Académique Documents
Professionnel Documents
Culture Documents
ungrounded neutral
resistance grounding
reactance grounding
Petersen coil grounding
direct grounding
1
Five methods are used to fix the
potential of the neutral of Medium
Voltage networks with respect to the
ground.
They are differentiated by the kind
(capacity, resistance, inductance) and
the value (zero to infinity) of the
grounding link impedance Zn.
2
In the case of a phase/ground
fault
3
The fault current is limited to capacitive currents,
which technically authorizes continuity of service.
This means that the equipment must be able to operate
with the network mesh voltage.
The capacitive current depends on the number of km of
cables used for it to flow.
It must be ensured that it is not a risk for persons and
equipment.
The phase voltage transformers complying with the IEC
standard can run for 8 hours with 1.9 V.
In normal operation, the overvoltages do not flow off
to the ground, the equipment must also be
superinsulated.
Insulation monitoring is compulsory and, should a
fault occur, qualified maintenance staff must take rapid
action.
Fault detection must be rapid, either by:
zero sequence voltage relays.
or a continuous insulation monitor.
4
Case of voltage transformers,star cabled, P2
grounded
5
If an insulation monitor injects direct current, the monitor
would conclude there was a fault if the P2s were directly
grounded.
This is why in this case the P2s must be grounded via a
capacitor and a CARDEW in parallel in order to prevent
the direct current to loop round on itself by the VTs.
6
7
8
9
10
11
12
13
14
15
16