Ordering information
T C 4 S 1 4 R
N Indicator - Without control output
Control output Relay output + SSRP output (AC power)
R
Relay output + SSR output (AC/DC power)
Power supply 2 24-48VDC, 24VAC 50/60Hz
4 100-240VAC 50/60Hz
N No alarm output
Alarm output
1 Alarm1 output
1
2 Alarm1 output + Alarm2 output
S DIN W48H48mm (Terminal block type)
2
SP DIN W48H48mm (11pin plug type)
Y DIN W72H36mm
Size
M DIN W72H72mm
H DIN W48H96mm
W DIN W96H48mm
L DIN W96H96mm
Digit
4 9999 (4digit)
Setting type
C Set by touch switch
Item
T Temperature controller
1. It is unavailable for TC4SP, TC4Y.
2. 11pin socket(PG-11, PS-11) for TC4SP: sold separately.
Specifications
Series TC4S TC4SP TC4Y TC4M TC4W TC4H TC4L
Power AC power 100-240VAC 50/60Hz
supply AC/DC power 24VAC 50/60Hz, 24-48VDC
Allowable voltage range 90 to 110% of rated voltage
H-54
Economical PID Control
Specifications (A)
Photo
electric
Series TC4S TC4SP TC4Y TC4M TC4W TC4H TC4L sensor
Noise resistance 2kV R-phase, S-phase the square wave noise (pulse width: 1us) by the noise simulator
(I)
Memory retention Approx. 10 years (when using non-volatile semiconductor memory type) SSR/
Power
Environ- Ambient temperature -10 to 50, storage: -20 to 60 controller
Connections
meter
TC4 Series has selectable control output; Relay output, and SSRP output. AC/DC power type has Relay output and
(M)
Tacho/
Speed/ Pulse
SSR output and it is selectable. meter
1 7 Relay OUT:
SSR OUT: AL1 OUT: 250VAC 3A 1a 6
12VDC 2V 250VAC 1A 1a 5 7 AL1 OUT:
SSR OUT:
12VDC 2V
(O)
20mA Max. 2 8 250VAC 1A 1a 20mA Max.
Sensor
controller
AL2 OUT:
250VAC 1A 1a 4 8
3 9 (P)
Relay OUT: TC RTD B'
B' RTD TC
4 250VAC 1A 1a 3 9 Switching
10 mode power
supply
1 1
B B
SOURCE: 5 11 2 10 SOURCE: (Q)
100-240VAC A A 100-240VAC Stepper
5VA 50/60Hz, 6 12 1 11 5VA 50/60Hz, motor&
Driver&Controller
24VAC 5VA 50/60Hz, SENSOR SENSOR 24VAC 5VA 50/60Hz,
24-48VDC 3W 24-48VDC 3W (R)
Graphic/
SENSOR Logic
TC4Y TC4W TC
panel
(S)
RTD Field
B' B A network
device
H-55
TC Series
TC4M TC4H/L
1 13
2 14
1 10
3 15
2 11
4 16
3 12
5 17
SSR OUT: 4 AL1 OUT: 13
12VDC 2V 250VAC 6 18
20mA Max. 1A 1a
5 14
SSR OUT: 7 AL1 OUT: 19
AL2 OUT: 250VAC
6 250VAC 15 12VDC 2V
Relay OUT: 20mA Max. 1A 1a
250VAC 3A 1a 1A 1a B' RTD TC 8 20
7 16 AL2 OUT:
1 9 250VAC 21
B 1A 1a
8 17 B' RTD TC
SOURCE: A 10 Relay OUT: 22
100-240VAC 9 18 1 250VAC 1A 1a B
5VA 50/60Hz, SENSOR 11 23
24VAC 5VA 50/60Hz, SOURCE:
24-48VDC 3W 100-240VAC A
5VA 50/60Hz, 12 24
1: AC power: 100-240VAC 5VA 50/60Hz 24VAC 5VA 50/60Hz, SENSOR
AC/DC power: 24VAC 5VA 50/60Hz, 24-48VDC 3W 24-48VDC 3W
45 +0.6
0
Min. 65
56
45 +0.6
0
45 +0.6
0
Min. 65
56
45 +0.6
0
30
68 +0.70
68 +0.7
0
H-56
Economical PID Control
TC4W Terminal cover Panel cut-out (A)
Photo
6
electric
<Bracket> sensor
Min. 115
(B)
96 6 64.5 Fiber
optic
sensor
45 +0.6
0
Min. 65
(C)
Door/Area
44.8
92 +0.8
48
0
sensor
(D)
Proximity
sensor
92 +0.8
encoder
0
Min. 115
(G)
101.5
Connector/
96
45+0.6
0
Socket
(H)
Temp.
