Vous êtes sur la page 1sur 200

4010 Fire Alarm

PC Programmer
Installation and Programming Instructions

574-187
Rev. C

Technical Manuals Online! - http://www.tech-man.com


Copyright and Trademarks Copyright Simplex Time Recorder Co., 2000. All rights reserved.
Printed in the United States of America.
Information in this document is subject to change without notice. No part of this
document may be reproduced or transmitted in any form or by any means,
electronic or mechanical, for any purpose, without the express written consent of
Simplex Time Recorder Company.
Walk Test is protected by US Patent No. 4,725,818.
MAPNET addressable communications is protected by US Patent No.4,796,025.
IDNet is patent pending.
TrueAlarm Analog Detection is protected by US Patent No. 5,155,468.
TrueAlarm Detector Base is protected by US Patent No. 5,173, 683.

Cautions and Warnings SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To


ensure proper system operation, this product must be tested in accordance with
NFPA72-1996, Chapter 7 after any programming operation or change in site-
specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification, repair or adjustment
to system hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified.
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in the
installation, operating and programming manuals. These instructions must be
followed to avoid damage to the control panel and associated equipment. Fire
Alarm Control Panel (FACP) operation and reliability depend upon proper
installation.

DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS


DAMAGED. Upon unpacking your Simplex product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.

ELECTRICAL HAZARD - Disconnect electrical power when making any


internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.

RADIO FREQUENCY ENERGY - This equipment generates, uses, and can


radiate radio frequency energy and if not installed and used in accordance with
the instruction manual, may cause interference to radio communications. It has
been tested and found to comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference when operated in a commercial
environment. Operation of this equipment in a residential area may cause
interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.

Technical Manuals Online! - http://www.tech-man.com


Codes and Standards The 4010 is listed for the following.

UL 864 Listings for Type of System:

UL 864 Power-Limited Fire Alarm Control Unit.

Local (formerly NFPA 72A).


Requires the sounding of an alarm via listed notification appliance(s).

Auxiliary (formerly NFPA 72B).


Requires 4010-9809 City Circuit Module.

Remote Station - protected premise (formerly NFPA 72C).


Requires 4010-9809 City Circuit Module or the 4010-9810 or -9816 DACT.

Proprietary - protected premise (formerly NFPA 72D).


Requires 4010-9817 (with 4010-9818 or 4010-9819) or 4010-9821 Network
Interface Modules.

Central Station - protected premise (formerly NFPA 71).


Requires 4010-9810 or -9816 DACT.

Suppression Releasing Service.


Requires 4010-9814 Suppression Kit.

UL 864 Listings for Type of Service:

Automatic, Manual, Waterflow, and Sprinkler Supervisory.

UL 864 Listings for Type of Signaling:

Coded, Non-Coded, March-Time and DACT.


DACT requires the 4010-9810 or -9816.

Factory Mutual Approved:

Same as UL above.

Local Approvals:

CSFM
MEA

Continued on next page

Technical Manuals Online! - http://www.tech-man.com


Codes and Standards The installer should be familiar with the relevant codes listed below as well as
(continued) any other applicable local codes and standards, when installing a fire alarm
system.

NFPA 72 National Fire Alarm Code


NFPA 11 Standard for Low-Expansion Foam and Combined Agent
Systems
NFPA 11A Standard for Medium- and High-Expansion Foam Systems
NFPA 12 Standard on Carbon Dioxide Extinguishing Systems
NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems
NFPA 13 Standard for the Installation of Sprinkler Systems
NFPA 14 Standard for the Installation of Standpipe and Hose Systems
NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection
NFPA 16 Standard for the Installation of Deluge Foam-Water Sprinkler
and Foam-Water Spray Systems
NFPA 16A Standard for the Installation of Closed-Head Foam-Water
Sprinkler Systems
NFPA 17 Standard for Dry Chemical Extinguishing Systems
NFPA 17A Standard for Wet Chemical Extinguishing Systems
NFPA 25 Standard for Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems
NFPA 70 National Electrical Code
NFPA 80 Standard for Fire Doors and Fire Windows
NFPA 90A Standard for the Installation of Air Conditioning and
Ventilation Systems
NFPA 90B Standard for the Installation of Warm Air Heating and Air
Conditioning Systems
NFPA 92A Recommended Practice for Smoke-Control Systems
NFPA 92B Guide for Smoke Management Systems in Malls, Atria, and
Large Areas
NFPA 101 Life Safety Code
NFPA 170 Standard for Fire Safety Symbols
NFPA 231C Standard for Rack Storage of Materials
NFPA 1221 Standard on the Installation, Maintenance, and Use of Public
Fire Service Communication Systems

About this Manual Before you start using the 4010 Fire Alarm Installing, Operating, and
Programming Instructions, its important to understand the conventions used in
this publication.

The following conventions are used in this publication to identify special names
or text.
When a membrane panel key (located below the display) is referenced in
this manual, it is normally shown between left and right arrows. Examples
are <ALARM SILENCE> and <SYSTEM RESET>.
Italic type indicates important terms or titles of publications, such as the
4010 Fire Alarm - Programming Instructions.
Bulleted lists, such as this one, provide you with information. They are also
used to indicate alternatives in numbered procedural steps.
Numbered lists indicate procedures with steps that you must carry out
sequentially.

Technical Manuals Online! - http://www.tech-man.com


Table of Contents

Chapter 1. Overview
Overview................................................................................................... 1-1
Related Documents ................................................................................... 1-1
In this Chapter........................................................................................... 1-1

Programmer Overview.................................................................................. 1-2


Introduction............................................................................................... 1-2
Tabs........................................................................................................... 1-3
Icons.......................................................................................................... 1-4
Menu Structure ......................................................................................... 1-4

4010 FACP Version 2.x Feature Enhancements........................................... 1-6


Summary of Features ................................................................................ 1-6

4010 Upgrade Compatibility......................................................................... 1-8


Introduction............................................................................................... 1-8
Using the Version 2.x Programmer with Version 1.x Jobs ....................... 1-9

Chapter 2. Installing/Upgrading PC Programmer


Software
Overview................................................................................................... 2-1
Before You Begin ..................................................................................... 2-1
In this Chapter........................................................................................... 2-1

Before You Begin ......................................................................................... 2-2


System Requirements................................................................................ 2-2
Required Components............................................................................... 2-2

Step 1. Install the Software Key .................................................................. 2-3


Overview................................................................................................... 2-3
Installation ................................................................................................ 2-3

Step 2. Create Floppy Disks (If Necessary) ................................................. 2-4


Overview................................................................................................... 2-4
Procedure .................................................................................................. 2-4

Step 3. Install or Upgrade the PC Programmer Software ............................ 2-7


Overview................................................................................................... 2-7
Procedure .................................................................................................. 2-7

Chapter 3. Downloading a Bin File


Overview................................................................................................... 3-1
Before You Begin ..................................................................................... 3-1
In this Chapter........................................................................................... 3-1

Step 1. Connect Serial Cable and Set Serial Parameters.............................. 3-2


Overview................................................................................................... 3-2
Step 1. Connect the Serial Cable.............................................................. 3-2
Step 2. Set PC Programmer Communication Parameters ........................ 3-2
Step 3. Set 4010 FACP Baud Rate........................................................... 3-3

Technical Manuals Online! - http://www.tech-man.com


Step 2. Enable Panel for Download ............................................................. 3-4
Procedure .................................................................................................. 3-4

Step 3. Upload and Archive Version 1.x Job Files ...................................... 3-5
Upload, Backup, and Archive Existing Version 1.x Job........................... 3-5

Step 4. Download BIN File.......................................................................... 3-6


Overview................................................................................................... 3-6
Step 1. Copy BIN File from Floppy to PC Programmer Computer ......... 3-6
Step 2. Start Download on PC Programmer............................................. 3-6
Step 3. Warm Start the 4010 FACP ......................................................... 3-8

Chapter 4. Getting Started


Overview................................................................................................... 4-1
In this Chapter........................................................................................... 4-1

Using Quick CFIG to Autoconfigure a Panel ............................................... 4-2


Using Quick CFIG to Create a New Job................................................... 4-2
Quick CFIG Reconfigure All Hardware Option ....................................... 4-2
Upload the Job from the Panel to the Laptop............................................ 4-3

Starting the Programmer ............................................................................... 4-4


Using the Start Menu ................................................................................ 4-4

Creating a New Job....................................................................................... 4-5


Introduction............................................................................................... 4-5
Step 1. Invoke New System Dialog ......................................................... 4-5
Step 2. Specify Job Number..................................................................... 4-6
Step 3. Specify System Type ................................................................... 4-6
Step 4. Specify Standalone or Network System....................................... 4-6

Opening an Existing Job Stored on the PC ................................................... 4-7


Introduction............................................................................................... 4-7
Procedure .................................................................................................. 4-7

Uploading a Job from the Panel.................................................................... 4-8


Introduction............................................................................................... 4-8
Step 1. Set Panel and PC Baud Rates to 19, 200...................................... 4-8
Step 2. Connect Serial Cable between PC and Panel ............................... 4-9
Step 3. Enable Upload on Panel............................................................... 4-9
Step 4. Start Upload at PC ..................................................................... 4-10

Saving, Archiving, Backing Up, and Restoring Jobs.................................. 4-13


Introduction............................................................................................. 4-13
Saving a Job ............................................................................................ 4-13
Using Save As......................................................................................... 4-14
Archiving a Job....................................................................................... 4-14
Backing Up a Job.................................................................................... 4-15
Restoring a Backed Up or Archived Job................................................. 4-16

Chapter 5. Setting General Information, System


Options, Passcodes, and Access Levels
Introduction............................................................................................... 5-1
In this Chapter........................................................................................... 5-1

Entering General Information ....................................................................... 5-2


Entering General Information ................................................................... 5-2

vi

Technical Manuals Online! - http://www.tech-man.com


Enabling System Options.............................................................................. 5-3
Introduction............................................................................................... 5-3
Time Format ............................................................................................. 5-3
Depleted Battery ....................................................................................... 5-4
Alarm Silence / Inhibit.............................................................................. 5-4
Alarm Cutout Timer.................................................................................. 5-4
Door Drop on Alarm................................................................................. 5-5
Door Drop on AC Fail .............................................................................. 5-5
Air Handling Units (AHU) Stagger Start.................................................. 5-5
Suppression Release.................................................................................. 5-6
Active Status Reminder ............................................................................ 5-7
Signal Operation ....................................................................................... 5-7

Setting Passcodes and Access Levels ........................................................... 5-9


Overview................................................................................................... 5-9
Setting Passcodes .................................................................................... 5-10
Setting Access Levels ............................................................................. 5-10

Chapter 6. Programming Cards


Introduction............................................................................................... 6-1
In this Chapter........................................................................................... 6-1

Overview Card Tab.................................................................................... 6-2


Card Tab Screen Components................................................................... 6-2
Card Configuration Rules ......................................................................... 6-2
Using AutoFill .......................................................................................... 6-3

Adding / Deleting Cards ............................................................................... 6-4


Introduction............................................................................................... 6-4
Adding Cards ............................................................................................ 6-4
Deleting Cards .......................................................................................... 6-4

Programming Master Controller (SFIO) Card .............................................. 6-5


Introduction............................................................................................... 6-5
Programming User-Defined LEDs............................................................ 6-5
Programming User-Defined Function Keys.............................................. 6-7

Programming the NAC Card ........................................................................ 6-9


Introduction............................................................................................... 6-9
Step 1. Open the NAC Card..................................................................... 6-9
Step 2. Edit Device Types........................................................................ 6-9
Step 3. Edit Point Types......................................................................... 6-10
Step 4. Edit Custom Labels.................................................................... 6-10

Programming the AUX Relay Card ............................................................ 6-11


Introduction............................................................................................. 6-11
Step 1. Open the AUX Relay Card ........................................................ 6-11
Step 2. Edit the Point Type .................................................................... 6-12
Step 3. Edit Custom Label ..................................................................... 6-12

Programming the IDNet Card ..................................................................... 6-13


Introduction............................................................................................. 6-13
Step 1. Open the IDNet Card ................................................................. 6-13
Step 2. Edit Each Points Device Type .................................................. 6-14
Step 3. Edit Each Points Point Type ..................................................... 6-15
Step 4. Set Single Station Mode (Detectors with Sounder Bases Only) 6-15

Viewing and Programming Analog and Digital Pseudos............................ 6-16


Introduction............................................................................................. 6-16

vii

Technical Manuals Online! - http://www.tech-man.com


Viewing Card 18 Digital System Pseudos ........................................... 6-16
Card 19 User Digital Pseudos .............................................................. 6-17
Card 20 Analog System Pseudos ......................................................... 6-18
Card 21 Analog User Pseudos ............................................................. 6-19
Card 22 System Defined List Pseudos ................................................. 6-20
Card 23 User Definable List Pseudos .................................................. 6-21

Programming a Dual RS-232 Card ............................................................. 6-22


Introduction............................................................................................. 6-22
Step 1. Open the RS-232 Card Screen ................................................... 6-22
Step 2. Configure Communication Settings........................................... 6-22
Step 3. Select Events.............................................................................. 6-23

Programming an RS-232 Service Modem Card.......................................... 6-24


Introduction............................................................................................. 6-24
Step 1. Open the RS-232 Service Modem Card Screen ......................... 6-24
Step 2. Configure Communication Settings for Port B .......................... 6-24
Step 3. Select Events to Forward to Remote System ............................. 6-25
Service Modem Command Summary ..................................................... 6-26

Programming a 4120 Network Card ........................................................... 6-29


