size, on a distribu- , , and
tion network. Close to unity values for the multiobjective per- , respectively. The minimum demand level consid-
formance index means higher DG benefits. ered was 10% of the maximum and was used for calculating the
index.
IV. TEST NETWORK
The IEEE 34-bus three-phase medium-voltage radial feeder A. Impact Indices and IMO with DG Location and Size
[19] will be used in order to perform the proposed analysis From Fig. 2(a) and Fig. 3(a), it can be observed that indices
(Fig. 1). Its total demand is 1770 kW, and 72% of the loads , , , , and , related to the power losses, voltage
OCHOA et al.: EVALUATING DISTRIBUTED GENERATION IMPACTS WITH A MULTIOBJECTIVE INDEX 1455

Fig. 2. Impact indices for IEEE-34 test feeder with a 300-kW generator sited Fig. 3. Impact indices for the IEEE-34 test feeder with a 1200-kW generator
at each node of the circuit. (a) Indices ILp, ILq, IVD, IVR, and IC. (b) Indices sited at each node of the circuit. (a) Indices ILp, ILq, IVD, IVR, and IC. (b)
ISC3 and ISC1. Indices ISC3 and ISC1.

drop and regulation, and conductor’s capacities, achieve higher TABLE II


values when DG is sited near the load concentration (i.e., far IMPACT INDICES COMPARISON FOR IEEE-34 TEST FEEDER CONSIDERING
from the substation). This indicates the importance of locating DIFFERENT POWER GENERATION OUTPUT (POWER FACTOR 1.0)
DG near the load. It can be noted that the values for and
present similar results; however, these indices should be
analyzed separately particularly where DG is operating away
from the unity power factor.
It is also clear that both real and reactive total losses decrease
with the power generation output ( and achieved higher
values with 1200 kW of power generation). Consequently, the
index related with voltage drop also achieved higher
values with higher power generation output. Moreover, since
voltage drops were smaller with a higher power generation
output, differences between maximum and minimum demand
voltages were also smaller. Thus, the index related to voltage
regulation achieved greater values.
The tendency of the maximum usage of the current capacity the greater the distance between the substation and the DG is,
of conductors index is to increase when the DG unit is close the lower the and values are. Also, it is important to
to the load concentration (in this case, far from the substation) remark that indices and present similar tendencies
(i.e., power flow from the substation diminished, alleviating the because of the normalization. However, the ratios “fault with
capacity of conductors). DG/fault without DG” are different as indicated in Table II.
As explained in Section II, short-circuit indices ( and Summarizing the assessment of the impact indices shows that
), presented in Figs. 2(b) and 3(b), considered the max- each index is capable of indicating how a DG unit benefits or
imum values of the ratios between short circuit with DG and harms the distribution network. Nevertheless, while these in-
without DG (original network), with faults in all nodes. The dices remain as isolated values, it is difficult to use them as a de-
maximum values for those ratios, for the analyzed generator, ap- cision-making tool. Therefore, the multiobjective performance
peared when a fault occurred at the generation node. Therefore, index becomes essential for assessing technical impacts
1456 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 3, JULY 2006

Fig. 4. Multiobjective performance index for the IEEE-34 test feeder with
different power generation outputs extensively located in the circuit. Fig. 5. Multiobjective performance index and total power losses for IEEE-34
test feeder varying the power generation output at node 19.