controller
(I)
SSR/
Power
controller
TC4L 96 6 64.5 6 Panel cut-out
(J)
<Bracket> Terminal Min. 115 Counter
cover
(K)
+0.8
0
Timer
92
Min. 115
101.5
(L)
92+0.8
0 Panel
meter
(M)
Tacho/
Speed/ Pulse
meter
(N)
Terminal cover(sold separately) Display
unit
RSA-COVER RMA-COVER RHA-COVER RLA-COVER
(4848mm) (7272mm) (4896mm) (9696mm) (O)
Sensor
2 94 controller
47.
70
(P)
91.5
Switching
48.4
13
68.5
mode power
91.5
22 13 supply
13
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
Product mounting
(S)
Field
network
device
TC4S/SP(4848mm) Series TC4Y(7236mm) Series Other Series
(T)
Software
(U)
Other
Mount the product on the panel, fasten bracket by pushing with tools as shown above.
(In case of TC4Y, fasten bolts for bracket.)
H-57
TC Series
Parts description
1
1
2 6 7, 8
3 4
2 5
8
6
7
3 5 4
Factory default
SV setting Parameter 2 group
Parameter Factory default Parameter Factory default Parameter Factory default
- 0 IN-T KCA T 02)0
UNIT ?C
Parameter 1 group AL-1 AMiA
IN-B 0000
Parameter Factory default MAvF 00)1 AL-2 AM@A
AL1 L-SV -050 AHYS 0001
1250
AL2 H-SV 1200 LBaT 0000
AT OFF O-FT HEAT LBaB 002
P 01)0 C-MD PID DI-K STOP
I OUT RLY ErMV 00)0
0000
D SSrM STND LOC OFF
REST 05)0
AC/DC power type has no SSR drive output method selection [ SSrM] function and
HYS 002 supports only ON/OFF output when selecting SSR in control output setting function [ OUT].
H-58
Economical PID Control
SV setting (A)
Photo
In case of changing set temperature from 210 to 250. electric
sensor
(B)
Fiber
optic
RUN mode(display a current temperature) sensor
(C)
Door/Area
Press any key among , , , sensor
(F)
Check SV Rotary
encoder
Run mode
(H)
Temp.
controller
Press any key among 2 sec. 4 sec.
, , , (I)
SSR/
Power
SV setting Parameter 1group [ PAR1] Parameter 2group [ PAR2] controller
D Derivative time
O-FT Control output operation
(N)
Display
unit
Manual reset
RSET (Normal deviation correction) C-MD Control type
(O)
HYS ON/OFF control hysteresis OUT Control output type Sensor
controller
1
SSrM SSR drive output method
(P)
1: It is not displayed for AC/DC power type. T Control cycle Switching
mode power
If no key entered for 30 sec., it returns to RUN mode automatically and the set value of supply
Press any key once in RUN mode, it advances to set value setting group. AHYS Alarm output hysteresis (R)
Press key over 2sec. in RUN mode, it advances to setting group 1. Graphic/
LBaT LBA monitoring time Logic
Press key over 4sec. in RUN mode, it advances to setting group 2. panel
First parameter will be displayed on viewer when it advances to the setting group. LBaB LBA detection range (S)
Field
Press key over 3sec. in the setting group, it returns to RUN mode. DI-K Digital key operation network
device
Exception: Press key once in SV setting group it returns to RUN mode. Control output MV in case of
ErMV input break error
Press key again within a sec after return to RUN mode by press key over
(T)
H-59
TC Series
Parameter 1 group
1: S : Press any key among , , .
Run mode 2: After checking/changing set value at each parameter, and press key, set value
2 sec. flashes twice and it moves to next parameter automatically.
3 sec. 3: It is displayed when control type parameter [ C-MD] of parameter 2group is set PID.
PAR1 Press key for 3 sec. to return RUN mode at any parameter.
This parameter might not be displayed depending on other parameter settings.