Introduction............................................................................................. 6-29
Step 1. Define Network Job Attributes (If Necessary)........................... 6-29
Step 2. Enter Description ....................................................................... 6-30
Step 3. Set Node / Loop Number and Comm Style ............................... 6-31
Step 4. Select Port Media (Modular Card Only) .................................... 6-31

Programming a 24 Point I/O Card .............................................................. 6-32


Introduction............................................................................................. 6-32
Programming an Input Device (Two- or Three-Position Switch) ........... 6-32
Programming an Output Point ................................................................ 6-36

Programming an LCD Annunciator Card ................................................... 6-37


Introduction............................................................................................. 6-37
Step 1. Open the LCD Annunciator Card Screen................................... 6-37
Step 2. Programming External Graphical LCD Annunciator Switches . 6-37
Step 3. Programming LEDs ................................................................... 6-39
Programming Events............................................................................... 6-40

Chapter 7. Programming Points


Overview................................................................................................... 7-1
In this Chapter........................................................................................... 7-1

Overview Point Tab ................................................................................... 7-2


Introduction............................................................................................... 7-2
Splitter Bar................................................................................................ 7-2
Site, Card, and Point Views ...................................................................... 7-2
Sort Order ................................................................................................. 7-2
Word Library ............................................................................................ 7-2
AutoFill..................................................................................................... 7-3
Custom Label Spell Check........................................................................ 7-3

Programming a Points Hardware Device Type ........................................... 7-5


Introduction............................................................................................... 7-5
Procedure .................................................................................................. 7-5

Programming a Points Software Point Type................................................ 7-8


Introduction............................................................................................... 7-8
Procedure .................................................................................................. 7-8

viii

Technical Manuals Online! - http://www.tech-man.com


Programming Custom Labels ..................................................................... 7-11
Introduction............................................................................................. 7-11
Procedure ................................................................................................ 7-11

Chapter 8. Programming Lists


Introduction............................................................................................... 8-1
In this Chapter........................................................................................... 8-1

Overview List Tab ..................................................................................... 8-2


Accessing the List Tab.............................................................................. 8-2
Icons used within the Screen..................................................................... 8-2
Sorting the Point Display .......................................................................... 8-3

Naming Lists and Adding/Deleting Points ................................................... 8-4


Naming a List............................................................................................ 8-4
Adding Points ........................................................................................... 8-4
Deleting Points.......................................................................................... 8-4

Chapter 9. Creating a Site Tree


Introduction............................................................................................... 9-1
In this Chapter........................................................................................... 9-1

Overview....................................................................................................... 9-2
Introduction............................................................................................... 9-2
Terms and Concepts.................................................................................. 9-2
The Site Tab.............................................................................................. 9-3

Building a Site Tree ...................................................................................... 9-5


Introduction............................................................................................... 9-5
Step 1. Add the Buildings ........................................................................ 9-5
Step 2. Add Floors ................................................................................... 9-5
Step 3. Add Floor Components................................................................ 9-6
Step 4. Add Points ................................................................................... 9-6

Chapter 10. Creating Custom Control Equations


Introduction............................................................................................. 10-1
In this Chapter......................................................................................... 10-1

Overview CC Tab .................................................................................... 10-2


CC Tab.................................................................................................... 10-2

Overview Components of a CC Equation................................................ 10-4


Introduction............................................................................................. 10-4
Input Statements ..................................................................................... 10-4
Output Statements................................................................................... 10-5

Step 1. Add a New Equation to the User Program..................................... 10-6


Procedure ................................................................................................ 10-6

Step 2. Add Additional Inputs and Outputs to an Equation ....................... 10-7


Introduction............................................................................................. 10-7
Adding Additional Inputs ....................................................................... 10-7
Adding Additional Outputs..................................................................... 10-7

Step 3. Edit Each Input Statements Properties ......................................... 10-8


Introduction............................................................................................. 10-8
ix

Technical Manuals Online! - http://www.tech-man.com


Associating Points with Input Statements............................................... 10-9
Input Opcodes and Qualifiers ............................................................... 10-10

Step 4. Edit Each Output Statements Properties..................................... 10-19


Procedure .............................................................................................. 10-19
Associating Points with Output Statements .......................................... 10-23

Chapter 11. Building and Downloading a Job


Introduction............................................................................................. 11-1
In this Chapter......................................................................................... 11-1

Building a Job ............................................................................................. 11-2


Introduction............................................................................................. 11-2
Using Job Builder ................................................................................... 11-2

Downloading a CFG File to the Panel ........................................................ 11-3


Introduction............................................................................................. 11-3
Step 1. Set Panel and PC Serial Communication Parameters ................ 11-3
Step 2. Connect Serial Cable between PC and Panel ............................. 11-4
Step 3. Enable Download on Panel........................................................ 11-4
Step 4. Start Download at PC................................................................. 11-5

Appendix A. Hardware Device Types, Software Point


Types, and Point Addresses

Appendix B. Conversion Table

Index

Technical Manuals Online! - http://www.tech-man.com


Chapter 1
Overview

Overview
Overview The 4010 is a single-channel, addressable, modular FACP that monitors and
controls up to 250 IDNet addressable devices. The Standard Function
Input/Output (SFI/O) card, power supply, and cabinet provide a complete fire
alarm control panel for most applications. Optional modules mount to the
chassis to provide additional outputs, network communication, and additional
power. Additionally, the 4010 can automatically control supplementary
equipment such as fire doors and fans during an alarm condition using its
auxiliary relay outputs.

This chapter provides an overview of the PC Programmer application and


discusses 4010 FACP Version 2.x feature enhancements and Version 2.x
upgrade requirements.

The remainder of this publication discusses:

Installing or upgrading the PC Programmer


Using the PC Programmer to program a 4010 job

Related Documents Additional information related to 4010 Version 2.x includes the following:

574-052 ....... 4010 Installation, Operation, and Front Panel Programming


Instructions
574-779 ....... 4010 SFIO Programmed IC Installation Instructions
574-499 ....... 4010 SFIO Board Installation Instructions
574-181 ....... 4009 IDNet NAC Extender Installation Instructions
574-182 ....... 4009 Fiber Optic Link Option Installation Instructions
574-325 ....... 4009-9807 NAC Option Card Installation Instructions
574-326 ....... 4009-9808 NAC Class A Adapter Option Card Installation
Instructions

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Programmer Overview 1-2
4010 FACP Version 2.x Feature Enhancements 1-6
4010 Upgrade Compatibility 1-8

1-1

Technical Manuals Online! - http://www.tech-man.com


Programmer Overview

Introduction The Simplex Programmer application provides a graphical interface for


programming the 4010 FACP. This application contains the following major
components.

A set of Tabs corresponding to the major programmable components of the


4010 system. Clicking on a tab gains access to a window that allows you to
program a specific set of system attributes. Figure 1-1 shows the location
of the tabs. Refer to Tabs later in this section for specific information.

Icons that allow you to quickly perform routine tasks such as printing,
saving a job, etc. Refer to Figure 1-2 for a quick reference on each icons
function.

Menus containing groups of similar choices. All menu choices have a


counterpart on the Icon Bar.

Icons provide quick


access to common Menus group similar
tasks tasks

Tabs access related


programming options
and choices

Figure 1-1. Programmer Application, Showing Location of Tabs,


Icons, and Menus

Continued on next page

1-2

Technical Manuals Online! - http://www.tech-man.com


Programmer Overview, Continued

Tabs Each tab contains a group of related programming functions, as follows:

Overview
The Panel Tab allows you to do the following:

- Edit general information such as network, panel, branch, and listing


information
- Select and program system options, such as Alarm Silence Inhibit,
Alarm Cutout Timer, etc.
- Define passcodes for access levels one through four
- Set access levels for various system functions (Fire Alarm
Acknowledge, etc.)

The Card Tab allows you to do the following:

- Add and delete cards


- Program user-defined LEDs and function keys
- Edit each points hardware device type, point type, and custom label on
a per-card basis

The Site Tab provides a means of creating a two-dimensional


representation of a job site. This involves creating and adding labels that
represent the building components -- floors, offices, hallways, etc. -- to the
site tree, and associating points with the correct label. (For example, if the
site tree contains a label named LOBBY, you would associate the points
located in the Lobby area with the LOBBY label.)

Use the Point Tab to do the following:

- List points
- Edit each points hardware device type, point type, or custom label
- AutoFill a points custom label field
- Search for a point, based on its name, device type, point type, or label
- Spell check custom labels

The List Tab allows you to create and edit system lists.

Custom Control Tab provides a graphical interface for creating Custom


Control equations. A significant advantage of this interface is the ability to
display all of an equations operators and points.

Continued on next page

1-3

Technical Manuals Online! - http://www.tech-man.com


Programmer Overview, Continued

Icons The Icon Bar contains a set of icons that allow you to quickly perform basic
tasks, such as creating a new job or error checking a job. Figure 1-2 shows the
location of the Icon Bar and identifies the function of each icon.

Figure 1-2. Icon Bar

Menu Structure Figure 1-3 shows the menu structure of the 4010 PC Programmer application.
Note that some of the options contained in the menu structure are not available
elsewhere in the application (i.e., there is no icon or tab for Preferences).

1-4

Technical Manuals Online! - http://www.tech-man.com


Technical Manuals Online! - http://www.tech-man.com

Transfer Window
File Menu Edit Menu View Menu Build Menu Help Menu
Menu Menu

Help
New Undo Panel Error Check Settings New Window
Topics

Open Cut Cards Build Transfer Cascade About

Close Copy Site Terminal Tile

Save Paste Points Arrange Icons

Save As Preferences Lists

Print Report Custom Control

Revision
Preview Report
History

Print Setup Flip View

Archive Toolbar

Backup Status Bar

Restore

Figure 1-3. 4010 Programmer Menu Structure

1-5
4010 FACP Version 2.x Feature Enhancements

Summary of Features Table 1-1 summarizes the Version 2.x feature enhancements. Refer to the next
section of this manual for a list of the hardware and software components
required to support these features.

Table 1-1. Version 2.x Feature Enhancements

Feature Description
Version 2.x provides the ability to connect the 4009 IDNet NAC Extender
to the 4010. Key features of the new 4009 include:
Standard unit provides four Class B NACs (rated 2A @ 24 VDC),
power supply (8A) and charger.
IDNet Communication and Control. Provides status monitoring and
individual NAC control using a single IDNet address.
Option cards include:
Support for 4009 IDNet
NAC Extender - Class A Adapter
- Four-circuit NAC card provides four additional NACs, rated 1.5A
@ 24 VDC
- IDNet Repeater permits additional 2500 cable run for IDNet
applications
- IDNet Fiber Optic receiver card accepts IDNet transmission from
up to 3000 over fiber optic conductors.
TrueAlarm utility temperature sensing achieved by assigning the
TrueAlarm Utility UTILITY point type to a TrueAlarm heat sensor point allows you to
Temperature Sensing create Custom Control equations that monitor the heat sensor and trigger
output(s) when a threshold temperature is reached.
The addition of Day/Night programming to Custom Control allows devices
to be controlled differently at different times of the day. A common
Day/Night Programming application for this type of programming is to decrease the sensitivity of a
TrueAlarm Photo sensor during the day and increase its sensitivity at
night.
60 Equation Custom The number of Custom Control equations allowed by the 4010 has been
Control Capacity increased from 40 to 60.
A discrete Battery Charger Trouble was added to Version 2.x, providing
Discrete Battery Charger
more exact trouble reporting for charger-related problems. Version 1.x of
Trouble
the system reported only a common trouble.
Version 2.x incorporates a revised polling sequence for Earth Fault
Faster Earth Fault
Search Diagnostics, resulting in improved cycle times and faster location
Search Diagnostics
of Earth faults.

Continued on next page

1-6

Technical Manuals Online! - http://www.tech-man.com


4010 FACP Version 2.x Feature Enhancements, Continued

Summary of Features

Overview
(continued) Table 1-1. Version 2.x Feature Enhancements

Feature Description
Version 2.x adds the ability to reset a City Circuit in the following situation:
Support for AHJ Alarm If the device(s) in alarm is physically removed.
City Circuit No other devices are in an alarm state.
Programming System Reset is performed.
Enabling City Circuit reset is done via Custom Control.
Version 2.x includes support for TrueAlert Non-Addressable NAC devices.
With these devices, horn control occurs over the same two wires that
power and fire the strobe appliances, allowing horns and strobes to exist
on the same NAC and still be controlled separately (i.e., horns on until
silenced while strobes remain on until reset). Important points to
remember about TrueAlert Non-Addressable NAC devices include:
Hardware Device Type. TrueAlert Non-Addressable NACs use a
hardware device type of either SIGA (Class A NAC) or SIGB (Class B
NAC).
Software Device Types. Two separate software point types support
two distinct modes of operation:
- QALERT device type has no automatic operation. All operations
for this type of device type must be programmed with Custom
Control.
- SQALERT device type automatically turns on the designated
circuit on alarm detect (general alarm), issues the horn silence
command upon Alarm Silence, and turns off the circuit at the
completion of System Reset. Any point programmed with the
TrueAlert Non- SQALERT point type is not available for use in Custom Control
Addressable Devices programming.
Quick CFIG. TrueAlert Non-Addressable functionality is not
supported by the front panel Quick CFIG option. You must manually
program TrueAlert hardware and software device types, using either
the front panel interface or the PC Programmer.
Horn Operation. Operation of TrueAlert Non-Addressable Horns is
through the new TrueAlert Horn Operation system option. Possible
selections for this option are STEADY, TEMPORAL, and SLOW
MARCH.
Alarm Operation. In an alarm condition, any NAC programmed with
the SQALERT device type automatically activates. Horns operate as
defined by the TrueAlert Horn Operation system option, and strobes
activate. Pressing Alarm Silence turns off the horns, leaving the
strobes active. System reset automatically turns TrueAlert NACs off.
SMPL Programming. The QALERT point type provides Custom
Control capability for TrueAlert Non-Addressable devices. Existing
opcodes such as ON, OFF, S MARCH, F MARCH, and TEMPORAL
provide standard functionality, and a new opcode HORN OFF
provides specific control of TrueAlert Non-Addressable horns.

