Académique Documents
Professionnel Documents
Culture Documents
1.1.1 General
All drill-through equipment shall be subjected to a hydrostatic proof test prior to shipment from the
service or repair facility. Water or water with additives shall be used as the testing fluid. Any additives
shall be documented in the test records.
When a BOP requires PWHT, regardless if the BOP has traceability to a previous shell proof test, the
hydrostatic test pressure shall be tested at a minimum test pressure equal to 1.5 times the rated
working pressure.
When a BOP requires NO PWHT, and has traceability to a previous proof test, the hydrostatic test
pressure shall be tested at a minimum test pressure equal to the rated working pressure.
For equipment with end or outlet connections having different working pressures, the lowest rated
working pressure shall be used to determine the shell pressure test.
The hydraulic operating chamber shall be tested at a minimum test pressure equal to 1.5 times the
operating chambers rated working pressure.
When a BOP requires PWHT, regardless if the BOP has traceability to a previous operating chamber
pressure test, the operating chamber test pressure shall be tested at a minimum test pressure equal to
1.5 times the rated working pressure.
When a BOP requires NO PWHT, and has traceability to a previous operating chamber pressure test,
the operating chamber test pressure shall be tested at a minimum test pressure equal to the rated
working pressure.
The timing of the test shall not start until the test pressure has been stabilized within the manufacturers
specified range and the external surfaces have been thoroughly dried.
Closed-preventer tests shall be performed at low and high pressures, with the low pressure test always
preceding the high pressure test.
The stage one test shall require pressure-testing on the appropriate size drill pipe in accordance with
Table 1.2.4.1.
The stage two test shall require pressure-testing without drill pipe in the preventer, i.e. on the open
hole. The high pressure test for this stage shall be as specified in 1.2.2, except as a minimum it shall
be performed at 50% of the rated working pressure of the preventer.