Vous êtes sur la page 1sur 3

Designation: PS 128 01

Provisional Standard Specification for


Pool Alarms1
This provisional standard is issued under the fixed designation PS 128; the number immediately following the designation indicates the
year of original adoption.

INTRODUCTION

According to CPSC data, each year, on average, 350 children under five years of age drown in
swimming pools, with most deaths occurring in residential settings. Also, each year, on average, 2,600
children under five years of age are treated in hospital emergency rooms for near drowning incidents
in swimming pools. About 42 % of the incidents require hospitalization of the child. About 79 % of
the near drowning incidents occur in a residential setting. These numbers have remained relatively
unchanged for the past several years.

1. Scope 3.1.3 Pool PerimeterPool alarm located such as to detect


1.1 This provisional standard is intended to provide perfor- movement at the perimeter of or above the water surface.
mance requirements for pool alarms for residential swimming 3.1.4 Personal Immersion AlarmPool Alarm device lo-
pools and spas. cated on the person(s).
1.2 This provisional standard is intended to describe devices 4. Performance Requirements
intended to improve personal safety and reduce injuries or
deaths. 4.1 General:
1.3 This provisional standard covers devices that provide 4.1.1 Alarms shall sound both at poolside and inside any
for rapid and automatic detection and alarm in cases of adjacent residence or building of occupancy via a remote
unintentional, unsupervised or accidental entry of a child one receiver within 20 s or less when tested in accordance
year of age or older into the water of swimming pools or spas. withSection 5.
1.4 This provisional standard is not intended to replace 4.1.2 The condition of a swimming pool alarm, either on or
other standard safety requirements that should be in place, that off, shall be indicated with an energized lamp or other
is, adult supervision, fences, gates, locks, etc. distinctive indicator, visible from a distance of 10 ft (3.5 m) at
1.5 This standard covers four different types of alarms. angles of 6 45 perpendicular to the unit, to indicate the
1.6 The detection criteria for this standard is for a child one operability of the product.
year of age and older. 4.1.3 Pool alarms shall have a minimum sound pressure
rating of 85 decibels at 10 ft (3.5 m) for 3 min.
NOTE 1Provisional standards require only subcommittee consensus 4.1.4 If the device is battery operated, there must be a low
and are published for a limited time of two years.
battery indicator. A low battery condition is defined as an
2. Terminology inability to meet the requirements of 4.1.3.
4.1.5 Pool alarms shall automatically reset.
2.1 Definitions of Terms Specific to This Standard:
4.2 Type A:
2.1.1 pool alarm, na device designed to provide a rapid
4.2.1 Type A alarms are to provide for automatic sound of
detection and automatic alarm in incidents of accidental,
the alarm when tested in accordance with 5.1. For alarms with
unintentional or unsupervised entry of a child one year of age
variable sensitivity, the setting shall be set at the least sensitive,
or older into the water of a swimming pool or spa.
according to manufacturers instructions.
3. Classification 4.2.2 Type A alarms are not to alarm when tested in
accordance with 5.2. For alarms with variable sensitivity, the
3.1 Types:
setting shall be set at the most sensitive, according to manu-
3.1.1 SurfacePool alarm floating on water surface.
facturers instructions.
3.1.2 SubsurfacePool alarm located below the water sur-
4.2.3 Type A alarms are not to alarm when tested in
face.
accordance with 5.3. For alarms with variable sensitivity, the
setting shall be set at the most sensitive, according to manu-
1
This provisional specification is under the jurisdiction of ASTM Committee facturers instructions.
F15 on Consumer Products and is the direct responsibility of Subcommittee F15.49
on Pool Alarms. 4.3 Type B:
Current edition approved May 30, 2001. Published July 2001. 4.3.1 Type B alarms are to provide for automatic sound of

Copyright ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States.

1
PS 128
the alarm when tested in accordance with 5.1. For alarms with
variable sensitivity, the setting shall be set at the least sensitive,
according to manufacturers instructions.
4.3.2 Type B alarms are not to alarm when tested in
accordance with 5.2. For alarms with variable sensitivity, the
setting shall be set at the most sensitive, according to manu-
facturers instructions.
4.3.3 Type B alarms are not to alarm when tested in
accordance with 5.3. For alarms with variable sensitivity, the
setting shall be set at the most sensitive, according to manu-
facturers instructions.
4.4 Type C:
4.4.1 Type C alarms are to provide for automatic sound of
the alarm when tested in accordance with 5.4, according to
manufacturers instructions.
4.4.2 Type C alarms are not to alarm when tested in
accordance with 5.5, according to manufacturers instructions.
4.5 Type D:
4.5.1 Type D alarms are to provide for automatic sound of
the alarm when tested in accordance with 5.6, according to
manufacturers instructions.
4.5.2 Type D alarms shall have a key locking device to
prevent the removal or disabling of the device.