1-7

Technical Manuals Online! - http://www.tech-man.com


4010 Upgrade Compatibility

Introduction Table 1-2 lists the 4010 FACPs features and indicates whether a specific
hardware or software component is required to support a specific feature or set
of features.

Keep the following in mind when reviewing this table:

4010 Phase 1 features are compatible with any mix of SFIO card, SFIO
firmware, BIN file, and programmer software (BIN and programmer
software must be same revision level).

The REV. C SFIO board provides improved overload protection for the U9
voltage regulator.

TrueAlert Non-Addressable functionality for the 4010 SFIOs NACs


requires the REV. C SFIO board, Version 2 SFIO firmware, and a Version
2 of the BIN file and programmer application.

Discrete battery trouble reporting requires the REV. C SFIO board, Version
2 SFIO firmware, and a Version 2 of the BIN file and programmer
application.

4009 IDNet NACs require either the REV. B or REV. C SFIO board,
Version 2 SFIO firmware, and Version 2 of the BIN file and programmer
application.

All other 4010 Version 2 features are supported by either version of the
SFIO card and SFIO firmware, but you must have Version 2 of the BIN file
and programmer application.

Table 1-2. Compatibility Matrix for Versions 1 and 2

Programmer Programmer
SFIO Board SFIO Board SFIO FW SFIO FW and BIN File and BIN File
Feature Rev. B Rev. C Version 1 Version 2 Version 1 Version 2
565-736 565-736 742-147 742-147 741-108 & 741-108 &
107 107
Phase 1
Yes Yes Yes Yes Yes Yes
Features
IDNet U9
Yes
Overload
Protection
4010 SFIO
Yes Yes Yes
TrueAlert Non-
Addressable
NACs
FM Battery
Yes Yes Yes
Charger TBL
4009 IDNet
Yes Yes Yes Yes
Interface
Other Version 2
Yes Yes Yes Yes Yes
Features

Continued on next page

1-8

Technical Manuals Online! - http://www.tech-man.com


4010 Upgrade Compatibility, Continued

Using the Version 2.x Using the programmer to edit jobs on a panel containing older versions of the

Overview
Programmer with Version 1.x SFIO chip and board has the following effect:
Jobs
After saving the job, the panel tags the job as a Phase II job.
Subsequent editing of the job cannot take advantage of the full set of Phase
II features, despite the jobs Phase II designation.

Because this situation may become confusing, it is recommended that you


upgrade the panels SFIO card and SFIO firmware before editing its job with the
Phase II programmer.

1-9

Technical Manuals Online! - http://www.tech-man.com


BLANK PAGE

Technical Manuals Online! - http://www.tech-man.com


Chapter 2
Installing/Upgrading
PC Programmer Software

Overview This chapter lists the system requirements for the PC on which you intend to
install the PC Programmer software and describes installing or upgrading the
Version 2.x programmer software on your PC.

Once you have done this, you must download the BIN file from the distribution
floppy disk to the panel. Refer to Chapter 3 for information on downloading the
Version 2.x BIN file to the 4010 FACP.

PC Programmer Software
Installation/Upgrade
Before You Begin Before getting started, make sure that you have the following:

Software key (Simplex Part # 742-079)


Download cable (Simplex Part # 733-794)
Version 2.x PC Programmer CD-ROM (Simplex Part # 741-107)
Blank floppy disks (optional)
Floppy disk with Version 2.x BIN file (Simplex Part # 741-108)

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Before You Begin 2-2
Step 1. Install the Software Key 2-3
Step 2. Create Floppy Disks (If Necessary) 2-4
Step 3. Install or Upgrade the PC Programmer 2-7
Software

2-1

Technical Manuals Online! - http://www.tech-man.com


Before You Begin

System Requirements The Panel Programmer is a Microsoft Windows 95 application. To install


and use the Panel Programmer, you must have the following:
An IBM-compatible personal computer with a Pentium Processor and
a free serial communications port
Microsoft Windows 95 operating system software
Mouse (with at least two buttons)
16 Mb RAM (32Mb recommended)
850 Mb (or greater) hard drive
If a DACT is installed, you will need the SDACT Programmer software
(Part No. 553-807)

Required Components Other components that you may need include:

A 733-794 serial download cable


A 740-989 software key (see Field Service Bulletin FSB-549 for the
ordering procedure)
A 741-107 CD-ROM, containing 4010 Programmer software
If a DACT is installed, you will need the SDACT Programmer software
(Part No. 553-807)

2-2

Technical Manuals Online! - http://www.tech-man.com


Step 1. Install the Software Key

Overview The Software Key (740-989) controls access to the Panel Programmer. When
the Panel Programmer is started, the software reads the parallel port on the PC
looking for a Software Key before the main programming window is displayed.
If the correct key is not detected, a message box is displayed noting that there is
either a missing or incorrect key and the Panel Programmer will terminate with
no further action.

Installation Use the following procedure to install the key:


1. Turn OFF power to your computer.

PC Programmer Software
2. Remove your printer cable from your parallel port (if installed).

Installation/Upgrade
Connect the software key to your parallel port and reconnect your
printer cable to the software key. (See Figure 2-1.)
3. Turn ON power to your computer.

LAPTOP PARALLEL PORT LPT1


COMPUTER
(REAR VIEW)
740-989 SOFTWARE KEY

PRINTER CABLE

Figure 2-1. Software Key Installation

2-3

Technical Manuals Online! - http://www.tech-man.com


Step 2. Create Floppy Disks (If Necessary)

Overview This section describes creating a set of floppy disks that contain the PC
Programmer software. This step is only necessary if the PC on which you
intend to install the PC Programmer does not contain a CD-ROM drive. Skip to
Step 3. Install or Upgrade the PC Programmer Software, if the system on
which you intend to install or upgrade the PC Programmer software contains a
CD-ROM drive.

Before creating disks, make sure you have the following:

A PC containing a CD-ROM drive on which the diskettes can be made.


Seven 3.5, high-density (1.44 MB) floppy diskettes. Ensure that the
diskettes are blank and virus free before using them.
Ensure that the software key is properly installed. The programmer
software will not install if the key is not properly connected to the system.

Procedure 1. Insert the CD-ROM (741-107) in the drive of the PC on which the disks
will be made.

The initial screen shown in Figure 2-2 automatically appears after


approximately 10 to 20 seconds.

Figure 2-2. Initial Installation Screen

2. Click on the DiskBuilder button.

A progress thermometer appears, showing the progress of the Install Wizard


installation. The next screen, shown in Figure 2-3, cautions you to exit all
Windows programs before continuing with the installation.

Continued on next page

2-4

Technical Manuals Online! - http://www.tech-man.com


Step 2. Create Floppy Disks (If Necessary), Continued

Procedure (continued)

PC Programmer Software
Installation/Upgrade
Figure 2-3. Welcome Screen

3. Click Next to continue.

The screen shown in Figure 2-4 appears, prompting you to insert a disk in
Drive A:\.

Figure 2-4. Prompt to Insert Disks

4. Insert a disk in Drive A:\ and click Next.

Continued on next page

2-5

Technical Manuals Online! - http://www.tech-man.com


Step 2. Create Floppy Disks (If Necessary), Continued

Procedure (continued) A progress thermometer appears, showing the progress of the file copy
operation. A series of prompts, similar to the one shown in Figure 2-5 appear,
prompting you to insert each additional disk.

Figure 2-5. Prompt for Additional Disk

Disk Builder is complete when the Finished dialog, shown in the next figure,
appears.

Figure 2-6. Finished Dialog

2-6

Technical Manuals Online! - http://www.tech-man.com


Step 3. Install or Upgrade the PC Programmer Software

Overview This section describes installing Version 2.x of the PC Programmer software. If
the PC on which you are installing the programmer already contains Version 1.x
software, make sure to overwrite the Version 1.x software with the Version 2.x
programmer software.

Procedure 1. Do one of the following, depending on which type of media you are using:

If installing from CD-ROM, do the following:

a. Insert the CD in the drive. The initial screen shown in Figure 2-7

PC Programmer Software
automatically appears after approximately 10 to 20 seconds.

Installation/Upgrade
Figure 2-7. Initial Installation Screen

b. Click Simplex Programmer. The Welcome Screen, shown in Figure


2-8, appears.

If Installing from Floppy Disk, do the following:

a. Insert Disk 1 in the floppy drive.


b. Click the Start button and choose the Run option. The Run dialog
appears.
c. Click Browse. After the Browse dialog appears, click on the Look In
list box, and select the A:\ drive.
d. When the contents of the A:\ drive appear, click on Setup.
e. Click on the Open button. The Browse dialog closes and the Run
dialog becomes the active dialog.
f. Click OK.
A progress thermometer appears, showing the progress of the Install Shield
installation. This is followed by the Welcome Screen shown in Figure 2-8.

Continued on next page

2-7

Technical Manuals Online! - http://www.tech-man.com


Step 3. Install or Upgrade the PC Programmer Software, Continued

Procedure (continued)

Figure 2-8. Installation Welcome Screen

2. Click Next.

The screen shown in Figure 2-9 appears. As shown in the figure, the
default installation directory is:
C:\Program Files\Simplex\Programmer\
In most cases, it is recommended that you install the software in this
directory. If necessary, use the Browse button to specify a different drive or
directory path.

Figure 2-9. Choose Destination Directory Dialog

Continued on next page

2-8

Technical Manuals Online! - http://www.tech-man.com


Step 3. Install or Upgrade the PC Programmer Software, Continued

Procedure (continued) 3. Click Next.

A progress thermometer appears, indicating the progress of the file copy


operation. The next prompt, shown in Figure 2-10, indicates that the
installation is finished and that you need to reboot the machine.

PC Programmer Software
Installation/Upgrade
Figure 2-10. Reboot Prompt

2-9

Technical Manuals Online! - http://www.tech-man.com


This is Blank

Technical Manuals Online! - http://www.tech-man.com


Chapter 3
Downloading a Bin File

Overview This chapter describes downloading a BIN File from the PC on which the PC
Programmer software is installed to the 4010 FACP. You need to do this in the
following situations:

Following installation of the Version 2.x PC Programmer software, you


must download the Version 2.x BIN file that accompanied the programmer
software to the panel.

As revisions to the 4010 FACP are made, you may receive additional copies
of the BIN file to download.

Before You Begin Before getting started, make sure that you have the following:

Download cable (Simplex Part # 733-794)


Floppy with Version 2.x BIN file (Simplex Part # 741-108)

In this Chapter Refer to the following page for specific information on a topic.

Downloading a BIN File


Topic See Page #
Step 1. Connect Serial Cable and Set Serial 3-2
Parameters
Step 2. Enable Panel for Download 3-4
Step 3. Upload and Archive Version 1.x Jobs 3-5
Step 4. Download (BIN) File 3-6

3-1

Technical Manuals Online! - http://www.tech-man.com


Step 1. Connect Serial Cable and Set Serial Parameters

Overview This section describes:

Connecting the serial cable (733-794) between the PC on which the


programmer software is installed and the 4010 FACPs service port.
Setting PC Programmer serial communication parameters.
Setting the baud rate on the 4010 FACP.

Step 1. Connect the Serial Connect the 733-794 serial cable between a free serial port on the service PC
Cable and the service port of the 4010 FACP, as follows:

1. Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 3-1 to the PC. Make sure that the red stripe is aligned to the left
as you connect the cable.

2. Connect the other end to the service port on the 4010 FACP.

Align Red Stripe


to the Left

9-Pin Connector
goes to PC

Figure 3-1. Connecting Serial Cable

Step 2. Set PC Programmer The PC Programmer software requires you to specify settings for the following
Communication Parameters serial communication parameters.

Port = COMx
Baud = 9600 or 19200 (recommended)
Parity = None
Stop Bits = 1
Data Bits =8

Continued on next page

3-2

Technical Manuals Online! - http://www.tech-man.com


Step 1. Connect Serial Cable and Set Serial Parameters, Continued

Step 2. Set PC Programmer Click the Start button. Point to Programs and select Simplex. When the choices
Communication Parameters appear, select Programmer.
(continued)
1. Click on the Programmer applications Transfer menu and select Settings.
A dialog similar to the one shown in Figure 3-2 appears.

2. Set the parameters to the settings listed earlier in this section.

Figure 3-2. Serial Port Settings

Step 3. Set 4010 FACP Baud Switches 2-1 and 2-2 on the 4010 FACP set the panels baud rate. Table 3-1
Rate summarizes the possible settings for these switches, and Figure 3-3 shows their

Downloading a BIN File


location. Make sure that the baud rate you set on the 4010 FACP matches the
baud rate set for the PC Programmer software.

Table 3-1. 4010 Baud Rate Switch Settings

Baud Rate SW 2-1 SW 2-2


OFF LINE ON ON
9600 OFF ON
19,200 ON OFF

Black indicates switch positio

OFF LINE

9600

19,200

Figure 3-3. Using Switches SW1 and SW2 to Set Panel Baud Rate

3-3

Technical Manuals Online! - http://www.tech-man.com


Step 2. Enable Panel for Download

Procedure Follow the steps in this section to enable the 4010 FACP for downloads.

