Gdynia Maritime University, Department of Ship Electrical Power Engineering, Morska Street 83, 81225 Gdynia, Poland
Abstract
This paper investigates the inuence of the CVUF angle on the windings temperature rise and the derating factor of an induction
machine supplied with unbalanced voltage. The eect of simultaneous voltage unbalance and harmonics on its operational life is ana-
lyzed as well. The results of calculations and experimental investigations are presented for two induction cage machines of rated power 3
and 5.5 kW.
2007 Elsevier Ltd. All rights reserved.
Keywords: Induction motor; Temperature; Complex voltage unbalance factor; Voltage unbalance
0196-8904/$ - see front matter 2007 Elsevier Ltd. All rights reserved.
doi:10.1016/j.enconman.2007.07.033
762 P. Gnacinski / Energy Conversion and Management 49 (2008) 761770
where rr is normalized DC rotor windings resistance (trans- where Irrat is rated rotor current (transformed to a stator)
formed to the stator) and kr is the coecient for rotor and ir is normalized negative sequence rotor current com-
windings resistance increase due to the skin eect. On the ponent (transformed to a stator).
basis of Refs. [1416] kr can be evaluated as: Power losses in iron due to voltage unbalance are not
r taken into consideration [12].
H cm fr The backward rotating magnetic eld also produces an
k r cr 0; 1 1 cr additional load torque that decreases the net machine tor-
1 cm 1 Hz
r 8 que. The normalized value of the additional torque (related
H cm fr
for 0; 1 P1 to the rated torque) t can be evaluated as (based on
1 cm 1 Hz Ref. [14]):
where H is rotor slot depth, cr = 0,25 . . . 0,5 [15] and fr is 2
rotor frequency; for the negative sequence component it I rat i2r k r
t srat 12
is equal to: I rrat 2
764 P. Gnacinski / Energy Conversion and Management 49 (2008) 761770
3.2. Harmonic losses and torques DPFe,dist is iron losses with a distorted supply voltage wave-
form, DPFe,sin is iron losses with a sinusoidal supply voltage
Supplying an induction machine with distorted voltage waveform, x is the Steimnetz coecient, ph,sin is the contri-
causes harmonic currents: bution of hysteresis losses in total iron losses in the condi-
Ih uh tions of sinusoidal supply, pec,sin is the contribution of eddy
ih r
2 13 current losses in total iron losses in the conditions of sinu-
I rat
k sh rs krh fshrh rr x2h soidal supply, Uav is the voltage average rectied value,
Uav1 is the average rectied value of the fundamental volt-
where Ih is hth harmonic current, ih is normalized hth har- age harmonic, Urms is rms voltage value and U1 is the rms
monic current, ksh is the coecient of the stator windings value of the fundamental voltage harmonic.
resistance increase due to the skin eect [15], krh is the coef- It should be noted that the g coecient is equal to the
cient of the rotor windings resistance increase due to the ratio of the peak value of the ux density with sinusoidal
skin eect that can be evaluated with Eq. (8) and sh is har- supply and the peak value of the ux density with distorted
monic slip: voltage supply. Its value can be determined from the
decomposition of the ux density on harmonics.
h1 Voltage waveform distortions produce harmonic tor-
sh 14
h ques. Their normalized value (related to the rated torque)
frh is rotor harmonic frequency: can be assessed with the following expressions for positive
sequence and negative sequence harmonics, respectively
frh jh 1jf1 15
(based on Ref. [14]):
where h is harmonic order. 2 2
The signs and + in Eqs. (14) and (15) are for I rat ih k rh
th srat 20
positive sequence and negative sequence harmonics, I rrat h 1
respectively. 2 2
I rat ih k rh
xh is normalized leakage reactance for the hth harmonic: th srat 21
I rrat h 1
0;16
fh frh
xh 2x1 f rh P 100 Hz 16 The sign before Eq. (21) indicates that for the negative
frat 1 Hz sequence, the harmonic torques decrease the net machine
(based on Ref. [15] and the fact that the stator leakage torque, whereas for the positive sequence, they increase it.
inductance is essentially constant with frequency [18])
where fh is frequency of the hth harmonic and x1 is normal- 3.3. Thermal model
ized leakage reactance for the fundamental harmonic.