in a global manner regarding specific concerns of an electric


utility.
Based on the adopted relevance factors (Table I), Fig. 4 shows
the values obtained by using the impact indices previ-
ously calculated in Figs. 2 and 3, and also considering a case
with 600-kW power generation output. It is noticeable that for
300-kW power generation, most nodes present almost the same
values, whereas for 1200 kW, a certain set of nodes (neigh-
borhood of node 19) have the largest values (more bene-
fits to the distribution network). Fig. 4 also shows that the
values increase with the power generation output, mainly due to
the impact on the total power losses.
To show how DG insertion can impact on distribution net-
works, Table II presents the non-normalized impact indices for
power generation outputs from Fig. 4, calculated for a DG unit Fig. 6. Multiobjective performance index for IEEE-34 test feeder considering
different power factors (power generation 600 kW).
located at node 19 (largest for the three power generation
output cases). The benefits of DG connection are represented
by , , , , and , where losses diminished up to Beyond reaching that point, values decrease. Furthermore,
38%, 64%, and 91%, for 300, 600, and 1200 kW of output, re- the smallest total losses were achieved with 1650 kW of power
spectively. Even considering the first case of power generation generation, which also exhibits the maximum value.
output (300 kW, feeding 16.9% of the network demand), expres-
sive benefits are achieved when a DG unit is suitably inserted C. Impact Indices and IMO with different Power Factor
in the feeder: voltage drop and maximum usage of the current In the same way that technical impacts vary according to
capacity of conductors decreased up to 20% compared to the the power generation, they also vary according to the operating
original network (no DG). However, by locating a DG unit at power factor of generators. Fig. 6 shows the curves consid-
node 19, the maximum three-phase and single-phase short-cir- ering 600 kW of power generation and three different operating
cuit currents are, respectively, nine and 19 times the original power factors: 0.95 lagging (producing reactive power), unity,
short-circuit currents (no DG). The values of and and 0.95 leading (absorbing reactive power). Table III shows the
mean that special attention should be paid to the adjustment and non-normalized impact indices for a DG unit located at the most
selection of protection devices. beneficial nodes found for each case.
It is evident that the proposed impact indices are sensitive to
B. IMO and Total Line Power Losses the reactive power produced or absorbed by distributed genera-
Since most attention is given to the impact on network total tion, as can be observed in Table III. Moreover, results suggest
losses, Fig. 5 shows and total active power-loss curves for that with 600 kW of power generation, a 0.95 lagging power
a DG unit located at node 19 with variable power generation factor presents more benefits (Fig. 6 and Table III) (i.e., pro-
output. Dashed squares show the corresponding values for the ducing reactive power improves network performance).
three cases analyzed above (300, 600, and 1200 kW). It should Since three-phase load data are difficult to obtain, a single-
be noted that the values are closely related to the power phase analysis is required. Therefore, after adapting the pre-
losses (the smaller the losses, the larger the value) due sented impact indices, the analysis described above (varying
to the high relevance factor assigned to the index . Fig. 5 generation at unity power factor and varying power factor with
also indicates that increasing power generation output to values 600-kW power generation) was carried out considering a single-
near the network total demand tends to increase the total losses. phase approach. curves presented the same tendencies,
OCHOA et al.: EVALUATING DISTRIBUTED GENERATION IMPACTS WITH A MULTIOBJECTIVE INDEX 1457

TABLE III
IMPACT INDICES COMPARISON FOR IEEE-34 TEST FEEDER CONSIDERING
DIFFERENT POWER FACTORS (POWER GENERATION 600 kW)

Fig. 7. Nine-bus radial system [17].

and almost the same values than the three-phase analysis. Nev-
ertheless, high unbalanced loads could make noticeable differ-
ences between values using single-phase and three-phase
approaches. Fig. 8. Multiobjective performance index (IMO), active power losses index
In general, distribution networks will not present the same (ILp), and voltage drop index (IVD) for nine-bus systems for three power
generation output scenarios (0.05, 0.10, and 0.15 p.u.).
impact indices tendencies, regarding power generation output
and operating power factor. It is not necessarily surprising that APPENDIX
a higher power generation output does not bring more benefits
An analysis of a nine-bus radial distribution test system
since it will depend mainly on the load distribution and location
(Fig. 7), presented in [17], is performed in this section, as well
of the DG.
as a comparison between results obtained in that reference and
The proposed methodology does not consider the time varia-
those with the proposed methodology. The following assump-
tion of loading levels and their associated DG benefits or oth-
tions were considered: 135-kV three-phase three-wire balanced
erwise. Extension of the approach with time-varying loading
system; line section impedance is ;
and power generation patterns could evaluate the time-depen-
system zero- and positive-sequence impedances at the HV/MV
dent benefits or drawbacks of DG. Other constraints or impact
substation are and ,
indices, reflecting economic [12]; environmental [17]; or relia-
respectively; the generator’s zero–, positive-, and neg-
bility [2], [7] considerations may be included depending on the
ative-sequence impedances are ,
availability of required data as well as the analysis of reverse
, and , respec-
power flows.
tively. Minimum demand level considered is 10% of the
maximum. Loads were modeled as constant power.
VI. CONCLUSION Eight configurations were analyzed by locating a DG unit in
nodes 2 to 9 considering three power generation scenarios: 18,
Various impact indices were addressed in this work, aimed at 36, and 54 MW (0.05, 0.10, and 0.15 p.u., respectively, on a
characterizing the benefits and negative impacts of DG in dis- 400-MVA base) with a power factor 0.9 lagging, whereas the
tribution networks. Furthermore, a multiobjective performance total network demand is 311.352 MW.
index that relates impact indices by strategically assigning a rel- Figs. 8 and 9 show calculated values and impact indices
evance factor to each index was proposed. , and for the three power generation scenarios.
Though the selection of values of relevance factors will It can be noticed that according to the obtained values
depend on engineering experience, the presented values solved, (using relevance factors from Table I), node 7 presents most
in a satisfactory and coherent fashion, the DG location problem, benefits for the three power generation scenarios. This is mainly
considering different power generation outputs for the IEEE-34 due to its high influence in reducing losses and improving the
test feeder. Nevertheless, the proposed relevance factors are voltage profile in its corresponding feeder. At the same time,
flexible since electric utilities have different concerns about node 7 presents a reduced number of line sections with reverse
losses, voltages, protection schemes, etc. This flexibility makes power flow (solely for 54-MW generation) and better short-cir-
the proposed methodology even more suitable as a tool for cuit index values than nodes 8 and 9 which are farther from the
finding the most beneficial places where DGs may be located, substation (Fig. 9).
as viewed from an electric utility technical perspective. Conse- Since this network presents three feeders, the calculation of
quently, these may have an economic influence, since technical was normalized considering the best voltage profile im-
impacts may be used to shape the nature of the contract that provement found. In this way, a DG unit located at node 9 pre-
might be established between the utility and the DG owner [15]. sented the largest improvement ( equal to unity, 0.011 p.u.
1458 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 3, JULY 2006