1. Login to the 4010 at Access Level 4.


2. Press <MENU>.
3. Press <NEXT> until [UPLOAD/DOWNLOAD] is displayed.

<ENTER> to Accept <NEXT/PREV to Scroll


Menu: [Upload/Download]

4. Press <ENTER>. A screen similar to the following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Prog. Interface: [Initialize Up/Dwnload]

5. Press the <NEXT> or <PREV> keys until [Initialize Up/Dwnload] is


displayed and press <ENTER>.

The 4010 displays the following message to indicate that the panel is ready to
accept a download.

*** File Transfer Initialized ***


*** Check Programming Unit **

3-4

Technical Manuals Online! - http://www.tech-man.com


Step 3. Upload and Archive Version 1.x Job Files

Upload, Backup, and Archive If a Version 1.x job is currently loaded on the panel, make sure to upload,
Existing Version 1.x Job backup, and archive this job before downloading the Version 2.x BIN file.
Downloading the Version 2.x BIN file erases the existing Version 1.x job from
the panel.

After uploading and restoring the Version 2.x BIN file, you can restore the
Version 1.x job, rebuild it as a Version 2.x job, and download it back to the
panel.

Refer to the following sections of this manual for information on uploading and
backing up a job.

Topic Refer to
Uploading a Job Chapter 4 Uploading a Job from
the Panel
Backing Up and Archiving a Job Chapter 4 Saving, Archiving,
Backing Up, and Restoring Jobs

Downloading a BIN File

3-5

Technical Manuals Online! - http://www.tech-man.com


Step 4. Download BIN File

Overview Downloading the BIN file is a three-step process:

1. Copy the BIN file from the floppy to the PC Programmer computer.
2. Start the download process on the PC.
3. Perform a Warm Start on the 4010 FACP.

Follow the steps outlined below for specific instructions.

Step 1. Copy BIN File from Use Windows Explorer to copy the BIN file from the floppy disk to a directory
Floppy to PC Programmer on the PC Programmers hard drive. It is recommended that you copy the file to
Computer the following directory. This is the default directory in which the programmer
looks for BIN files.

\PROGRAM FILES\SIMPLEX\PROGRAMMER

Step 2. Start Download on PC 1. Click on the Transfer menu. When the selections appear, choose Transfer.
Programmer A window similar to the one shown Figure 3-4 appears.

Figure 3-4. Upload/Download Window

2. Select the following radio button options in the windows panels.

Download
Direct
Panel EXEC

3. Click OK. The dialog shown in Figure 3-5 appears, warning you to backup
the system before continuing.

Continued on next page

3-6

Technical Manuals Online! - http://www.tech-man.com


Step 4. Download BIN File, Continued

Step 2. Start Download on PC


Programmer (continued)

Figure 3-5. Caution Dialog

4. Click Yes.

A window similar to the following appears, prompting you for the location
of the EXEC (Bin) file.

Downloading a BIN File


Figure 3-6. Open Dialog

5. Select the directory to which the file was copied, click on the name of the
EXEC file, and then select the Open button.

A dialog similar to the following displays.

Figure 3-7. Download Dialog

6. Click the Start button.

A message appears in the Download Dialog (Figure 3-7), indicating that the
PC Programmer is waiting for the 4010 FACP to begin downloading the
file.

Continued on next page

3-7

Technical Manuals Online! - http://www.tech-man.com


Step 4. Download BIN File, Continued

Step 3. Warm Start the 4010 Performing a Warm Start of the 4010 FACP triggers the panel to download the
FACP EXEC (Bin) file from the PC Programmer.

1. Login to the 4010 at Access Level 4.


2. Press <MENU>.
3. Press <NEXT> until [PANEL RESTART] is displayed.

<ENTER> to Accept <NEXT/PREV to Scroll


Menu: [Panel Restart]

4. Press <ENTER>. A screen similar to the following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Panel Restart: [Warm Start]

5. Press the <NEXT> or <PREV> keys until [Warm Start] is displayed and
press <ENTER>

A warm start initiates the start of the download. At the PC Programmer, the
Download dialog (Figure 3-7) shows the progress of the download.

When the download is complete, you should restore and download the Version
1.x job (if necessary).

3-8

Technical Manuals Online! - http://www.tech-man.com


Chapter 4
Getting Started

Overview This chapter describes the following tasks:

Using Quick CFIG to autoconfigure a panel


Starting the programmer
Creating a new job
Opening an existing job
Uploading a job from the panel
Saving, archiving, backing up and restoring jobs

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Using Quick CFIG to Autoconfigure a Panel 4-2
Starting the Programmer 4-4
Creating a New Job 4-5
Opening an Existing Job Stored on the PC 4-7
Uploading a Job from the Panel 4-8
Saving, Archiving, Backing Up, and Restoring Jobs 4-13

Getting Started

4-1

Technical Manuals Online! - http://www.tech-man.com


Using Quick CFIG to Autoconfigure a Panel

Using Quick CFIG to Create a The 4010 FACP includes the Quick CFIG utility, an automatic configuration
New Job tool that automatically detects 4010 points. For most new installations, it is
more efficient to run 4010 Quick CFIG from the front panel and then upload the
CFIG from the 4010 to the PC Programmer, where any changes to the point
types, custom labels, and system options can be made.

Using Quick CFIG on a new panel configures the panel for general alarm
operation as follows:

All initiating devices found by Quick CFIG are assigned a FIRE point type.
SIG1 and SIG2 are set to point type SSIGNAL. SIG3 and SIG4 are set to
RSIGNAL.
AUX1 is set to point type RRELAY. AUX2 is set to TRELAY.
Remote annunciators are detected at their set address.

Hardware that is not automatically configured includes:

Graphic annunciators
Suppression points
Network card
SDACT or CCDACT card

Quick CFIG Reconfigure All The Quick CFIG Reconfigure All Hardware option, described in this section,
Hardware Option creates a new 4010 configuration.

Note1: If a configuration exists and this option is selected, it clears the current
configuration and adds all currently connected devices to the CFIG.

Note 2: Quick CFIG terminates if duplicate IDNet devices are detected. If this
happens, run Quick CFIG again and watch the LCD. Before the
program terminates, it will list the first seven duplicate addresses
found.

1. Press <MENU>.
2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no
longer in the Fire Alarm Operation mode.

Please Wait . . .
Fire Alarm Operation Suspended

3. Press <ENTER> to continue with the Quick-CFIG option.


4. Press <NEXT> or <PREVIOUS> until <RECONFIGURE ALL
HARDWARE> is displayed and then press <ENTER>. A warning
appears, indicating that this will delete the current configuration.

WARNING <Enter> to Continue WARNING


This will DELETE current configuration

Continued on next page

4-2

Technical Manuals Online! - http://www.tech-man.com


Using Quick CFIG to Autoconfigure a Panel, Continued

Quick CFIG Reconfigure All 5. Press <ENTER> to continue. Another warning appears, indicating that you
Hardware Option (continued) need to press <ENTER> to confirm the deletion.

WARNING <Enter> to Continue WARNING


Press <Enter> to confirm deletion

6. A message appears indicating that Quick CFIG is reconfiguring the


hardware. This message is followed by another, which indicates that Quick
CFIG is scanning for IDNet devices. The Reconfigure ALL Hardware
function is complete when a message similar to the following appears.

** Automatic Hardware Detection Completed **


Total IDNet Devices Added: 128

Upload the Job from the When Quick CFIG completes, you need to upload the job from the panel to the
Panel to the Laptop laptop PC on which the programmer is installed. Once the job is uploaded, you
can open it and customize it as required by the customer, i.e., custom labels,
system options, etc.

See Uploading a Job from the Panel, later in this chapter for specific
information on doing this.

Getting Started

4-3

Technical Manuals Online! - http://www.tech-man.com


Starting the Programmer

Using the Start Menu Click on the Start menu and point to Programs. When the choices appear, point
to Simplex and then choose Programmer.

A screen similar to the one shown in Figure 4-1 appears.

Figure 4-1. Initial Programmer Screen

4-4

Technical Manuals Online! - http://www.tech-man.com


Creating a New Job

Introduction This section describes creating a new job with the PC programmer. Doing this
creates a job with limited definitions for the devices (i.e., no custom labels and
default device type or point types assigned to IDNet points). This is useful for
off-site configuration of a system.

After creating a job in this manner, refer to the subsequent chapters in this book
for information on adding option cards to the job, defining system options,
defining device and point types, and adding custom control equations.

Skip this section if you used Quick CFIG to create a new job and uploaded it to
the laptop.

Note: Each branch is responsible for assigning and archiving jobs. The
exception to this is a network job, in which case the network job
number must be assigned by Simplex Applications Engineering.

Step 1. Invoke New System 1. Start the programmer, as described in the previous section.
Dialog
2. At the initial Programmer Screen (Figure 4-1), click on the File menu and
choose New.

The dialog shown in Figure 4-2 appears.

Getting Started
Figure 4-2. New System Dialog

Continued on next page

4-5

Technical Manuals Online! - http://www.tech-man.com


Creating a New Job, Continued

Step 2. Specify Job Number Enter a name for the job in the Job Number field. It is recommended that you
use a seven-character number with the following format:

BBYMTJJ

BB = Branch Number (1296 possible numbers using the Base 36 numbering


system.) See Appendix B for a Base 36 conversion table.
Y = Year (0 = 1997; 1 = 1998;. . . A = 2007)
M = Month (1 = Jan; 2 = Feb; . . . C = Dec)
T = Panel Type (D = 4010)
JJ = Job number (1296 jobs per branch per month possible using the Base 36
numbering system.) See Appendix B for a Base 36 conversion table.

Example: Job 3004D01 translates to the following:


Branch Number: 108 (becomes 30 using the Base 36 numbering
system)
Year: 1997 (becomes 0)
Month: April (becomes 4)
Panel Type: 4010 (becomes D)
Job Number: 01 (still 01 using the Base 36 numbering system)
Note: See Appendix B for the Base 10 to Base 36 Conversion Table.
If you enter a Job Name that does not conform to this convention, a warning
message box is presented reminding you of the Job Name format. However, a
non-conforming Job Name will be allowed as long as it follows the DOS file-
naming conventions and only contains characters that are part of the 4010
character set. All alpha characters entered will be automatically converted to
upper-case.
When you create a new job file, the Programmer places the letter A at the end
of your seven-character job name. Each time you open this job and make a
revision, the revision letter is also upgraded.

Step 3. Specify System Type Examine the entry for the System Type drop down list box. The selection must
read 4010. Click on this list box and change the currently selected system
type to 4010 if necessary.

Step 4. Specify Standalone or The System Options panel, located at the bottom of Figure 4-2, allows you to
Network System specify whether the 4010 system is operating as a standalone or networked
system. This panel contains the following three choices:

Standalone System specifies that the 4010 is not connected via a 4120
network to other panels.

New Network specifies that the 4010 is physically connected to other


panels, but no network job exists in the 4010s \NETJOBS folder. In this
case, you must specify a network job number in the Job Number field of
Figure 4-2. Make sure to specify only a job number supplied by Simplex
Applications Engineering.

Existing Network specifies that the 4010 is connected to other panels, and
the job has been previously programmed.

4-6

Technical Manuals Online! - http://www.tech-man.com


Opening an Existing Job Stored on the PC

Introduction By default, previously programmed jobs are stored in either the \4010JOBS or
the \NETJOBS directory. If the job for the panel that you are currently
programming is stored on the PC, use the following procedure to open it for
additional editing.

You should only do this if you are sure that the job on the PC is exactly the same
as the programming (CFIG) currently in use on the panel. For example, if you
have made changes to the panels programming from the 4010 front panel, it
may be more desirable to upload the CFIG from the panel to the laptop PC
before performing additional programming. See the next section for details.

Procedure 1. Click on the File menu.

2. Select Open.

A window similar to the following appears.

Figure 4-3. Open Database Dialog

3. Open the folder containing the job that corresponds to the panel you are
currently programming.

The name of the job (filename.sdb) appears.

Getting Started
4. Select the job name and click on the Open button. One of the following
occurs, depending on whether the job has been previously archived.

Non-Archived Jobs. A series of messages appear, indicating that the


programmer is loading the job and updating links. These messages are
followed by the main PC Programmer screen.

Archived Jobs. A prompt appears, indicating that the job has been
previously archived and changes will be saved to a new revision of the
job. Click OK to continue. The next screen displays the main PC
Programmer screen.

4-7

Technical Manuals Online! - http://www.tech-man.com


Uploading a Job from the Panel

Introduction This section describes uploading an existing job from a 4010 FACP to the
service PC for editing. An upload occurs over a serial link running between the
panel and the PC. Follow the steps outlined in the following sections to link the
PC and panel and upload the job.

Note: If the panel containing the job that you want to upload is on a network,
you can upload the job, but you cannot edit the jobs attributes (i.e.,
change system options, add points, etc.). Contact Simplex Service for
additional information.

Step 1. Set Panel and PC 1. Set switches SW1 and SW2 to the positions shown in Figure 4-4. These
Baud Rates to 19,200 positions enable a baud rate of 19,200 on the 4010 FACP.

Black indicates switch position

19,200

Figure 4-4. Switch Position for 19,200 Baud

2. Start the 4010 Programmer application.

Click on the Transfer menu and select Settings.

A dialog similar to the one shown in Figure 4-5 appears.

Figure 4-5. Setting PC Transfer Rate to 19,200

3. Set these parameters as follows:

Port. Set this radio button to the setting that corresponds to the serial
port to which the serial cable will be connected. In most cases, this will
be COM1.
Baud Rate. Set to 19,200.
Parity. Set to None.
Stop Bits. Set to 1.
Data Bits. Set to 8.