AL1 alarm temperature
S 1
AL1 1250
Set range: Deviation alarm(-[F.S] to [F.S], Absolute value alarm(temperature range)
2 In case alarm operation mode [ AL-1, AL-2], AM)_/ SBa / LBa of setting group 2 is
set to [ AL-1, AL-2], no parameters is displayed.
AL2 alarm temperature
S
AL2 1250
3
Auto-tuning
S It starts to operate auto-tuning when it is ON and set as OFF automatically
AT OFF ON after finish the operation.
Deviation indicator(, , ) will be flashing(cycle:1 sec.) during auto
Proportional band tuning function.
S
P 01)0 Set range: 0.1 to 999.9/
Integral time
S Set range: 0 to 9999 sec.
1 0000 Integral operation will be OFF when set value is "0".
Derivation time
S Set range: 0 to 9999 sec.
D 0000
Derivative operation will be OFF when set value is "0".
Manual reset
S
Set range: 0.0 to 100.0%
REST 05)0
It is displayed in P/PD control.
Hysteresis
S Set range: 1 to 100/ (0.1 to 50.0/)
HYS 002
It is displayed when control type parameter [ C-MD] of setting group 2 is set ONOF.
Temperature unit
S
UNIT ?C ?F Front temperature unit indicator will flash when selecting the unit.
Input correction
S
IN-B 000 Set range: -999 to 999 (DPtL / CUsL: -199.9 to 999.9)
H-60
Economical PID Control
(A)
Photo
electric
SV low-limit value sensor
S
L-SV -050 Set range: Within the rated temperature range (B)
by input sensor In case of [ IN-T] input sensor type, Fiber
optic
[ L-SV ( H-SV-1digit) ] low/high-limit setting temperature(SV) is sensor
S
O-FT HEAT COOL (E)
Pressure
sensor
(G)
Connector/
Control output type Socket
S
OUT RLY SSR Operates only selected output between Relay or SSR.
(H)
Temp.
controller
SSR dirve output method It is displayed when selecting control output [ OUT] as SSR. (I)
SSR/
S
SSrM STND CYCL PHAS AC/DC power type has no SSR dirve output method setting Power
controller
function.
(J)
Counter
Control cycle
S Set range:0.5 to 120.0 sec.
T 02)0
If control output [ OUT] is set as RLY, factory default is 20.0 sec, or set as SSR, factory (K)
Timer
default is 2.0 sec.
It will not be displayed when SSR drive output mode [ SSrM] is set as CYCL, PHAS.
(L)
Panel
AL1 alarm operation mode meter
S Press key to convert alarm
AL-1 AMiA LBaA AM!A AMiB operation mode into alarm option. (M)
Tacho/
Alarm operation mode Alarm option Refer to H-62 page. Speed/ Pulse
meter
AL2 alarm operation mode
S (N)
AL-2 AM@A Same with the above [ AL-1]. Display
unit
(O)
Alarm output hysteresis Sensor
S controller
Set range: 1 to 100/(DPtL/ CYsL: 0.1 to 50.0)
AHYS 00I
If alarm operation mod [ AL-1, AL-2] of setting group 2 is set to AM)_, SBa , LBA , AHYS (P)
Switching
parameter is not displayed. mode power
supply
LBA monitoring time
S
LBaT 0 Set range: 0 to 9999sec. (Automatically setting with Auto-tunning) (Q)
Stepper
LBaT parameter is displayed when alarm operation mode [ AL-1, AL-2] of setting group 2 motor&
Driver&Controller
is set as LBA .
LBA detection band (R)
S Set range: 0 to 999/ (DPtL/ CUs: 0.0 to 999.9/) Graphic/
LBaB 002 Logic
(Automatically setting with Auto-tunning) panel
When alarm operation mode [ AL-1, AL-2] of setting group 2 is set as loop break alarm(LBA) (S)
Field
[ LBA ], and LBaT parameter does not set as 0, LBaB parameter is displayed. network
Digital input key device
S
DI-K STOP AlRE AlRE is not displayed in case of indicator model.(TC4 -N N)
(T)
Software
Lock
S For indicator model(TC4 -N N),
LOC OFF LOC1 LOC2 LOC3
only OFF, LOC1 are available.
H-61
TC Series
Functions
Alarm [ AL-1 / AL-2 ] AM!A There are two alarms which operate individually. You can set
combined alarm operation and alarm option. Use digital input
Alarm Alarm
operation option key(set as AlRE) or turn OFF power and re-start this unit to
release alarm operation.