The normalized harmonic losses in windings (related to One of the methods of simulating the temperature dis-
the rated ones) are expressed with: tribution in electrical machines is the method of an equiv-
alent thermal network [17,20,21]. In this method, the
X
N
Dpewhar i2h 17a whole machine is divided into basic elements, like: end
h61 windings, stator slot windings, stator core and so on.
X
N Each of the elements is modelled by a node in the thermal
Dpswhar k swh fh i2h 17b network. Power losses, which occur in a real machine,
h61 correspond to current sources in a thermal network.
2 X
N The thermal resistance between each of the elements of
I rat
Dprhar k rh frh i2h 17c a machine are modelled with a thermal resistance between
I rrat h61 the nodes. Furthermore, the thermal capacitance of each
where Dpewhar, Dpswhar and Dprhar are normalized harmonic machine element corresponds to the capacitance in the
losses in the stator end windings, the stator slot windings network. The applied thermal model is presented in
and the rotor windings, respectively, and kswh is the coe- Fig. 2. The nodes 2, 3 and 7 correspond to the phase
cient of the stator slot windings resistance increase due to winding between the U1U2 machine terminals, nodes
the skin eect [15]. 8, 9 and 10 to the phase winding V1V2 terminals and
The iron losses due to the supply with distorted voltage nodes 11, 12 and 13 to the phase winding W1W2 termi-
can be evaluated with (on the basis of Ref. [19]): nals. The model parameters were determined with the
experimental method and calculations (based mostly on
DP Fe;dist Ref. [21]).
gx ph;sin v2 pec;sin 18
DP Fe; sin
4. Laboratory stand
where
U av U rms The laboratory stand consists of three induction cage
g v 19
U av1 U1 machines TSg 100L-4B (3 kW), Sg132S-4 (5.5 kW) and
P. Gnacinski / Energy Conversion and Management 49 (2008) 761770 765
slot
end windings windings
11 13
12
PC computer
programmable AC
power source RS-232
shaft bearings
rotor 1
Fig. 2. The applied thermal model of an induction cage machine. supply voltage
mSZJe 34a (3 kW) loaded with DC generators and sup- motor under the DC
research generator
plied with a programmable AC power source.
The programmable AC power source enables us to set
precisely the magnitude or phase unbalance and to inject Fig. 4. The scheme of the measurement system to investigate the induction
harmonics of programmable magnitude and phase. The cage machines Sg 132S-4 (a) and TSg 100L-4B (b).
maximum power of the source is 9 kVA (3 kVA per phase).
In dierent parts of the induction motors there are built
5. Results of research
in thermocouples: in the end windings, slot windings, teeth,
stator cores, under bearings and on casings. The locations
5.1. Inuence of the CVUF angle on the windings
of the thermocouples in the investigated Sg132S-4 machine
temperature rise
are shown in Fig. 3 and described in Table 1. The locations
of the thermocouples in the stator of the FSg 100L-4B
Below are the results of the experimental investigations
machine (the investigated machine TSg 100L-4B equipped
and numerical calculations for two induction cage
with the additional system of foreign ventilation) is pre-
machines of the types: TSg 100L-4B and Sg132S-4. All
sented in Ref. [22].
the results are determined for the nominal load and the
The scheme of the measurement system is presented in
positive sequence voltage component equal to the rated
Fig. 4.
value (an asymmetrically fed induction machine in the con-
ditions of voltage and frequency deviations, often appear-
ing in ship power systems, will be analyzed in separate
4.5 13 14 11 15 10 19 papers).