[10] E. Van Geert, “Toward new challenges for distribution system planners,”
in Proc. Int. Conf. Exhibit. Electricity Distribution. Part 1. Contribu-
tions, vol. 6, 1997, pp. I1/1–I1/3.
[11] A. Silvestri, A. Berizzi, and S. Buonanno, “Distributed generation plan-
ning using genetic algorithms,” in Proc. IEEE PowerTech, 1999, p. 257.
[12] G. Celli and F. Pilo, “MV network planning under uncertainties on dis-
tributed generation penetration,” in Proc. IEEE Power Eng. Soc. Summer
Meeting, vol. 1, 2001, pp. 485–490.
[13] R. E. Brown, J. Pan, X. Feng, and K. Koutlev, “Siting distributed gen-
eration to defer T&D expansion,” Proc. IEEE Power Engineering Soc.
Transmission Distribution Conf. Expo., vol. 2, pp. 622–627, 2001.
[14] G. W. Ault and J. R. McDonald, “Planning for distributed generation
within distribution networks in restructured electricity markets,” IEEE
Power Eng. Rev., vol. 20, no. 2, pp. 52–54, Feb. 2000.
[15] R. C. Dugan, T. E. McDermott, and G. J. Ball, “Planning for distributed
generation,” IEEE Ind. Appl. Mag., vol. 7, no. 2, pp. 80–88, Mar./Apr.
2001.
Fig. 9. Line-to-ground short-circuit index (ISC1) for nine-bus systems for [16] C. L. Masters, “Voltage rise—the big issue when connecting embedded
three power generation output scenarios (0.05, 0.10, and 0.15 p.u.). generation to long 11 kV overhead lines,” Power Eng. J., vol. 16, no. 1,
pp. 5–12, Feb. 2002.
[17] P. Chiradeja and R. Ramakumar, “An approach to quantify the technical
over the configuration without DG) with 0.05 p.u. of power gen- benefits of distributed generation,” IEEE Trans. Energy Convers., vol.
eration, whereas for 0.10 and 0.15 p.u. (0.023 and 0.013 p.u., 19, no. 4, pp. 764–773, Dec. 2004.
[18] W. H. Kersting, “The computation of neutral and dirt currents and power
respectively) it was for the connection at node 7. It can be ob- losses,” in Proc. IEEE Power Eng. Soc. Transmission Distribution Conf.
served that when locating DG at nodes 8 and 9, values Expo., 2003.
are the smallest, thus discouraging such locations (Fig. 9) when [19] W. H. Kersting, “Radial distribution test feeders,” IEEE Trans. Power
Syst., vol. 6, no. 3, pp. 975–985, Aug. 1991.
values are calculated. [20] R. M. Ciric, A. Padilha-Feltrin, and L. F. Ochoa, “Power flow in four-
Comparing nodes 8 and 9 according to the values, it can wire distribution networks-general approach,” IEEE Trans. Power Syst.,
be concluded that for power generation of 0.05 and 0.10 p.u., the vol. 18, no. 4, pp. 1283–1290, Nov. 2003.
connection at node 8 is more beneficial, whereas for 0.15 p.u., it
is at node 9. However, only the latter power generation scenario
result agrees with the analysis performed in [17] (Table A-4,
Luis F. Ochoa (S’01) received the M.Sc. degree
Cases 1 and 2, Set #1) where it was found that the connection in 2003 from the Universidade Estadual Paulista
at node 9 is better than node 8 for the same three scenarios. (UNESP), Ilha Solteira, Brazil, where he is currently
This occurs because the proposed methodology utilizes other pursuing the Ph.D. degree.
Currently, he is a Visiting Postgraduate Researcher
impact indices, such as , and , that affect the with the School of Engineering and Electronics,
global index. Consequently, it can be concluded that these University of Edinburgh, Edinburgh, U.K. His
impact indices should be taken into account in order to consider research interests are distribution system analysis
and distributed generation.
the drawbacks of each analyzed configuration.