5. Test Procedures
5.1 The Child Intrusion Simulator (Fig. 1) weighing 18 6
0.5 lb is dropped horizontally into the water from a height of 6
in. above the water surface. The Child Intrusion Simulator shall
be dropped into the pool at the farthest point from the alarm to
simulate worse case conditions. This test shall be repeated two
times in ten-minute intervals. The Child Intrusion Simulator
weighing 18 6 0.5 lb is dropped vertically at a 45-degree angle
6 10 degrees into the water from a height of 6 in. above the FIG. 1 Child Intrusion Simulator
water surface. The Child Intrusion Simulator shall be dropped
into the pool at the farthest point from the alarm to simulate
worse case conditions. This test shall be repeated two times in Both fans must be operated at the same time for the test. See
10 min intervals. The Child Intrusion Simulator shall subse- Notes on Fig. 2. This test is completed one time.
quently be dropped into the pool at a second but similar 5.4 The Child Intrusion Simulator (Fig. 1) is introduced
location that would also simulate worse case conditions. Both vertically at a 45 angle 610 and then horizontally, (crossing
the horizontal and vertical test shall be repeated two times in 10 the field of detection at 2 to 4 mph and removed) at the point
min intervals. (There is a total of four drops for each test farthest from the sensor. This test is repeated three times.
location). 5.5 A sheet of metal, 2 by 2 in. at 12 in. thick, is introduced
at 36 6 1 in. from the sensor into the field of detection at 6 mph
NOTE 2All testing shall be done in a standard 16 by 32 ft rectangular and removed. This test is repeated three times at 10-minute
swimming pool with a maximum depth varying between 6 and 8 ft. (See intervals.
Fig. 2)
5.6 The personal alarm device is to be installed on the Child
5.2 A regulation size basketball is dropped into the water Intrusion Simulator (Fig. 1) and the Child Intrusion Simulator
from a height of 6 in. above the water surface and at a distance dropped into the water from a height of 6 in. above the water
of 36 6 1 in from the pool alarm. This test is repeated three surface. The test is repeated three times.
times at 10-min intervals.
5.3 A simulated wind test is generated to impact the pool 6. Quality Assurance
alarm and the pool surface. Using the test pool model (16 by 32 6.1 Manufacturers shall have a quality assurance program
ft) and a 15 in diameter fan, generate wind from one end of the providing for frequent testing of the finished product to ensure
pool creating a wind velocity of 15 mph on the pool surface compliance with the ASTM standard.
within 24 in of the pool wall registered by a wind anemometer
(See Fig. 2). Locate another 15 in diameter fan by the alarm 7. Instructions
location on the side of the pool creating a wind velocity of 15 7.1 Instructions shall be shipped with each unit and shall
mph on the pool surface within 24 in of the pool wall and at the address, at minimum:
pool alarm, registered by a wind anemometer (See Fig. 2). 7.1.1 Proper installation.

2
PS 128

FIG. 2 Wind Test

7.1.2 Any adjustments needed. 8. Labeling


7.1.3 Size and shape limitations, if any, on pools.
8.1 Products complying with all requirements of this provi-
7.1.4 Troubleshooting instructions.
sionalstandard may be labeled or marked Meets requirements
7.1.5 Name, address, telephone number of manufacturer.
of ASTM Standard PS 128, or equivalent.
7.1.6 Power requirements or batteries.
7.1.7 Recommended distance from transmitter to receiver. 8.2 Name, model number, date of manufacture, and tele-
7.1.8 Statement This device is not intended to replace any phone number.
other safety consideration that is, adult supervision, life-
guards, fences, gates, pool covers, locks, etc. and some devices 9. Keywords
may not detect gradual entry. 9.1 alarm; childrens safety; pool alarm; spas; swimming
7.2 For pools with sides greater than 16 by 32 ft or irregular pool
shapes, manufacturers instructions shall clarify the recom-
mended number of alarms and location for alarms.

The American Society for Testing and Materials takes no position respecting the validity of any patent rights asserted in connection
with any item mentioned in this standard. Users of this standard are expressly advised that determination of the validity of any such
patent rights, and the risk of infringement of such rights, are entirely their own responsibility.

Vous aimerez peut-être aussi