Continued on next page


4-8

Technical Manuals Online! - http://www.tech-man.com


Uploading a Job from the Panel, Continued

Step 2. Connect Serial Cable Connect a 733-794 serial cable between a free serial port on the service PC and
between PC and Panel the service port of the 4010 FACP.

1. Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 4-6 to the PC.

2. Connect the other end to the service port on the 4010 FACP. Make sure that
the red stripe is aligned to the left as you connect the cable.

Align Red Stripe


to the Left

9-Pin Connector
goes to PC

Figure 4-6. Connecting Serial Cable

Step 3. Enable Upload on 1. Login to the 4010 at Access Level 4.


Panel 2. Press <MENU>.
3. Press <NEXT> until [UPLOAD/DOWNLOAD] is displayed.

<ENTER> to Accept <NEXT/PREV to Scroll


Menu: [Upload/Download]

Getting Started
4. Press <ENTER>. A screen similar to the following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Prog. Interface: [Initialize Up/Dwnload]

5. Press the <NEXT> or <PREV> keys until [Initialize Up/Dwnload] is


displayed and press <ENTER>.

Continued on next page

4-9

Technical Manuals Online! - http://www.tech-man.com


Uploading a Job from the Panel, Continued

Step 3. Enable Upload on The 4010 displays the following message to indicate that the panel is ready to
Panel (continued) upload a job.

*** File Transfer Initialized ***


*** Check Programming Unit **

Step 4. Start Upload at PC 1. Click on the Transfer menu. When the selections appear, choose Transfer.
A window similar to the one shown in Figure 4-7 appears.

Figure 4-7. Upload/Download Dialog


2. Select the following radio button options in the windows panels.
Upload
Direct
Panel CFIG
3. Click OK.

The dialog shown in Figure 4-8 appears, prompting you to begin the upload.

Figure 4-8. Upload Dialog


4. Click on the Start button to begin the upload. One of the following occurs,
depending on whether a job by the same name already exists in the PCs
\4010JOBS folder.

Continued on next page

4-10

Technical Manuals Online! - http://www.tech-man.com


Uploading a Job from the Panel, Continued

Step 4. Start Upload at PC If Job Name Already Exists on PC. If a job by the same name already
(continued) exists in the 4010JOBS folder on the PC, the programmer generates a
prompt asking whether you want to write over the existing file. If you do
not want to write over the existing file, click on No. Another dialog
appears, giving you the opportunity to rename the job. If you want to
overwrite the existing job, click on Yes button. A dialog similar to the one
shown in Figure 4-9 appears, indicating the progress of the file transfer.

If Job Name Does Not Exist on PC. If no job with this name exists on the
PC, the programmer begins the download after you click on the Start
button. A dialog similar to the one shown in Figure 4-9 appears, indicating
the progress of the file transfer.

Figure 4-9. Transfer in Progress

The following message appears when the upload is complete.

Figure 4-10. Upload Complete Message

5. Click OK to continue.

The next message indicates that the programmer is unbuilding the job.

Getting Started
Figure 4-11. Unbuilding 4010 Job Message

The programmer displays the next message to indicate that the job has been
successfully unbuilt and is now stored in the 4010JOBS folder.

Continued on next page

4-11

Technical Manuals Online! - http://www.tech-man.com


Uploading a Job from the Panel, Continued

Step 4. Start Upload at PC


(continued)

Figure 4-12. Job Unbuild Complete Message

To open this job, refer to Opening an Existing Job Stored on the PC, earlier in
this chapter.

4-12

Technical Manuals Online! - http://www.tech-man.com


Saving, Archiving, Backing Up, and Restoring Jobs

Introduction This section discusses the programmers file management tools Save, Archive,
Backup, and Restore. Refer to the appropriate section below for additional
information.

Always backup and archive a job following editing and successful download.
Doing this allows you to return to a known state should critical problems occur
with an edited job file.

Saving a Job This option writes an editable version of the job using the job name specified
by the user, followed by the .MDB file extension to the PCs hard disk.

To save a job, do the following:

1. Open the Save dialog, in either of the following ways:

Click on the Save icon, represented by a disk icon on the icon bar.
Click on the File menu and select the Save option.

A dialog similar to the following appears, allowing you to specify the name
of the file and list the modifications made to the file.

Getting Started
Figure 4-13. Save Dialog

2. Enter the jobs file name in the Name field.


3. List any changes made to the job in the Enter Modifications field.
4. Click on OK to close the dialog.

Continued on next page

4-13

Technical Manuals Online! - http://www.tech-man.com


Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Using Save As To create a copy of the job currently being edited, use the Save As option. To
do this, click on the File menu and choose Save As.

A dialog similar to the one shown in Figure 4-14 appears, allowing you to
specify the new file name, the destination directory, and the destination drive.

Figure 4-14. Save As Dialog

Archiving a Job Archive creates a compressed, permanent/non-writable copy of a job, and does
the following with it:

Saves the job to floppy, or a remote (networked) disk.


Saves the job to the hard disk, marking it Read-Only. (This copy can be
restored at a later date, using the Restore command, which is described
below.)

To archive a job, follow these steps:

1. Make sure the job has been saved before archiving.


2. Click on the File menu and select the Archive option.

A dialog similar to the following appears.

Figure 4-15. Archive Dialog

3. Click on a destination drive. The Archive utility automatically names the


file and creates a \4010ARCH directory on the drive that you choose.

Continued on next page

4-14

Technical Manuals Online! - http://www.tech-man.com


Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Archiving a Job (continued) 4. Click on the Archive button.


The system generates a prompt, asking whether you really want to archive
the job.
5. Click Yes to continue or No to exit.
If the 4010ARCH directory does not already exist on the target drive, the
system prompts you to create it. If the directory exists, this prompt does not
appear.
6. Choose Yes to create the directory.
The system displays a message indicating that the archive is complete and
the job can no longer be edited. (Use Restore to restore an archived job, if
necessary.)
7. Click OK.

8. When the Programmer Archive Utility dialog reappears, click Exit to close
the Archive utility.

Backing Up a Job Backup stores a read/writable version of the job on either a removable storage
medium or a remote disk. Follow these steps to backup a job.

1. Click on the File menu and select the Backup option.


A dialog similar to the one shown in Figure 4-16 appears:

Continued on next page

Getting Started

4-15

Technical Manuals Online! - http://www.tech-man.com


Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Backing Up a Job (continued) 2. Select the destination directory and drive.

3. Click on the Backup button.

Figure 4-16. Backup Dialog

A message appears, prompting whether to continue with the backup or


terminate the operation.

4. Click Yes to continue.

The progress of the backup appears on the bottom of the Backup dialog.

5. Click Exit to exit the application when the backup is complete.

Restoring a Backed Up or Restore allows previously backed up or archived jobs to be retrieved for
Archived Job subsequent viewing or editing.

To restore a backed up or archived job, follow these steps:

1. Click on the File menu and select the Restore option.

A dialog, similar to the one shown in Figure 4-17, appears.

Continued on next page

4-16

Technical Manuals Online! - http://www.tech-man.com


Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Restoring a Backed Up or
Archived Job (continued)

Figure 4-17. Restore Dialog

2. Select the drive and directory containing the Backup or Archive files.

3. Choose the file to restore and click on the Restore button. Archived files
are listed with an SDA4010 file extension, and Backup files are listed with
an SDC4010 file extension.

A message similar to the following appears.

Getting Started

4. Click Yes to continue. One of the following occurs, depending on whether


a copy of the job already exists on the PC.

If the job does not already exist on the PC, the progress of the Restore
operation displays at the bottom of the screen.

If the job already exists on the PC, Restore asks if you want to
overwrite the existing file. Click Yes to initiate the Restore or No to
exit.

4-17

Technical Manuals Online! - http://www.tech-man.com


White text

Technical Manuals Online! - http://www.tech-man.com


Chapter 5
Setting General Information,

Genl Info/System Options


System Options, Passcodes, and Access Levels

Introduction This chapter describes setting the systems general information, system options,
passcodes, and access levels.

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Entering General Information 5-2
Enabling System Options 5-3
Setting Passcodes and Access Levels 5-9

5-1

Technical Manuals Online! - http://www.tech-man.com


Entering General Information

Entering General Information 1. Select the Panel tab.


2. Select the General Information radio button.
A window similar to the following appears.
3. Enter the applicable information in the fields.

Figure 5-1. General Information

5-2

Technical Manuals Online! - http://www.tech-man.com


Enabling System Options

Genl Info/System Options


Introduction The following section describes setting the 4010s system options. Click on the
Panel tab and then choose the System Options radio button to gain access to the
options. Refer to the applicable section below for information on a specific
system option.

Figure 5-2. System Options

Time Format The Time Format option allows you to display system time in 12- or 24-hour
format. That is, time is displayed in either a 12-hour format that uses an AM
(morning) or PM (afternoon) designation, or in 24-hour (military style) format.

The Time format directly affects how time is displayed on the 4010 not only at
the high-level status screen but in the Historical Logs.

Enable either 12- or 24-hour format by selecting the appropriate check box, as
shown below: Refer to Figure 5-2 for the location of this option.

Continued on next page

5-3

Technical Manuals Online! - http://www.tech-man.com


Enabling System Options, Continued

Depleted Battery This option selects the mode of operation for the 4010 FACP if an alarm occurs
during an AC power loss while a Depleted Battery trouble exists. The specific
operation of this option differs slightly, depending on whether you have a
domestic or Canadian system.
Domestic Operation. The default setting for the option is OFF and the depleted
battery threshold voltage is 19.4 VDC 5%. Operation of this option for a
domestic system is as follows:

If the system is in alarm and a depleted battery condition occurs, any NACs
that are active remain active.
If the system in not in alarm and a depleted battery condition occurs, the
NACs are prevented from activating.
Canadian Operation. The default setting for the option is OFF and the depleted
battery threshold voltage is 19.4 VDC 5%. Operation of this option for a
Canadian system is as follows:
When a depleted battery condition occurs, power is turned off to the 4010.
AC power must be restored to re-activate the 4010.
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Alarm Silence/Inhibit You can inhibit the Alarm Silence/System Reset on a 4010 FACP for a set
duration. The range for the Silence/Reset Inhibit timer is 0-60 minutes with zero
(No Inhibit) being the default setting.

Enable this option by selecting the following check box, as shown below. Refer
to Figure 5-2 for the location of this option.

Alarm Cutout Timer The Alarm Signal Cutout timer allows you to set a duration for how long
signals sound after an alarm. In other words, when an alarm condition exists,
the signals sound until silenced. With this option set at two minutes, building
signals sound on alarm for two minutes and then stop sounding. However, the
alarm condition remains active in the panel. The default setting for this options
is No Cutout (meaning an Alarm Silence is required to shut off signals).

Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Continued on next page

5-4

Technical Manuals Online! - http://www.tech-man.com


Enabling System Options, Continued

Genl Info/System Options


Door Drop on Alarm The Door Drop on Alarm timer allows the 4010 to hold doors open for a set
duration during an alarm condition. After that duration has expired, the 4010
shuts off the door holder relays and the doors close. The range for the timer is
0-60 seconds with a default setting of zero seconds. To have door holders drop
the doors immediately, leave the timer set to zero seconds.

Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Note: To make a relay a door holder relay, you must assign it the DHOLDER
point type.

Door Drop on AC Fail The Door Holder - AC Fail Door Drop Timer allows the 4010 to hold doors
open for a set duration during an AC power loss condition. After that duration
has expired, the 4010 shuts off the door holder devices and the doors close. The
range for the timer is 0-60 minutes, with a default setting of 5 minutes. To have
door holders drop the doors immediately upon AC power loss, set the timer to
zero minutes.

Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Air Handling Units (AHU) This option allows you to set the 4010 to stagger start any Air Handling Units
Stagger Start (point types AHUR, AHUO, and AHUF) in the 4010 FACP . This option
protects against power spikes that may cause the circuit breakers to trip when
AHUs start simultaneously. The range for stagger starting the AHUs is 0-60
seconds. The default setting for this option is 30 seconds. A setting of zero
allows all AHUs to start immediately.

The 4010 FACP displays an AHU Stagger Start message when the sequence
starts and an AHU Stagger Start Complete message when the sequence ends.

Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Continued on next page

5-5

Technical Manuals Online! - http://www.tech-man.com


Enabling System Options, Continued

Suppression Release The Suppression Release option contains three selections:

Dual Detector. When enabled, this option requires two points in L9


(Automatic Suppression Release Points List) to activate before the outputs
specified in L12 (Suppression Release Output Points List) activate.

Detector Delay. When enabled, this option allows you to specify a delay
between the time that a detector activates and the time that a point within
the L9 list triggers. The range is from 0 to 60 seconds (60 is the default).

Manual Delay. When enabled, this option allows you to specify a delay,
ranging from 0 to 30 seconds, between the time that a manual release point
is activated and the time that the suppression release points in L10 trigger.

- L9 Automatic Suppression Release Points


- L10 Suppression Manual Release Points
- L11 Suppression Release Abort Points
- L12 Suppression Release Output Points
For example: any points in L9 have a default delay of 60 seconds before L12
activates, any points in L10 have a default delay of 30 seconds before L12
activates. Once points in L10 are activated, L12 activates after the default 30-
second delay regardless of the state of abort switches in L11. When Dual
Detector operation is ON, this requires two points in L9 to activate before
suppression release operation is initiated.

WARNING: When any points in L11 are activated during the


cycling of a delay function, the delay timers continue
to count down to zero. If you release the abort
switch that is in L11 after the timer has reached zero,
points in L12 activate immediately.