Figs. 5 and 6 show the measured and calculated addi-
tional end windings temperature rise (D#u) due to unbal-
1.2 ance versus the CVUF angle Hv for VUF = 3%. The
16
former gure corresponds to the delta connected motor
17 TSg 100L-4B type and the latter to the wye connected
motor Sg 132S-4. Additionally, in Figs. 79, there is a com-
12 parison of the measured temperature rise distribution for a
18 nominally loaded machine TSg 100L-4B and various sup-
3
ply conditions. Fig. 7 corresponds to the nominal supply
and Figs. 8 and 9 to a voltage unbalance with the VUF fac-
tor equal to 3% but with dierent values of the CVUF
6 7 8 9
angle. Namely, the CVUF angle for the thermal test pre-
Fig. 3. The location of thermocouples in the stator of the investigated sented in Fig. 8 corresponds to the worst case (see Fig. 5)
induction cage machine Sg 132S-4. for phase winding V1-V2 (the hottest measured point in
766 P. Gnacinski / Energy Conversion and Management 49 (2008) 761770
88.9
10
5
u [K]
85
0
44.2 82.1 73.7
a b c d
-10
89.8
0 120 240 360
v [] 101
12
46.2 72.8 72.8
3
u [K]
-3 96.3
-6
a b c d
-9
0 120 240 360
v [] 93.3
rise lower than that for a balanced supply (negative val- / rat [-]
ues of D#u in Figs. 5, 6). Moreover, signicant dier- 1.25
ences appear between the worst and the most 1.2-1.25
1.2
favourable cases. For the worst case, D#u was about 1.15-1.2
1012 K, whereas for the most favourable case, it was 1.15
1.1-1.15
1.05-1.1
about 78 K. It should be noticed that the most favour-
1-1.05
able case appears for wye connected machines for the 1.1
CVUF angle for which the worst case appears for delta 1.05
connected machines.
Calculated and measured D#u versus VUF are given 1
0
in Fig. 10. In this chart, the most favourable and the 60
120
5
worst cases are compared for the induction machine 180
240 0 VUF
v [deg] 300
Sg132S-4. The next gure (Fig. 11) shows the normalized 360 [%]
end windings temperature rise in the worst aected
Fig. 11. The normalized (referred to the rated one) end windings
phase winding versus VUF and the CVUF angle for temperature rise in the worst aected phase winding versus VUF and
the machine Sg132S-4. The charts show how important the CVUF angle for the induction machine Sg132S-4; T = Trat,
the CVUF angle is: for VUF equal to 35%, D#u in the f = frat = 50 Hz, U+ = Urat = 380 V.
worst case is about 4050% higher than in the most
favourable case, whereas for VUF less than 1.5%, it is
5.2. Load carrying capacity of an induction machine fed with
even higher, 7090%.
unbalanced voltage
It is also worth mentioning that the total power losses in
the stator windings as well as in the rotor windings due to
An induction machine supplied with unbalanced voltage
unbalance are proportional to the squared percentage of
cannot be loaded nominally; it needs derating. In several
voltage unbalance. No wonder that D#u is considered also
works, the appropriate derating factor was determined in
proportional to the squared percentage of voltage unbal-
such a way that the currents could keep their rated values
ance. In reality, the results of the calculations and measure-
in the worst aected phase windings in order to prevent
ments presented here show that the dependence is more
overheating the machine.
linear, especially for the worst case. So, estimation of D#u
Below, Fig. 12 presents the derating factor versus VUF,
as proportional to the square percentage of voltage unbal-
determined in such a way that it can keep the rated temper-
ance may result in signicant errors.
ature rise in the worst aected phase winding. The curves
were obtained for the induction motor Sg 132S-4 with
the model presented in Fig. 2. Comparison of the plots
25
1.02
20
1
0.98
15
The derating factor [-]
u [K]
0.96
10
a
b 0.94
c
d a
5 0.92 b
0.9
0
0 1 2 3 4 5 6
VUF [%] 0.88
0 1 2 3 4 5
Fig. 10. The additional end windings temperature rise due to unbalance VUF [%]
(D#u) versus VUF, motor Sg 132S-4 type, T = Trat, f = frat = 50 Hz,
U+ = Urat = 380 V a the worst case (calculation); b the most Fig. 12. The derating factor versus VUF, motor Sg 132S-4 type,
favourable case (calculation), c the worst case (measurement); d the f = frat = 50 Hz, U+ = Urat = 380 V a the worst case; b the most
most favourable case (measurement points). favourable case.
