Cable Selection Chart for motors
Cable selection chart for motors (Induction motors) for 3-Phase power supply is as below:-
Follow

Start Download - View PDF


Convert From Doc
to PDF, PDF to Doc
Simply With The
Free Online App!
Start Download
- View PDF
Motor rating on Full load current of
Main Cable Size requirement
KW motor
1x3 CoreX1.5mmSq copper
0.06 0.21
cable
1x3 CoreX1.5mmSq copper
0.09 0.32
cable
1x3 CoreX1.5mmSq copper
0.12 0.38
cable Convert From Doc to PDF,
1x3 CoreX1.5mmSq copper
0.18 0.58 PDF to Doc Simply With
cable
1x3 CoreX1.5mmSq copper The Free Online App!
0.25 0.7
cable
1x3 CoreX1.5mmSq copper
0.37 1.1
cable
1x3 CoreX1.5mmSq copper
0.55 1.3
cable
1x3 CoreX1.5mmSq copper
0.75 1.8
cable
1x3 CoreX2.5mmSq copper
1.1 2.4
cable
1x3 CoreX2.5mmSq copper
1.5 3.2
cable
1x3 CoreX2.5mmSq copper
2.2 4.5
cable
1x3 CoreX2.5mmSq copper
3 5.9
cable
1x3 CoreX2.5mmSq copper
3.7 7.3
cable
1x3 CoreX4mmSq copper
4 7.7
cable
1x3 CoreX4mmSq copper
5.5 10.5
cable
1x3 CoreX4mmSq copper
7.5 14
cable
1x3 CoreX6mmSq copper
11 20.5
cable
1x3 CoreX10mmSq copper
15 27
cable
1x3 CoreX16mmSq copper
18.5 33
cable
1x3 CoreX16mmSq copper
22 38
cable
30 52 1x3 CoreX25mmSq copper

http://electrialstandards.blogspot.com/2015/10/cable-selection-chart-for-motors.html 1/3
7/22/2017 Electrical Standards: Cable Selection Chart for motors
cable
1x3 CoreX35mmSq copper
37 64
cable
1x3 CoreX50mmsq copper
45 78
cable
1x3 CoreX50mmsq copper
55 97
cable
1x3 CoreX70mmsq Copper
75 132
cable
1x3 CoreX95mmsq copper
90 156
cable
1x3 CoreX120mmsq copper
110 187
cable
1x3 coreX150mmsq copper
132 221
cable
1x3 CoreX185mmsq copper
160 260
cable
1x3CoreX 240mmsq copper
200 330
cable
1x 3CoreX400mmsq copper
250 415
cable
2X3CoreX 300 mmsq copper
315 520
cable
Above chart is for copper cables.

If there is requirement for aluminum cables then same will be increased by 1.5 times that the size
of copper cable.

Cable selection chart for motors is for 3-phase , 415V at 50 HZ frequency.

For checking motors rating and Motor rated current visit:-


http://electrialstandards.blogspot.in/2015/10/ac-current-rating-chart.html

For cable size and current carrying capacity visit:-


http://electrialstandards.blogspot.com/2015/11/cable-size-and-current-carrying-capacity.html
Replay
Replay

*T&C apply.
*T&C apply.

Mega offer week


Posted by Navdeep Goyal at 10:52 PM

http://electrialstandards.blogspot.com/2015/10/cable-selection-chart-for-motors.html 2/3
7/22/2017 Electrical Standards: Cable Selection Chart for motors

2 comments

Add a comment as PRITAM surve

Top comments

Navdeep Goyal shared this via Google+ 1 year ago - Shared publicly Adsense
1 Reply

Navdeep Goyal via Google+ 1 year ago - Shared publicly



Cable Selection Chart for motors
Cable selection chart for motors (Induction motors) for 3-Phase power
supply is as below:- Motor rating on KW Full
load current of motor Main
Cable Size requirement 0.06 0.21 1x3
CoreX1.5mmSq copper cable 0.09 0.32 1x3
1 Reply

Newer Post Home Older Post

Subscribe to: Post Comments (Atom)

Adsense

Adsense

Simple theme. Powered by Blogger.

http://electrialstandards.blogspot.com/2015/10/cable-selection-chart-for-motors.html 3/3

Vous aimerez peut-être aussi