Note 1. Do not use the PC Programmer to change the point type of a


suppression release point; doing this causes the PC Programmer to change the
point type back to its default setting. To change the point type of a suppression
release point, you must use the front panel programmer.

Note 2. Set the Depleted Battery Cut Out Timer system option to ON for
suppression release systems. Refer to Depleted Battery earlier in this section
for information.

Continued on next page

5-6

Technical Manuals Online! - http://www.tech-man.com


Enabling System Options, Continued

Genl Info/System Options


Active Status Reminder The Active Status Reminder option allows you to set an interval and duration
during which the 4010 reminds operators that a FIRE, SUPV, or TBL condition
still exists in the panel.

Active Status Reminder consists of two parts. Refer to Figure 5-2 for the
location of these options.

Reminder Interval. Enable the Reminder Interval by selecting the check


box shown below. Use the control on the right to set the interval. The
range can be from 1 to 12 hours, and the default is 8 hours.

Acknowledge Option. This option sets the duration of the acknowledge


signal. The range can be from 1 to 12 hours, and the default is 5 seconds.
For troubles, a setting of 0 sounds a continuous signal until acknowledged
from the front panel. For alarms, a setting of 0 sounds a continuous signal
until the alarm condition is cleared.

Signal Operation Audible and Visible ON til Silence Notification Appliance Circuits (NACs) can
be set to the choices shown in Table 5-1. The default setting for the Audible
NACs is Temporal; the default setting for the Visible NACs is Synchronous; and
the default setting for TrueAlert Non-Addressable Horns is TEMPORAL.

Continued on next page

5-7

Technical Manuals Online! - http://www.tech-man.com


Enabling System Options, Continued

Signal Operation (continued)


Table 5-1. Signal Choices

Signal Type Choices


Audible NAC Temporal A three pulse coding pattern
Operation consisting of three second pulses, each
separated by second silence. Each group of
three pulses is separated by 1.5 seconds of
silence.
Steady
March Time
Slow March Time
Visual NAC Steady
Operation March Time
Slow March Time
Temporal
Synchronous
TrueAlert Non- Possible selections for this option are
Addressable Horn Steady
Operation Temporal
Slow March Time

5-8

Technical Manuals Online! - http://www.tech-man.com


Setting Passcodes and Access Levels

Genl Info/System Options


Overview All operations in the 4010 are protected at a preset level with designated
passcodes to access these operations. The table below shows the basic
operations and menu choices for specific access levels. The default passcodes
are listed for Levels 2 through 4.

Table 5-2. Access Levels and Operations

ACCESS LEVEL OPERATIONS


Ack
1 Silence
System Reset
All Level 1 Operations, plus:
2 Set Time/Date
Default Point Control
Passcode = 2000 Enable/Disable Points
All Level 1 & 2 Operations,
plus:
Clear Logs
Clear Verification Tallies
3 Programming
Default
Passcode = 3000 - Edit/Clear Point Label
- Restore/Save CFIG
TrueTest
Walk Test
Reports
All Level 1,2, & 3 Operations,
plus:
Quick CFIG
Run Diagnostics
4 Upload/Download
Default Programming
Passcode = 4000 Edit Cards
Edit SMPL Program
System Options
Restart Panel
Warm Start
Cold Start

Continued on next page

5-9

Technical Manuals Online! - http://www.tech-man.com


Setting Passcodes and Access Levels, Continued

Setting Passcodes 1. Select the Panel tab, if it is not already selected.


2. Click on the Passcodes radio button. See Figure 5-3.
3. Edit the passcodes, as necessary.

Figure 5-3. Passcodes

Setting Access Levels 1. Select the Panel tab, if it is not already selected.

2. Click on the Access Levels radio button. See Figure 5-3.

3. For each of the operations listed in Figure 5-4, use the controls to set an
access level of 1, 2, 3, or 4.

Figure 5-4. Access Levels

5-10

Technical Manuals Online! - http://www.tech-man.com


Chapter 6
Programming Cards

Introduction The 4010 allows you to manually add and delete option cards, and to view and
program points and card options (user-defined LEDs and function keys) on a
per-card basis.

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #

Programming Cards
Overview Card Tab 6-2
Adding / Deleting Cards 6-4
Programming Master Controller (SFIO) Card 6-5
Programming the NAC Card 6-9
Programming the AUX Relay Card 6-11
Programming the IDNet Card 6-13
Viewing and Programming Analog and Digital 6-16
Pseudos
Programming a Dual RS-232 Card 6-22
Programming an RS-232 Service Modem Card 6-24
Programming a 4120 Network Card 6-29
Programming a 24 Point I/O Card 6-32
Programming an LCD Annunciator Card 6-37

6-1

Technical Manuals Online! - http://www.tech-man.com


Overview Card Tab

Card Tab Screen Components The Card Tab, shown in Figure 6-1, provides a graphical means of adding,
deleting, and programming 4010 FACP cards. Components of the Card Tab
screen include:

Active Card List. The left-hand side of the screen lists all cards (hardware
and logical) installed on the 4010 FACP. Green cards represent hardware
components and blue cards represent logical groups of similar points. (For
example, Card 19 represents all Digital User Pseudo Points.)
Available Card List. The right-hand side of the screen lists available
option cards that can be added to the system.
Splitter Bar. The width of the Active Card and Available Card lists can be
changed by positioning the cursor directly over the splitter bar, clicking and
holding the left mouse button, dragging the bar to a new location, and then
releasing the bar.

Splitter Bar

Figure 6-1. Card Tab

Card Configuration Rules The following card configuration rules apply to the 4010 FACP:

Cards 1 through 3 and 17 through 23 cannot be deleted.


One 4120 Network Card or One DACT is allowed.
One Dual RS232 Card or One RS232/Modem is allowed.

Continued on next page

6-2

Technical Manuals Online! - http://www.tech-man.com


Overview Card Tab, Continued

Using AutoFill The programmer includes an AutoFill feature that allows you to automatically
add pre-selected text or selections to a points device type, point type, or custom
label fields.

Follow these steps to use AutoFill:

1. Open the card whose points you want to edit.

2. Click on the point containing the text or selections you want to copy. The
points entry highlights to show it is selected.

3. If you want to copy the highlighted text to a range of points, do one of the

Programming Cards
following:

Range of Adjoining Points. If the points adjoin one and other, hold
down the SHIFT key and click the left mouse button on the topmost
point in the range. Continue to hold down the SHIFT key, move to the
bottom point in the range, and click and release the mouse button.

Range of Non-Adjoining Points. If the points do not adjoin one


another, hold down the CTRL key and select each point. Release the
CTRL key only after all points have been selected.

4. Press the F4 key. The AutoFill dialog appears.

5. Click on the check boxes (device type, point type, or custom label)
corresponding to the fields that you want to automatically fill. You can
select multiple fields (i.e. device type and custom label).

6. Click on the appropriate radio button in the Selection panel, as follows:

All Points. Automatically fills every point with the device type, point
type, or custom label of the point selected in Step 2 above.

Selected Points. Automatically fills every selected point (Step 3 above)


with the device type, point type, or custom label of the point selected in
Step 2 above.

Point Forward. Automatically fills every point forward of the point


selected in Step 2 above with that points device type, point type, or
custom label.

7. Click OK to AutoFill the selected fields.

6-3

Technical Manuals Online! - http://www.tech-man.com


Adding / Deleting Cards

Introduction This section describes manually adding or deleting option cards. Each time you
add a card, the programmer specifies default values for card and point attributes.
After you add a card(s), refer to the appropriate section later in this chapter for
information on editing card-specific information. Refer to Chapter 7
Programming Points for information on programming a cards points and
options.

Adding Cards 1. In the Available Cards List, select the card you want to add.

2. Hold the left mouse button down, drag the card to the Active Card List, and
release the mouse button.

The programmer prevents you from adding cards that violate the card
configuration rules.

Deleting Cards 1. In the Active Card List, click the right mouse button on the icon
representing the card you want to delete. A menu, containing the Delete
and Properties choices, appears. Refer to Figure 6-2.

2. Select Delete.

The programmer prevents you from deleting cards 1 through 3 and 17


through 23.

3. Select Yes when the programmer prompts you to confirm the delete
operation.

Figure 6-2. Delete Option

6-4

Technical Manuals Online! - http://www.tech-man.com


Programming Master Controller (SFIO) Card

Introduction The Master Controller card icon, located at the top of the Active Cards List
(refer to Figure 6-1), represents the 4010s SFIO board. Double clicking on this
icon invokes the Master Controller (SFIO) Card Programming Screen shown in
Figure 6-3.

The top of the screen contains a list of the points associated with the SFIO card.
The point name, device type, and point type none of which is editable is
shown for each point.

Programmable components of the Master Controller card include:

User Defined LED1, LED2, and LED3. See Programming User-Defined

Programming Cards
LEDs, later in this section for additional information.
User Defined Function Key 1 and User Defined Function Key 2. See
Programming User-Defined Function Keys later in this section for
additional information.

Figure 6-3. Master Controller (SFIO) Card Programming Screen

Programming User-Defined Each user defined LED allows you to monitor the state of a specific system
LEDs point, illuminating when the state of the point changes. For example, LED 1 can
be programmed to light RED when the state (mode) of list point L26 (Waterflow
points) changes to ALARM.

Follow these steps to program an LED.

1. Choose the LED color by clicking on the radio button to the left of the
appropriate color.

NOTE: It is not possible to independently program the LEDs colors. In


other words, you cannot have the LED light RED when one state is true or
YELLOW when another state is true.

Continued on next page

6-5

Technical Manuals Online! - http://www.tech-man.com


Programming Master Controller (SFIO) Card, Continued

Programming User-Defined 2. Click on the Mode drop down list box. Choose the mode (State) that must
LEDs (continued) be true to illuminate the LED. Refer to Table 6-1 for details on the
available modes.

3. Click on the Ref Address list box and associate a point with the mode you
set in Step 2. The list that appears depends on the Mode selection. The Ref
Address list contains either physical points, pseudo points, list points, or no
entries.

Table 6-1. Modes for User-Defined LEDs

Mode Meaning
Disable LED illuminates when the state of the REF ADDR
(point) is DISABLED.
Fire LED illuminates when the state of the REF ADDR
(point) goes into ALARM
LF LED illuminates when the ALARM ACK button on the
panel is pushed.
LS LED illuminates when the SUPV ACK button on the
panel is pushed.
LT LED illuminates when the TROUBLE ACK button on
the panel is pushed.
OFF LED illuminates when the state of the REF ADDR
(point) is OFF.
ON LED illuminates when the state of the REF ADDR
(point) is ON
SMPL LED illuminates when the state of a Custom Control
equation(s) is TRUE.
SUPERV LED illuminates when the state of the REF ADDR
(point) goes into SUPERV.
TROUBLE LED illuminates when the state of the REF ADDR
(point) goes into ALARM

User-Defined LED Examples. The following examples show typical ways in


which user-defined LEDs are used.

Waterflow Indicator. The following example monitors L26, a user-defined


list containing all Waterflow Points, and illuminates the RED LED if any point
within this list goes into an ALARM state.

1. Click on the radio button to the left of the RED led.


2. Click on the Mode drop-down list box and select FIRE.
3. Click on the Ref. Address list box and select L26.

Continued on next page

6-6

Technical Manuals Online! - http://www.tech-man.com


Programming Master Controller (SFIO) Card, Continued

Programming User-Defined Earth Ground Detect. The following example tracks the state of P76, a user-
LEDs (continued) defined pseudo point, and illuminates the Yellow LED if P76 turns ON.

P76 is, in turn, controlled by an SMPL equation, shown below, that monitors
power supply points 2-2 (+ Earth Ground) and 2-3 (Neg. Earth Ground). If
either point turns ON (i.e., indicates an Earth ground problem, either positive or
negative), the equation turns on P76, which illuminates the Yellow LED to
indicate the problem.

1. Click on the radio button to the left of the Yellow led.


2. Click on the Mode drop-down list box and select ON.
3. Click on the Ref. Address list box and select P76.

Programming Cards
The SMPL equation for the Earth Ground Detect example is shown below.

INPUT

ON/CODE 2-2
or ON/CODE 2-3

OUTPUT

TRACK ON P76 PRI 9,9

Programming User-Defined Function keys are a way to easily and repeatedly perform a specific function
Function Keys (Mode) on a particular system point (Reference Address).

1. Click on the Mode drop-down list box and choose the appropriate mode.
Refer to Table 6-2 for information on the modes.

2. If the Mode allows, click on the Ref. Address drop-down list box and
choose the point to which the mode applies.

Continued on next page

6-7

Technical Manuals Online! - http://www.tech-man.com


Programming Master Controller (SFIO) Card, Continued

Programming User-Defined
Function Keys (continued) Table 6-2. Modes for User-Defined Function Keys

Mode Meaning
ACK Function key acknowledges all alarms, troubles, and
supervisories.
DE N/A with user-defined function keys.
LFACK Function key acknowledges all fire alarms.
LSACK Function key acknowledges all supervisory events.
LSR Function key performs a system reset on the local
panel.
LSS Function key performs a signal silence on the local
panel.
LTACK Function key acknowledges all trouble events.
LTEST Function key performs a lamp test.
ONOFF N/A with user-defined function keys.
PBH Pressing the function key turns the specified point
(Ref. Address) ON until the function key is released.
PBT This mode allows the reference address to track the
state of the function key. The point turns ON if the
switch is active and turns OFF if the switch is not
active.
SMPL Used to indicate that an SMPL equation is being
used to program the function key.
TDE Function key toggles (reverses) the Disable/Enable
state of the specified point (Ref. Address).
TOF Function key toggles (reverses) the ON/OFF state of
the specified point (Ref. Address).