768 P. Gnacinski / Energy Conversion and Management 49 (2008) 761770
for the worst case and the most favourable one proves that The thermal loss of life may be especially signicant if
the CVUF angle should be taken into account while derat- dierent disturbances in the supply network appear simul-
ing an induction machine. taneously (the results of thermal investigation for such
The next gure (Fig. 13) presents the normalized cur- undesirable supply conditions are presented in Refs.
rent in the worst aected phase winding versus VUF [1,2]). Below, in Table 2, we have the measured additional
after applying the required derating factor as in temperature rise increase due to the lowered voltage quality
Fig. 12. As one can see, the currents signicantly exceed for the investigated induction cage machine TSg 100L-4B.
their rated value despite the fact that there is no risk of The measurements were performed for the voltage unbal-
overheating the insulation system. Further, signicant ance of the VUF factor equal to 2% (for the most favour-
dierences appear between the worst and the most able and worst case) and for sinusoidal and a distorted
favourable cases. Additionally, the chart shows that waveforms (based on Ref. [12]). Similar waveforms may
determining the derating factor in such a way that cur- appear in some power systems. The harmonic content of
rents do not exceed their rated value in any phase wind- the testing voltage is presented in Table 3.
ing will lead to considerable underestimation of the load Comparison of the results of the measurements, given in
carrying capacity of an induction machine, especially for Table 2, shows that variation of the CVUF angle has a
the worst case. more important eect on windings temperature rise (and
consequently, thermal loss of life) than the possible pres-
5.3. The eect of voltage unbalance and voltage waveform ence of harmonics in the case of low-power induction
distortion on windings temperature and operational life of an machines.
induction machine Figs. 14 and 15 present the operational life expectancy
L%, (in percent of operational life expectancy of a nomi-
An increase in windings temperature causes the pro- nally supplied machine) versus VUF and THD (total har-
cesses of degradation of the insulation system to hasten monic distortion) factors. The results of calculations are
rapidly. The life time of the insulation system L can be esti- shown for the nominally loaded induction motor Sg
mated with [23]: 132S-4 supplied with the voltage of a positive component
u of the fundamental harmonic equal to the rated value
L Bek# 22 and the voltage spectrum containing 5th, 7th, 11th and
13th harmonics. The ratio of amplitudes of each voltage
where # is the absolute temperature (in K),
harmonic is the same as for the considered spectrum
k = 0.8617 104 eV/K is the Boltzmann constant, u is
(U5:U7:U11:U13 = 55:20:10:8).
the activation energy (1.05 eV for F class of insulation)
Fig. 14 corresponds to the worst case of unbalance,
and B is a constant.
whereas Fig. 15 corresponds to the most favourable one.
For the most favourable case and voltage unbalance of
1.2
VUF equal to 3% (the maximal permissible level of unbal-
ance in ship power systems is 3%), the lifetime expectancy
L% is about 61% of that with the nominal supply. When
unbalance is combined with waveform voltage distortions
1.15 a of THD equal to 8% (voltage waveform distortions causing
b still more signicant heating of induction machines are not
expected), the lifetime expectancy is approximately equal to
1.1
Table 2
i [-]
The measured additional end windings temperature rise increase due to the
1.05 lowered voltage quality (the average values of 2 or 3 thermal tests);
machine TSg100L-4B, VUF = 2%, T = Trat, f = frat, a positive component
of the fundamental voltage harmonic equal to the rated value
Unbalance case The worst case Most favourable case
1
Sinusoidal voltage 7.1 4.1
Distorted voltage 8.1 4.9
0.95
0 1 2 3 4 5 Table 3
VUF [%] The harmonic content of the testing voltage (based on [12]), THD = 6%,
the 5th and 11th harmonics are of the negative sequence, whereas the 7th
Fig. 13. The normalized current (referred to the rated one) in the worst and 13th are of the positive one
aected phase winding after applying the required derating factor as in
HarmonicNumber 5 7 11 13
Fig. 12, motor Sg 132S-4 type, f = frat = 50 Hz, U+ = Urat = 380 V a the
Content 5.5 2.0 1.0 0.8
worst case; b the most favourable case.