Alarm operation
Mode Name Alarm operation Description
AM)_ - - No alarm output
OFF H ON OFF H ON
Deviation If deviation between PV and SV as high-limit is
AM! high-limit SV PV PV SV higher than set value of deviation temperature,
alarm 100 110 90 100 the alarm output will be ON.
High deviation: Set as 10 High deviation: Set as -10
ON H OFF ON H OFF
Deviation If deviation between PV and SV as low-limit is
AM@ low-limit PV SV SV PV higher than set value of deviation temperature,
alarm 90 100 100 110 the alarm output will be ON.
Lower deviation: Set as 10 Lower deviation: Set as -10
ON H OFF H ON
Deviation If deviation between PV and SV as high/low-limit
AM# high/low-limit PV SV PV is higher than set value of deviation temperature,
alarm 90 100 120 the alarm output will be ON.
Lower deviation: Set as 10, High deviation: Set as 20
OFF H ON H OFF
Deviation If deviation between PV and SV as high/low-limit
AM$ high/low-limit PV SV PV is higher than set value of deviation temperature,
reserve alarm 90 100 120 the alarm output will be OFF.
Lower deviation: Set as 10, High deviation: Set as 20
OFF H ON OFF H ON
Absolute
PV SV SV PV If PV is higher than the absolute value,
AM% value high
90 100 100 110 the output will be ON.
limit alarm
Absolute-value Alarm: Absolute-value Alarm:
Set as 90 Set as 110
ON H OFF ON H OFF
Absolute
PV SV SV PV If PV is lower than the absolute value,
AM^ value low
90 100 100 110 the output will be ON.
limit alarm
Absolute-value Alarm: Absolute-value Alarm:
Set as 90 Set as 110
SBa Sensor break Alarm - It will be ON when it detects sensor disconnection.
LBa Loop break Alarm - It will be ON when it detects loop break.
H: Alarm output hysteresis [ AHYS]
Alarm option
Mode Name Description
AM .A Standard alarm If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
AM .B Alarm latch If it is an alarm condition, alarm output is ON and maintains ON status.
First alarm condition is ignored and from second alarm condition, standard alarm operates.
AM .C Standby sequence1 When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the
second alarm condition, standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied
Alarm latch and
standby sequence1 and
AM .D it is an alarm condition, this first alarm condition is ignored and from the second alarm condition,
alarm latch operates.
First alarm condition is ignored and from second alarm condition, standard alarm operates.
AM .E Standby sequence2 When re-applied standby sequence and if it is alarm condition, alarm output does not turn ON.
After clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence1. It operates not only by power ON/OFF,
Alarm latch and but also alarm setting value, or alarm option changing. When re-applied standby sequence and if it is
AM .F standby sequence2 alarm condition, alarm output does not turn ON.
After clearing alarm condition, alarm latch operates.
Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set
temperature, alarm temperature[ AL1, AL2] or alarm operation[ AL-1, AL-2], switching STOP mode to RUN mode.
Sensor break alarm
The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is detected during temperature
controlling. You can check whether the sensor is connected with buzzer or other units using alarm output contact. It is selectable between
standard alarm [ SBaA], or alarm latch [ SBaB].
H-62
Economical PID Control
SV
LBA detection (D)
PV band Proximity
sensor
LBA detection LBA detection
band band
Control LBA detection
output band (E)
Pressure
MV LBA LBA LBA
sensor
0%
Loop break Time (G)
Connector/
alarm(LBA) Socket
(H)
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB] during LBA monitoring Temp.
Start control to controller
time [ LBaT]
(I)
to The status of changing control output MV (LBA monitoring time is reset.) SSR/
Power
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB] during LBA monitoring controller
to
time [ LBa] loop break alarm (LBA) turns ON after LBA monitoring time.
to Control output MV is 0% and loop break alarm (LBA) turns and maintains ON. (J)
Counter
When control output MV is 100% and PV is increased over than LBA detection band [ LBaB] during LBA monitoring
to
time [ LBaT] loop break alarm (LBA) turns OFF after LBA monitoring time. (L)
Panel
meter
to The status of changing control output MV (LBA monitoring time is reset.)