6-8

Technical Manuals Online! - http://www.tech-man.com


Programming the NAC Card

Introduction The 4010 FACP provides four Notification Appliance Circuits (NACs), each of
which connects one or more Notification Appliances (horns, strobes, bells, etc.)
to the 4010.

The PC Programmer represents the 4010s standard, hardwired NACs as the


NAC card. (Note: 4009 IDNet NACs are grouped and programmed under the
IDNet card.) Opening the NAC card allows you to view and program the device
type, point type, and custom label of the standard Notification Appliances.

The position of the NAC card within the Active Cards List is shown below.

Programming Cards
Figure 6-4. NAC Card Location within Active Cards List

Step 1. Open the NAC Card Double click on the NAC icon shown in Figure 6-4. A window similar to the
following appears. This window displays all standard NACs.

Figure 6-5. Card Data Entry Window for NACs

Step 2. Edit Device Types Edit a NACs Device Type, as follows:

1. Move to the line corresponding to the NAC whose device type you want to
change.
2. Double click on the NACs existing device type. A list box appears,
containing the following choices:

SIGA - Class A NAC. NAC contains multiple signal paths, allowing


circuit operation to continue if a single open circuit occurs. This option
requires installation of a Class A NAC adapter card.
SIGB - Class B NAC. NAC contains only a single circuit path.

Continued on next page

6-9

Technical Manuals Online! - http://www.tech-man.com


Programming the NAC Card, Continued

Step 3. Edit Point Types Edit a NACs Point Type, as follows:

1. Double click on the NACs existing Point Type. A list box appears,
containing NAC-specific point types.
2. Select the appropriate Point Type. Refer to Table 6-3 for a quick reference
of point types, or refer to Appendix A for detailed point type descriptions.

Table 6-3. NAC Point Types Quick Reference

NAC Point Types Application


AHUF AHU off relay dual relay control
AHUO AHU on relay dual relay control
AHUR AHU on/off relay signal relay
ALTERN Elevator capture - alternate
BSIGNAL Trouble/supervisory bell signal
DHOLDER Door holder control
PRIMARY Elevator capture - primary
QALERT TrueAlert Non-Addressable signal
RELAY Generic relay
RSIGNAL Alarm signal on until reset
RVISUAL Visual on until reset
RWATER Waterflow signal on until reset
SIGNAL Generic signal (no default operation)
SQALERT TrueAlert Non-Addressable signal
on until silence
SSIGNAL Alarm signal on until silence
SUPREL Suppression release output
SUPV Sprinkler supervisory signal
SVISUAL Visual on until silence
SWATER Waterflow signal on until silence
TSIGNAL Trouble/supervisory signal

Step 4. Edit Custom Labels Edit a NACs Custom Label, as follows:

1. Move to the line corresponding to the NAC whose custom label you want to
change.
2. Double click on the NACs existing label and type the appropriate label.

Refer to Using AutoFill at the beginning of this chapter for information on


copying custom label text to a range of points.

6-10

Technical Manuals Online! - http://www.tech-man.com


Programming the AUX Relay Card

Introduction The 4010 FACP includes two auxiliary relays commonly referred to as AUX
relays. Each relay provides one Form C contact, normally open or normally
closed, rated at 2A (24 VDC) or 0.5 A (120 VAC) with the optional auxiliary
relay kit.

The PC Programmer represents all AUX relays as the AUX Relay card.
Opening this card allows you to view and program the point type and custom
label for these relays. (Note: AUX Relays do not have a programmable device
type.)

Figure 6-6 shows the location of the AUX Relay card within the Active Card
List.

Programming Cards
Figure 6-6. AUX Relay Icon

Step 1. Open the AUX Relay Double click on the AUX Relay icon. A window similar to the following
Card appears.

Figure 6-7. Card Data Entry Window for AUX Relays

Continued on next page


6-11

Technical Manuals Online! - http://www.tech-man.com


Programming the AUX Relay Card, Continued

Step 2. Edit the Point Type Edit an AUX Relays Point Type, as follows:

1. Double click on the AUX Relays existing Point Type.


2. Select the appropriate Point Type. Refer to Table 6-4 for a quick reference
of point types, or refer to Appendix A for detailed point type descriptions.

Table 6-4. AUX Relay Point Types Quick Reference

AUX Relay Point Application


Types
AHUF AHU off relay dual relay control
AHUO AHU on relay dual relay control
AHUR AHU on/off relay signal relay
ALTERN Elevator capture - alternate
BSIGNAL Trouble/supervisory bell signal
DHOLDER Door holder control
PRIMARY Elevator capture - primary
QALERT TrueAlert Non-Addressable signal
RELAY Generic relay
RSIGNAL Alarm signal on until reset
RVISUAL Visual on until reset
RWATER Waterflow signal on until reset
SIGNAL Generic signal (no default operation)
SQALERT TrueAlert Non-Addressable signal on until
silence
SSIGNAL Alarm signal on until silence
SUPREL Not Applicable
SUPV Sprinkler supervisory signal
SVISUAL Visual on until silence
SWATER Waterflow signal on until silence
TSIGNAL Trouble/supervisory signal

Step 3. Edit Custom Label Edit an AUX Relays Custom Label, as follows:

1. Move to the line corresponding to the AUX Relay whose custom label you
want to change.
2. Double click on the relays custom label field and enter the appropriate
label.

Refer to Using AutoFill at the beginning of this chapter for information on


copying custom label text to a range of points.

6-12

Technical Manuals Online! - http://www.tech-man.com


Programming the IDNet Card

Introduction The 4010 FACP supports up to 250 IDNet points.

The PC Programmer represents all IDNet points as the IDNet card. Opening
this card allows you to view and program the device type, point type, custom
label, and mode (sounder base smoke detectors only) for each IDNet point.

Figure 6-8 shows the location of the IDNet card within the Active Card List.

Programming Cards
Figure 6-8. IDNet Card Icon

Step 1. Open the IDNet Card Double click on the IDNet icon, shown in Figure 6-8. A window similar to the
following appears.

Figure 6-9. Card Data Entry Window for IDNet

Continued on next page

6-13

Technical Manuals Online! - http://www.tech-man.com


Programming the IDNet Card, Continued

Step 2. Edit Each Points Edit an IDNet points Device Type, as follows:
Device Type
1. Move to the line corresponding to the point whose device type you want to
change.

2. Double click on the points device type field. A list box appears, containing
the IDNet-specific choices shown in Table 6-5. Refer to Appendix A for
detailed descriptions of these device types.

Table 6-5. IDNet Device Types

Device Type Application


4009A 4009A with 4 NACs
4009A8 4009A with 8 NACs
ADRPUL Addressable Pull Station
CANPUL Canadian Pull Station
HEAT TrueAlarm Heat Detector
IAM Line Power Sup. IAM with TrueSense
IHEAT TrueAlarm heat detector with isolator
IION TrueAlarm ion detector with isolator
IOHEAT TrueAlarm heat detector with ROR and Relay
ION TrueAlarm ionization detector
IPHOTO TrueAlarm photo detector with isolator base
KACPULL KAC Pull Station
MAZAM Class A Monitor ZAM (T-sense)
MBZAM Class B Monitor ZAM (T-sense)
OHEAT TrueAlarm Heat Detector with ROR
PHOTO TrueAlarm Photoelectric Detector
QIPHOTO Quick Connect Photo with Isolator
QPHOTO Quick Connect Photo
QRPHOTO Quick Connect Photo with Relay
QSPHOTO Quick Connect Photo with Sounder
R4009A 4009A 4 NACs with Repeater
R4009A8 4009A 8 NACs with Repeater
RHEAT TrueAlarm heat detector with relay
RIAM Relay IAM
RION TrueAlarm ion detector with relay
ROHEAT TrueAlarm heat detector with ROR and Relay
RPHOTO TrueAlarm photo detector with relay
SHEAT TrueAlarm heat detector with sounder
SION TrueAlarm ion detector with sounder
SOHEAT TrueAlarm heat detector with ROR and Relay
SPHOTO TrueAlarm photo detector with sounder
XIPHOTO Extra sensitive TrueAlarm photo detector with
isolator
XPHOTO Extra sensitive TrueAlarm photo detector
XRPHOTO Extra sensitive TrueAlarm photo detector with
relay
XSPHOTO Extra sensitive TrueAlarm photo detector with
sounder

Continued on next page

6-14

Technical Manuals Online! - http://www.tech-man.com


Programming the IDNet Card, Continued

Step 3. Edit Each Points Edit an IDNet points Point Type, as follows:
Point Type
1. Move to the line corresponding to the IDNet point whose point type you
want to change and double click on the Point Type field.
2. Select the appropriate Point Type. Refer to the Monitor Point Type
descriptions in Appendix A for detailed information on IDNet point types.

Note: Do not use the PC Programmer to change the point type of a suppression
release point; doing this causes the PC Programmer to change the point type
back to its default setting. To change the point type of a suppression release
point, you must use the front panel programmer.

Programming Cards
Step 4. Set Single Station TrueAlarm devices with sounder bases default to Single Station mode. Single
Mode (Detectors with station has the following effect.
Sounder Bases Only)
Sounder activates when the associated sensor is above its alarm threshold.

Sounder silences when sensor is below its alarm threshold.

Alarm remains at panel until reset is performed.

Follow these steps to enable or disable Single Station mode for a specific point.

1. Double click on the points Mode field.

Two choices appear. One choice is blank (disables Single Station mode)
and the other choice is Single Station (enables Single Station mode).
2. Select the appropriate mode.

To globally disable Single Station mode, use the front panel programmer
interface (System Options menu).

6-15

Technical Manuals Online! - http://www.tech-man.com


Viewing and Programming Analog and Digital Pseudos

Introduction The pseudo point cards, each of which represents a separate and distinct group
of pseudo points, are located at the bottom of the Active Cards List. Figure 6-10
shows the location of these cards.

Figure 6-10. Digital and Analog Pseudo Cards

Viewing Card 18 Digital Card 18 represents the Digital System Pseudos. These points store a value of
System Pseudos ON or OFF and are used by the system to monitor and control system
components and functions.

Double clicking on the Card 18 icon, shown in Figure 6-11, displays the
systems 75 digital pseudo points and their pre-assigned label. This is a view-
only screen and cannot be edited.

Figure 6-11. Card 18 Digital System Pseudos (View Only)

Continued on next page

6-16

Technical Manuals Online! - http://www.tech-man.com


Viewing and Programming Analog and Digital Pseudos, Continued

Card 19 User Digital User-defined Digital Pseudo Points are used within Custom Control equations.
Pseudos The function of a user-defined digital pseudo point is determined by the point
type that you assign it. Table 6-6 lists the point types for user-defined digital
pseudo points and explains their function.

To program the Point Type and Custom Label for each user-defined digital
pseudo point, follow these steps.

1. Double click on the Card 19 icon within the Active Cards List. A window
similar to the following appears.

Programming Cards
Figure 6-12. Card 19 User-Defined Digital Pseudos

2. Edit a pseudo points point type, as follows:

a. Move to the line corresponding to the pseudo point whose point type
you want to change.
b. Double click on the points existing point type. A list box appears,
containing the choices shown in Table 6-6. Click on the appropriate
choice.

3. Double click on a points Custom Label field to edit its custom label.

Continued on next page

6-17

Technical Manuals Online! - http://www.tech-man.com


Viewing and Programming Analog and Digital Pseudos, Continued

Card 19 User Digital


Pseudos (continued) Table 6-6. Point Types for User-Defined Digital Pseudo Points

Point Type Application


ALARM Turning ON a digital pseudo point with this point type
causes an Alarm condition.
SUPV Turning ON a digital pseudo point with this point type
causes a Supervisory condition.
TROUBLE Turning ON a digital pseudo point with this point type
causes a Trouble condition.
UTILITY A UTILITY digital pseudo point can hold a value of
ON or OFF, and is typically used as an ON/OFF
switch within a custom control equation.
Example. In the following Custom Control equation,
P76 turns ON only when the state of point 2-2 or 2-3
is ON. P76 can then be monitored by other system
components, triggering other actions when it turns
ON.
INPUT

ON/CODE 2-2
or ON/CODE 2-3

OUTPUT

TRACK ON P76 PRI 9,9

Card 20 Analog System Card 20 represents the systems Analog Pseudo Points. These type of pseudo
Pseudos points store analog values (the number 128, for example), and can be used as a
threshold value within a Custom Control equation. (For example, perform some
action when the value of the Trouble Count analog pseudo point [A2] reaches a
specific value).

Double click on the Card 20 icon, shown in Figure 6-10, to display the systems
analog pseudo points and their pre-assigned labels. This is a view-only screen
and cannot be edited. Refer to Figure 6-13 for an example of this screen.

Continued on next page

6-18

Technical Manuals Online! - http://www.tech-man.com


Viewing and Programming Analog and Digital Pseudos, Continued

Card 20 Analog System


Pseudos (continued)

Programming Cards
Figure 6-13. Card 20 System Analog Pseudo Points (View Only)

Card 21 Analog User Analog User Pseudos store analog values that can be used in Custom Control
Pseudos equations. The exact function of an analog user pseudo depends on its point
type counter, timer, or analog value.

Double clicking on the Card 21 icon within the Active Cards List displays the
systems user Analog Pseudo points. Refer to Figure 6-14 for an example of
this screen.

Figure 6-14. Card 21 Analog User Pseudos

Continued on next page

6-19

Technical Manuals Online! - http://www.tech-man.com


Viewing and Programming Analog and Digital Pseudos, Continued

Card 21 Analog User Follow the steps below to program an analog user pseudos point type or custom
Pseudos (continued) label.