P. Gnacinski / Energy Conversion and Management 49 (2008) 761770 769
L% [%] able case can be denoted. For the worst one, the additional
temperature rise due to unbalance is c. 1.4 1.9 times as
100
large as for the most favourable case (for the investigated
machines). For this reason, the CVUF angle should be
80-100 taken into consideration while derating an induction
80 60-80
machine. It should be noted that determining the derating
40-60
20-40
factor in such a way that the currents can keep the rated
60
0-20 value in the worst aected phase windings, will lead to con-
siderable underestimation of the load carrying capacity of
40
an induction machine for the worst case of the CVUF
angle.
20
0 It is also worth mentioning that the impact of voltage
1
0 2 harmonics on the thermal loss of life of low-power induc-
0
3 tion machines is lower than the impact of the CVUF angle
2 4 VUF [%]
4 variation or a small variation of unbalance percentage.
6 5
THD [%] 8
Fig. 14. The operational life expectancy L%, (in percent of operational life References
expectancy of a nominally supplied machine) of the induction cage
machine Sg 132S-4, T = Trat, f = frat, a positive sequence voltage [1] Gnacinski P, Mindykowski J, Tarasiuk T. Inuence of electrical
component of the fundamental harmonic equal to the rated value, the power quality on induction cage machine durability. In: Proceed-
CVUF angle corresponds to the worst case of unbalance. ings of the seventh international conference electrical power quality
and utilisation, Crakow, Poland 1719 September 2003 (CD-
ROM).
L % [%] [2] Gnacinski P, Mindykowski J, Tarasiuk T. Thermal phenomena in
electric machines in the wake of electric power quality in ships
networks. In: Proceedings of the 8th international conference
100
electrical power quality and utilisation, Crakow, Poland 2123 Sept
80-100 2005 (CD-ROM).
80 60-80 [3] Wang YJ. Analysis of eects of three-phase voltage unbalance on
40-60 induction motors with emphasis on the angle of the complex
20-40
voltage unbalance factor. IEEE Trans Energ Conver 2001;16(3):
60
2705.
0-20
[4] Faiz J, Ebrahimpour H, Pillay P. Inuence of unbalanced voltage on
40 the steady-state performance of a three-phase squirrel-cage induction
motor. IEEE Trans Energ Conver 2004;19(4):65762.
20
[5] Lee CY. Eects of unbalanced voltage on the operation performance
0 of a three-phase induction motor. IEEE Trans Energ Conver
1 1999;14(2):2028.
0 2
3
[6] Lee CY, Chen BK, Lee WJ, Hsu YF. Eects of various unbalanced
0 VUF [%] voltages on the operation performance of an induction motor under
2 4
4 the same voltage unbalance factor conditions. Electr Pow Syst Res
6 5
THD [%] 8 1998;47(3):15363. <www.sciencedirect.com>.
[7] Pillay P, Hofmann P, Manyage M. Derating of induction motors
Fig. 15. The operational life expectancy L%, (in percent of operational life operating with a combination of unbalanced voltages and over or
expectancy of a nominally supplied machine) of induction cage machine under voltages. IEEE Trans Energ Conver 2002;17(4):48591.
Sg 132S-4, T = Trat, f = frat, a positive sequence voltage component of the [8] Kersting WH, Phillips WH. Phase frame analysis of the eects of
fundamental harmonic equal to the rated value, the CVUF angle voltage unbalance on induction machines. IEEE Trans Ind Appl
corresponds to the most favourable case of unbalance. 1997;3(2):41520.