REFERENCES
[1] A. Invernizzi, B. Buchholz, M. Stubbe, N. Jenkins, B. Dowd, and M.
Ceraolo, “Distribution Systems and Dispersed Generation: a New Focus
for CIGRE,” Electra, no. 213, pp. 17–21, Apr. 2004. Antonio Padilha-Feltrin (M’89) received the B.Sc.
[2] N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and G. Strbac, Embedded degree from the Escola Federal de Engenharia de Ita-
Generation. London, U.K.: IEE Power and Energy Series 31, Inst. jubá (EFEI), Itajubá, Brazil, and the M.Sc. and Ph.D.
Elect. Eng., 2000. degrees from the Universidade Estadual de Campinas
[3] P. P. Barker and R. W. de Mello, “Determining the impact of distributed (UNICAMP), Campinas, Brazil.
generation on power systems: Part 1—Radial Distribution Systems,” in Currently, he is an Associate Professor with
Proc. IEEE Power Eng. Soc. Summer Meeting, 2000, pp. 1645–1656. the Universidade Estadual Paulista (UNESP), Ilha
[4] N. Hadjsaid, J.-F. Canard, and F. Dumas, “Dispersed generation impact Solteira, Brazil. From 1995 to 1997, he was a
on distribution networks,” IEEE Comput. Appl. Power, vol. 12, no. 2, Visiting Faculty Member with the Electrical and
pp. 22–28, Apr. 1999. Computer Engineering (ECE) Department, Univer-
[5] J. A. P. Lopes, “Integration of dispersed generation on distribution net- sity of Wisconsin-Madison. His main interests are
works-impact studies,” in Proc. IEEE Power Eng. Soc. Winter Meeting, analysis and control of power systems.
vol. 1, 2002, pp. 323–328.
[6] M. T. Doyle, “Reviewing the impacts of distributed generation on dis-
tribution system protection,” in Proc. IEEE Power Eng. Soc. Summer
Meeting, vol. 1, 2002, pp. 103–105.
[7] R. E. Brown, “Modeling the reliability impact of distributed genera- Gareth P. Harrison (M’02) is a Lecturer in Energy
tion,” in Proc. IEEE Power Eng. Soc. Summer Meeting, vol. 1, 2002, Systems with the School of Engineering and Elec-
pp. 442–446. tronics, University of Edinburgh, Edinburgh, U.K.
[8] G. Strbac and N. Jenkins, “Calculation of cost and benefits to the dis- His research interests include network integration of
tribution network of embedded generation,” in Proc. Inst. Elect. Eng. distributed generation and analysis of the impact of
Colloq. Econom. Embedded Gen., 1998, pp. 6/1–6/13. climate change in the electricity industry.
[9] P. Espie, G. W. Ault, G. M. Burt, and J. R. McDonald, “Multiple criteria Dr. Harrison is a Chartered Engineer and member
decision making techniques applied to electricity distribution system of the Institution of Electrical Engineers, U.K.
planning,” Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol. 150, no.
5, pp. 527–535, Sep. 2003.

Vous aimerez peut-être aussi