(M)
When executing auto-tuning, LBA detection band[ LBaB] and LBA monitoring time are automatically set based on auto Tacho/
Speed/ Pulse
tuning value. When alarm operation mode [ AL-1, AL-2] is set as loop break alarm(LBA)[ LBa ], LBA detection band meter
Realizing high accuracy and cost effective temperature control with both current output (4-20mA) and linear output(cycle (O)
Sensor
control and phase control) controller
SSRP output is selectable one of standard ON/OFF control, cycle control, phase control by utilizing standard SSR drive (P)
voltage output. Switching
mode power
supply
Select one of standard ON/OFF control [ STND], cycle control[ CYCL] , phase control[ PHAS] at SSrM parameter of
setting 2 group. For cycle control, connect zero cross turn-on SSR (random turn-on SSR is also available). For phase (Q)
Stepper
control, connect random turn-on SSR. motor&
Driver&Controller
(S)
Field
INPUT LOAD network
device
(T)
Software
Power
(U)
100-240VAC Other
50/60Hz
When selecting phase or cycle control mode, the power supply for load and temperature controller must be the same.
In case of selecting PID control type and phase [ PHAS] / cycle [ CYCL] control output modes, control cycle [ T] is not
allowed to set.
For AC/DC power model (TC4 - 2R), this parameter is not displayed and it is available only standard control by relay
or SSR.
H-63
TC Series
Standard ON/OFF control mode [ STND]
A mode to control the load in the same way as Relay AC
output type.
(ON: output level 100%, OFF: output level 0%) OUT
ON OFF ON OFF
Input digital filter [ MAvF] Unit display lamp will be ON when converting temperature
unit
A function to filter input signals for more stable PV display
in order to provide stable control output. If noise occurs on
input signals or PV value keeps changing, it gets difficult to
perform high accuracy control since PV has a direct effect
on output level.
H-64
Economical PID Control
Manual reset [ REST] Digital input key( + 3sec.) [ DI-K] (A)
Photo
When selecting P/PD control mode, certain temperature electric
Press + keys for 3 sec. at the same time and it sensor
difference exists even after PV reaches stable status
operates RUN/STOP function[ STOP] which is set at DI-K (B)
because heater's rising and falling time is inconsistent due Fiber
or alarm clear function[ AlRE]. optic
to thermal characteristics of controlled objects, such as sensor
over 50.0% or PV is higher than SV, reset value is below control output.(auxiliary output is normally provided as
50.0%. setting values.) (E)
Pressure
sensor
Manual reset [ REST] by control result In case of STOP mode, STOP parameter and PV value is
Set below 50.0 as flashing in turn on display part. (F)
Rotary
reset value
When power is off in 'STOP' mode, 'STOP' mode will be encoder
Cool-function [ COOL] and heat-function [ HEAT] must setting group. Parameter setting values are still possible to unit
be set correctly according to the application, if set as check while Lock mode is ON.
(O)
opposite function, it may cause a fire. (If set cool-function Display Description Sensor
controller
[ COOL] at heater, it will be maintained ON and it may OFF Lock off
cause a fire.) Lock parameter group 2
(P)
LOC1 Switching
mode power
Avoid changing heat-function to cool-function or cool- LOC2 Lock parameter group 1, 2 supply
H-65
TC Series
Output connections
See H-139 page for output.
Application of relay output type Application of SSR drive output method
A
TC Series
TC Series SSR
+
Heater
Voltage I
L
Power N
O Power
Condenser output P
0.1 terminal U
A
T
D Load power
630V -
Keep A length as long as possible when wiring the SSR should be selected by the capacity of load,
temperature controller and the load. If wire length of A is otherwise, it may short-circuit and result in a fire. Indirect
short, counter electromotive force which occurs from a coil heated should be used with SSR for efficient working.
of magnet switch & power relay may flow in power line of Please use a cooling plate or it may cause the capability
the unit, and it may cause malfunction. deterioration, breakdown of SSR for a long usage.
If wire length of A is short, please connect mylar Refer to the H-63 page for phase/cycle control connections.
condensers 104(630V) on the both ends of " " (magnet
coil) to protect electromotive force.
Proper usage
Simple "error" diagnosis Caution for using
When the load (Heater etc) is not operated The connection wire of this unit should be separated from
the power line and high voltage line in order to prevent
Please check operation of the OUT lamp located in front
from inductive noise.
panel of the unit.
For crimp terminal, select following shaped terminal (M3)
If the OUT lamp does not operate, please check the
parameter of all programmed mode.
If lamp is operating, please check the output(Relay, SSR Max. 5.8mm Max. 5.8mm
H-66