[9] Faiz J, Ebrahimpour H, Pillay P. Inuence of unbalanced voltage
supply on eciency of three phase squirrel cage induction motor and
54%. Further, for the worst case and the same percentage economic analysis. Energ Conver Manag 2006;47(3):289302.
value of voltage unbalance, the lifetime expectancy L% is doi:10.1016/j.enconman.2005.04.009. <www.sciencedirect.com>.
about 47% for a nominal supply. When this case of unbal- [10] Pillay P, Manyage M. Loss of life in induction machines operating
with unbalanced supplies. IEEE Trans Energ Conver
ance appears simultaneously with waveform voltage distor-
2006;42(6):110. doi:10.1109/TEC.2005.853724.
tions of THD equal to 8%, the lifetime expectancy is [11] Oraee H. A quantative approach to estimate the life expectancy of
reduced to about 42%. motor insulation systems. IEEE Trans Dielect El In 2000;7(6):7906.
[12] de Abreu JPG, Emanuel AE. Induction motor thermal aging caused
6. Conclusions by voltage distortion and imbalance: loss of useful life and its
estimated costs. IEEE Trans Ind Appl 2002;38(1):1220.
[13] Zhelezhenko IV, Sayenko YL, Gorpinich AV. Electrical equipment
The paper shows that the CVUF angle signicantly reliability evaluation at the voltage distortion and unbalance. In:
inuences the thermal eect of voltage unbalance. On the Proceedings of the eighth international conference electrical power
basis of the CVUF angle, the worst and the most favour- quality and utilisation, Crakow, Poland 2123.09.2005.
770 P. Gnacinski / Energy Conversion and Management 49 (2008) 761770
[14] Mindykowski J, Tarasiuk T, Gnacinski P, Rupnik P. Evaluation of the tional conference electrical power quality and utilisation, Cracow,
inuence of an electrical power quality deterioration on operation of Poland 2123 Sept 2005 (CD-ROM).
the selected devices in ship electrical power networks. Final report on [19] Boglietti A, Cvaganino A, Lazzari M, Pastorelli M. Predicting iron
grant No 4T10A 05124 of The State committee for scientic research, in losses in soft magnetic materials with arbitrary voltage supply: an
Poland, Gdynia Maritime Academy, Gdynia 2006 [in Polish]. engineering approach. IEEE Trans Magn 2003;39(2):9819.
[15] de Buck FGG, Gistelinck P, de Backer D. A simple but reliable model [20] Bousbaine A, McCormick M, Low WF. In situ determination of
for inverter-supplied induction motors. IEEE Trans Ind Appl thermal coecients for electrical machines. IEEE Trans Energ
1984;1A-20(1):190202. Conver 1995;10(3):38591.
[16] Dubicki B. Electrical machines, vol. 3 Induction motors, Warsow, [21] Mellor PH, Roberts D, Turner DR. Lumped parameter thermal
Panstwowe Wydawnictwo Naukowe; 1964 [in Polish]. model for electrical machines of TEFC design. In: IEE Proceedings-
[17] Shenkman AL, Chertkov M. Heat condition of a three-phase B, 1991; 138 (5): 20518.
induction motor by a one-phase supply. IEE Proc Electr Power [22] Gnacinski P. Energy saving work of frequency controlled induction
Appl 1999;146(4):3617. cage machine. Energ Conver Manag 2006;45. doi:10.1016/j.encon-
[18] de Abreu JPG, de Sa JS, Prado CC. Skin eect and harmonic currents man.2006.08.02. <www.sciencedirect.com>.
on induction motor rotor cage bars under harmonic-voltage distor- [23] Brancato EL. Estimation of lifetime expectancies of motors. IEEE
tion. an alternative approach. In: Proceedings of the eightth interna- Electr Insul Mag 1992;8(3):513.