Substation Automation and REL 670 Line Distance

Protection Training Protection IED

Distance protection ZM, PHS,


ZDIR
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


1

Distance Protection in REL 670


ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


2
Distance Protection in REL 670
ZD01 (directionality):
It detects the direction for all the
six loops. Memory voltage is here!

PHS (phase selection):


It detects the faulty loops by using
impedance-based algorithm
(STCNDZ), or by using current-
based algorithm (STCNDI).

It detects presence in the Load


area (load encroachment) by using
impedance-based algorithm.

ZM01, ZM02 ZM05 (zone measurements):


They calculate the 6 impedance loops with non directional characteristic.
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


3

Combination of ZD and ZM

Directionality Non Directional


Characteristic

d
ar
rw
Fo
AND is
n g nal
e tti r e c tio
S n - di
No
g is
ettin
S

rse
Reve
ng is
Setti
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


4
Combination of directional characteristic and Load Area
Directional Characteristic Load Area (in Phase Selector)

AND
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


5

Impedance protection characteristic - examples


PE or PP loops
Depending on settings of ZM, PHS and ZD, there can be different shapes of characteristics:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


6
ZM function blocks

ZM function blocks
(ZM01, ZM02, , ZM05)
are responsible for measuring the
distance to the fault.

In order to do this they


measure different electrical
impedances (loops)
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


7

Phase to phase faults and settings


Reach (settings X1, R1)

L1 Z1

Reach (settings X1, R1) Rf

L2 Z1

L3 Z1

arc resistance
(Setting RFPP)
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


8
ZM PP loops (2-phase faults)

ZM measures the ohm/phase impedance of the fault.


R1+j X1
L1

RFPP
2

RFPP
2

L2

R1+j X1

Test equipment must be set in ohm/phase!


ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


9

ZM PP loops (3-phase faults)

ZM measures the ohm/phase impedance of the fault.


R1+j X1
L1

RFPP
2

L2
RFPP RFPP
R1+j X1
2 2

L3
R1+j X1

Test equipment must be set in ohm/phase!


ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


10
Phase to earth faults and settings

Reach (settings X1, R1)

L1 Z1

L2 Z1
Rf

L3 Z1

N ZN

Neutral Impedance reach


Fault resistance
(settings X1, R1, X0, R0)
(Setting RFPE)
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


11

ZM PE loops (phase-earth faults)

ZM measures the ohm/loop impedance of the fault.


R1+j X1 2 (R1+j X1) + (R0+j X0)
Zloopset =
L1 3

RFPE

(R0+j X0) - (R1+j X1)


ZNset =
3

Test equipment must be set in ohm/loop!


ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


12
Example of ZM settings
Set ZM zones as indicated: ZM01 = 85% of line (fw) 0 ms
ZM02 = 125% of line (fw) 400 ms
ZM03 = 150% of line (rv) 800 ms
ZM04 = 200% of line (fw) 1000 ms
ZM05 = OFF
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


13

Settings for ZM01, 85% of line (fw) 0 ms


Settings are in primary, so there is no need to convert primary settings into
secondary.
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


14
Settings for ZM01, 85% of line (fw) 0 ms
Set RFPE = 15 ohms and RFPP = 10 ohms
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


15

Settings for ZM01, 85% of line (fw) 0 ms


Set primary nominal rated references (base values)
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


16
Settings for ZM01, 85% of line (fw) 0 ms
All settings for ZM1:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


17

Settings for ZM02, 125% of line (fw) 400 ms


Settings for ZM02:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


18
Settings for ZM03, 150% of line (rv) 800 ms
Settings for ZM03:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


19

Settings for ZM04, 200% of line (fw) 1000 ms


Settings for ZM04:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


20
Settings for ZM05, OFF
Settings for ZM05:

Operation = Off
is the important setting.

Other settings have been


modified in order to avoid
misunderstandings.
Note how they have been set to
the MAX allowed value.
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


21

Settings for ZD01, directional function


Directional lines function block (ZD01) must also be set.

Keep default unless network


calculations suggest different
settings

Keep default
(10%)
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


22
Settings for ZD01 series compensated lines
Settings for series compensated lines must be changed!

Change default settings for


series compensated networks
(from 115 to 130)
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


23

! The hidden link..


There is a hidden characteristic AND between PHS and ZM,
through the STCNDZ signal.
PHS settings should be calculated in such a way to COVER the zones connected to
STCNDZ (usually ZM01 and ZM02), otherwise the characteristic can be different from the
expected one!
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


24
Phase Selector - PHS
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


25

Basic PHS settings

Keep these settings as default


Unless system studies
suggest different values
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


26
Settings of PHS
PHS settings should be calculated in such a way to COVER the zones connected to
STCNDZ (usually ZM01 and ZM02).

In a more simple way:

Ground Faults (L1N, L2N, L3N PE loops): LN characteristic of PHS must cover LN
characteristic of ZM02

2-Phase faults (L1L2, L2L3, L3L1 PP loops): LL characteristic of PHS must cover LL
characteristic of ZM02

3-phase faults (L1L2L3 PP loops): L1L2L3 characteristic of PHS selector must cover
L1L2L3 characteristic of ZM02.
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


27

PHS LN Characteristic ohm/loop domain


The easiest way is to use the non-
directional characteristic of PHS
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


28
PHS LL and LLL Characteristic ohm/phase domain
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


29

PHS LL and LLL Characteristic ohm/phase domain


ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


30
Conclusion on PHS settings
PHS settings should be done according to users guide formulae. They can be
graphically verified by using the informal EXCEL tool given to the course participants
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


31

PHS settings to cover ZM01 and ZM02


PHS settings to cover the calculated ZM02 zone are the followings:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


32
PHS settings for the Load Area
PHS settings defining the load cutting area are the followings:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


33

PHS settings for the Load Area


From Power data to PHS load data:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


34
PHS settings for the Load Area
Load Area of PHS (example in forward direction).

jX

R
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


35

PHS Load Area for PE loops: LNfaults

LN faults:

Ohm/loop domain
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


36
PHS Load Area for PP loops: LL and L1L2L3 faults
LL faults: L1L2L3 faults:

Ohm/phase domain Ohm/phase domain


ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


37

Real PHS characteristic: PE Loops


LN faults:
Ohm/loop domain
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


38
Real PHS characteristic: PP Loops
LL faults: L1L2L3 faults:
Ohm/phase domain Ohm/phase domain
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


39

Consequences on ZM shape (PP Loops)


ArgLd < 30 degrees:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


40
Consequences on ZM shape (PP Loops)
ArgLd > 30 degrees:
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


41

PHS can trip


PHS can be seen as a non directional zone, with 3 different characteristics:

PE characteristic, LN faults
PP Characteristic, LL faults
PP characteristic, L1L2L3 faults

In some application, typical remote back-up


applications, PHS can be set to trip if the fault is
measured within the characteristics (not A32
application).
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


42
A32 - Impedance Protection Set-up
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


43

Measured characteristic for calculated settings


PE loops, LN faults ohm/loop domain (KL factor in test equipment = 0).
Primary ohms.
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


44
Measured characteristic for calculated settings
PP loops, LL faults ohm/phase domain. Primary ohms.
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


45

Measured characteristic for calculated settings


PP loops, L1L2L3 faults ohm/phase domain. Primary ohms.
ABB AB, 2007

2007-10-03 Substation Automation and Protection Training


46
A32 - Connections to TRIP function
ABB AB, 2007

This logic works BEFORE the trip and not


DURING the trip to avoid unwanted three-phase
trip command from A/R or Binary Input.

2007-10-03 Substation Automation and Protection Training


47