Académique Documents
Professionnel Documents
Culture Documents
Table of Contents
Problem Solving Shell & Tube Exchangers
Failures and Troubleshooting
How do you measure performance. U values and duty are hard if not impossible to
measure and often difficult to calculate. Single phase temperatures are relatively
easy to measure but not two phase temperatures. Accurate pressure can be hard to
measure due to dynamics in the system.
Failures and Troubleshooting
(continued)
What criteria that can be measured accurate may not adequately define the true
performance of the exchanger.
Knowing how fouled the surface is on average is difficult. Fouling is often heavier
in some part of the exchanger than others.
Failures and Troubleshooting
(continued)
Since most convection correlations and overall correction factors are based on
empirical data, the heat transfer calculations for exchangers are only accurate to
about 10 to 15% when all the necessary data is known. When some data has to be
estimated, the accuracy gets worse.
Failures and Troubleshooting
(continued)
MONITOR and check TRENDS rather than rely on a single survey to check on
performance.
Failures and Troubleshooting
(continued)
Trend pressure drop and hot or cold end approach temperatures besides the raw
data. Graphical data is easier to pick out trends.
Failures and Troubleshooting
(continued)
Examples:
A downward trend in hot approach indicates
fouling progression
An upward trend in P - fouling
Drastic changes in approach temperatures or
pressures can indicate leaks or blockages
PARALLEL EXCHANGERS
For exchangers in parallel, use the above
procedure but also watch trends in the differences
Example. watch trends in:
Hot end approach (A) - Hot end approach (B),
or Th,out(A) - Th,out(B)
If differences change at all, one exchanger has a
problem
Both exchangers should foul at the same rate
Performance of both exchangers should change
equally under all circumstances
EDS 2004/EXC 7-10
Flow distribution to parallel trains is never identical. We have seen splits come out
at 65-35% rather than 50-50%. As a result, the overall performance was not as
predicted.
Failures and Troubleshooting
(continued)
SUMMARY
If exchangers are regularly monitored in this way
You will not get many unpleasant surprises
You will have information for follow-up
investigations
Duty is a little higher but so is flow rate. Temperature changes on both sides are
similar (hot side and cold side T).
Calculate the LMTD and F factor for the design case. UA is Q/F/ T. Since A is
known, you get U.
Solutions
Design
Q MW 4.76
G kg/hr 70056
T in C 147
T out C 41
t in C 32
t out C 40
Tlm C 39.6
F - 0.845
UA = Q/(FTlm) W/C 142250
2
A m 480
2
U W/m /C 296
Since the hot side inlet was much higher and the cold side inlet was lower, the
LMTD was nearly double. Therefore, if the same performance was available the
duty should have been nearly double. Since the process had not really changed, the
only conclusion is that the performance is down due to fouling.
T in C 147 T in C 172
T out C 65
T out C 41
t in C 27.2
t in C 32
t out C 35
t out C 40
Tlm C 77
Tlm C 39.6
F - 0.97
F - 0.845
UA = Q/(FTlm) W/C 70558
UA = Q/(F Tlm) W/C 142250 A m
2
480
2
A m 480 U W/m /C
2
147
2
U W/m /C 296 U/Udesign 0.49
U is of design value even though shell and tube flows are higher
than design! The problem is severe fouling.
EDS 2004/EXC 7-14
Since the hot side inlet was much higher and the cold side inlet was lower, the
LMTD was nearly double. Therefore, if the same performance was available the
duty should have been nearly double. Since the process had not really changed, the
only conclusion is that the performance is down due to fouling.