1. Edit the point type of a user analog pseudo point, as follows:

a. Move to the line corresponding to the pseudo point whose point type
you want to change.
b. Double click on the points existing point type. A list box appears,
containing the choices shown in the following table. Click on the
appropriate choice.

Table 6-7. Analog Psuedo Point Types

Point Type Application


ANALOG Stores a static, analog value between 0 and 65,535.
COUNTER Allows the points analog value to be incremented by
Custom Control equations. Typically used to track
the number of some system condition and trigger
some action when a threshold is reached.
TIMER Allows you to set an analog value between 0 and
65, 535 that can be used as a countdown timer. A
timer can be used to delay some action until a
specified amount of time passes.

2. Double click in the Custom Label field to edit the points custom label.

Card 22 System Defined List List Pseudos provide a means of monitoring a range of similar devices. (All
Pseudos Waterflow Alarm Monitor Zones, for example.)

Double clicking on the Card 22 icon within the Active Cards List displays the
System List Pseudo points and their pre-assigned label. This is a view-only
screen and cannot be edited.

Figure 6-15. System List Pseudo Points

Continued on next page


6-20

Technical Manuals Online! - http://www.tech-man.com


Viewing and Programming Analog and Digital Pseudos, Continued

Card 23 User Definable List User Definable List Pseudos allow you to create a list of similar points for use in
Pseudos Custom Control equations, user-defined LEDs, user-defined function keys, etc.
The list point turns ON if one of the points referenced in the list turns ON. You
can only edit a lists custom label from the Card Tab.

Follow the steps below to program a user-defined list pseudos custom label.

1. Double click on the Card 23 icon. A screen similar to the one shown in
Figure 6-16 appears.

Programming Cards
Figure 6-16. User Defined List Pseudos

2. Move to the line corresponding to the point whose custom label you want to
change. Double click on the line and edit the points label.

6-21

Technical Manuals Online! - http://www.tech-man.com


Programming a Dual RS-232 Card

Introduction The Dual RS-232 card allows one or two printers to be attached to the 4010
panel. Programming a dual RS-232 card involves setting the communication
parameters and selecting which events are annunciated to the printer(s).

Step 1. Open the RS-232 Card Double click on the icon that represents the RS-232 card. (If the card is not
Screen already in the Active Cards List, you first need to drag it from the Available
Cards list into the Active Cards List.) A screen similar to the one shown in
Figure 6-17 appears.

Figure 6-17. RS-232 Card Screen

Step 2. Configure Configure the settings for the printer attached to Port A or Port B, as follows:
Communication Settings
1. Click on the Port A or Port B radio button.

2. Click on the drop-down list box beneath the radio button and specify the
type of printer attached to the port. If no printer is attached to the port,
select Unused. Do not select Command when configuring a printer.

Table 6-8. Supported Printer Types

Option Application
Unused Unused port
Print80U 80 character, unsupervised printer
Print80S 80 character, supervised printer
Print40U 40 character, unsupervised printer
Print40S 80 character, supervised printer
Command Used only when a service modem is
connected to an RS-232 Service Modem
Card. See next section of this manual for
details.

Continued on next page


6-22

Technical Manuals Online! - http://www.tech-man.com


Programming a Dual RS-232 Card, Continued

Step 2. Configure 3. Click on the Port Label field, shown below, and specify the location of the
Communication Settings printer.
(continued)

4. Use the drop down list boxes under Communication Settings to specify the
Baud Rate, number of Data Bits and Stop Bits, and the Parity setting in use
on the printer.

Programming Cards
Step 3. Select Events 1. Move to the Event Reporting panel and select the check boxes that
correspond to the types of events you want annunciated at the printer.
Refer to Table 6-9 for information on these checkboxes.

Table 6-9. Event Choices

Checkbox Application
Fire Alarm Events Prints an event when an ALARM condition
occurs.
Trouble Events Prints an event when a TROUBLE condition
occurs.
Supervisory Events Prints an event when a SUPERVISORY
condition occurs.
Walk Test Events Prints an event when a WALKTEST occurs.
Silence/Reset Events Prints an event when a System Reset or
Alarm Silence is performed.
SMPL Print Statements Allows SMPL Print statements to print at the
Events printer.
Control Events Prints an event when a control point (signal or
relay) turns ON or OFF.
Utility Events Prints an event when a point with the Utility
point type turns ON or OFF.
Pseudo Events Prints an event when a pseudo point changes
state, either from ON to OFF or vice versa.
Reports Events Specifies whether the printer prints a report
when a report is generated at the panel.

2. Click OK to close the screen.

6-23

Technical Manuals Online! - http://www.tech-man.com


Programming an RS-232 Service Modem Card

Introduction The RS-232 Service Modem card allows the following:

Service personnel can dial into the 4010 FACP through the RS-232 Service
Modem card and perform basic control and monitoring of the panel, and
request system reports.

System status and reports can be sent out the service modem port and
displayed on a remote terminal or computer.

This section describes programming the RS-232 Service Modem Card and
provides a brief description of the remote commands used to monitor/control the
4010 FACP.

Step 1. Open the RS-232 Double click on the icon that represents the RS-232 Service Modem card. (If
Service Modem Card Screen the card is not already in the Active Cards List, you first need to drag it from the
Available Cards list into the Active Cards List.)

A screen similar to the one shown in Figure 6-18 appears.

Figure 6-18. RS-232 Service Modem Card Screen

Step 2. Configure 1. Click on the Port B radio button.


Communication Settings for
Port B 2. Click on the drop-down list box beneath the Port B radio button and select
the Command option.

Continued on next page

6-24

Technical Manuals Online! - http://www.tech-man.com


Programming an RS-232 Service Modem Card, Continued

Step 2. Configure 3. Click on the Port Label field, shown below, and specify the location of the
Communication Settings for control device.
Port B (continued)

4. Use the drop down list boxes under Communication Settings to specify the
modems Baud Rate, number of Data Bits and Stop Bits, and the Parity.

Programming Cards
Step 3. Select Events to Move to the Event Reporting panel and select the check boxes that correspond
Forward to Remote System to the types of events you want annunciated at the remote system. Refer to
Table 6-10 for information on these checkboxes.

Table 6-10. Event Choices

Checkbox Application
Fire Alarm Events Displays an event when an ALARM condition
occurs.
Trouble Events Displays an event when a TROUBLE
condition occurs.
Supervisory Events Displays an event when a SUPERVISORY
condition occurs.
Walk Test Events Displays an event when a WALKTEST occurs.
Silence/Reset Events Displays an event when a System Reset or
Alarm Silence is performed.
SMPL Print Statements Displays SMPL Print statements at the remote
Events system.
Control Events Displays an event when a control point (signal
or relay) turns ON or OFF.
Utility Events Displays an event when a point with the Utility
type turns ON or OFF.
Pseudo Events Displays an event when a pseudo point
changes state, either from ON to OFF or vice
versa.
Reports Events Specifies whether the system displays a
report when one is generated at the panel.

Continued on next page

6-25

Technical Manuals Online! - http://www.tech-man.com


Programming an RS-232 Service Modem Card, Continued

Service Modem Command Service modem commands are either query type commands that request
Summary information or action type commands that direct the panel to perform some
function. The asterisk shown within each command denotes the minimum
number of characters that you must type. For example, to use the TIME
command, you need to type, at a minimum, the T character. In the examples,
the character represents the prompt.

Table 6-11. Service Modem Commands

Command Explanation / Examples


Sets and displays the system time and date.
Viewing Current Time and Date. Type T at the prompt as shown below:
-T
T*IME The system responds by displaying the time and date, similar to the following:
8:00:05 am Wed 25-DEC-98
Changing Current Time and Date. Type a T followed by the time and date.
-T 9:00 am 25-DEC-98

Returns the current logical point status (ON, OFF, FIRE, etc.) for the requested point.
Viewing Status for a Specific Point. Enter the LIST command, followed by the points
address (see Appendix A for a list of point addresses). For example:
-LIST P260
Viewing List of Current Alarms, Troubles, or Supervisories. Enter the LIST command,
L*IST followed by an F (current list of alarms), T (current list of Troubles), or S (current list of
Supervisories). For example:
-LIST F
Viewing Alarm, Trouble, or Supervisory Counts. Enter the List command, followed by
COUNT.
-LIST COUNT

Allows the user to manipulate the status of a control point or digital pseudo point.
Turning a Point ON. Enter the SET command, followed by the points address (see
Appendix A for a list of point addresses), and the ON qualifier. For example:
-SET P260 ON
Turning a Point OFF. Enter the SET command, followed by the points address (see
S*ET
Appendix A for a list of point addresses), and the OFF qualifier. For example:
-SET P260 OFF
Clearing an Override Trouble. Enter the SET command, followed by the points address
(see Appendix A for a list of point addresses), and the AUTO qualifier. For example:
-SET P260 AUTO

Continued on next page

6-26

Technical Manuals Online! - http://www.tech-man.com


Programming an RS-232 Service Modem Card, Continued

Service Modem Command


Summary (continued)

Table 6-12. Service Modem Commands (continued)

Command Explanation / Examples


Displays the revision of the 4010s system software and the revision and name of the CFIG
(job) executing on the panel. For example:
REV*ISION
-REVISION
SYS REV: 2.01 CFIG FORMAT: 71 JOB 92A1004A REV:7 24-NOV-99

Programming Cards
Help on Parameters. Enter HELP without a parameter to see a list of available
parameters. To see a short text description of a parameter, type HELP, followed by a
parameter.
Help on Commands. Enter HELP, followed by a command to see a short text description
HELP
for one of the service modem commands. Applicable commands are: TIME, LIST
REVISION, SET, DISABLE, HELP, LOGIN, RESTART, ACK, PRINT, CLEAR, TYPE. For
example:
-HELP TYPE

Allows the user to perform a cold or warm restart.


Performing a Warm Start. Enter RESTART, followed by the qualifier WARM. A warm
start re-initializes the hardware, but does not affect the logs, time and date, verification
tallys, and disable states. For example:
RES*TART
-RESTART WARM
Performing a Cold Start. Enter RESTART, followed by the qualifier COLD. A cold start
performs a complete re-initialization of the panel.
-RESTART COLD

Acknowledging the Highest Priority Abnormal Point. Enter the ACK command with no
qualifiers. For example:
-ACK
ACK
Acknowledging All Points in the Active Alarm (fire), Trouble, or Supervisory List.
Enter the ACK command, followed by F, T, or S. For example:
-ACK F

Logging in to a Remote System. Enter LOGIN at the prompt and wait for the prompt to
reappear. When it does, enter the 4 digit passcode that corresponds to the desired login
level. For example:
LOG*IN -LOGIN
-4000
Logging Out of a Remote System. Enter LOGIN at the prompt and wait for the prompt to
reappear. When it does, enter a carriage return.

Continued on next page

6-27

Technical Manuals Online! - http://www.tech-man.com


Programming an RS-232 Service Modem Card, Continued

Service Modem Command


Summary (continued)

Table 6-13. Service Modem Commands (continued)

Command Explanation / Examples


Sends a report to the report printer. The PRINT command must be followed by one of the
following qualifiers:
ALOG Prints the alarm log
PRINT TLOG Prints the trouble log
SLOG Prints the supervisory log
CLOG Prints the combined log
TASERV Prints a TrueAlarm service report
TASTAT Prints a TrueAlarm status report

The command allows the user to clear the alarm log, trouble log, supervisory log, or
combined log. Type CLEAR, followed by one of the following:

CLEAR ALOG Prints the alarm log


TLOG Prints the trouble log
SLOG Prints the supervisory log
CLOG Prints the combined log

Sends a report to the terminal (PC) from which the command was issued. The TYPE
command must be followed by one of the following qualifiers:
ALOG Prints the alarm log
TYPE TLOG Prints the trouble log
SLOG Prints the supervisory log
CLOG Prints the combined log
TASERV Prints a TrueAlarm service report
TASTAT Prints a TrueAlarm status report

Allows the user to disable/enable points.


Disabling a Point. Enter the DISABLE command, followed by a point and the ON
qualifier. For example:
DIS*ABLE -DISABLE P260 ON
Enabling a Point. Enter the DISABLE command, followed by a point and the OFF
qualifier. For example:
-DISABLE P260 OFF

Three control key commands are supported:


CTRL+A
CTRL+S CTRL+A Acknowledges the highest priority abnormal point
CTRL+D CTRL+S Alarm Silence
CTRL+D System Reset

6-28

Technical Manuals Online! - http://www.tech-man.com


Programming a 4120 Network Card

Introduction This section describes programming a 4120 network card -- either an RS485
card (also known as a Wired Media card) or a modular card with either RS485
or Fiber.

Be aware of the following before beginning:

You cannot create a network of only 4010 panels. You must connect the
4010 to a network containing either a 4100, GCC, or NPU.

Use the PC Programmers Network Tab to create public points.

Programming Cards
Step 1. Define Network Job If you are adding a network card to a non-networked job (i.e., you selected
Attributes (If Necessary) Standalone Panel when you originally created the job), the programmer presents
the following screen, which allows you to specify the network job number,
description, and network file. Once a standalone job is changed to a network
job, you can no longer upload the job to the laptop. Make sure you backup the
job before proceeding.

Figure 6-19. New Network Job Dialog

1. Select the appropriate radio button New Network or Existing Network


as required.

2. If the network job is new, you must specify the Network File number and
Network Description for the job. Refer to Simplex Applications
engineering for information on specifying a network file number.

Continued on next page

6-29

Technical Manuals Online! - http://www.tech-man.com


Programming a 4120 Network Card, Continued

Step 1. Define Network Job 3. Double click on the icon that represents the 4120 Network card. (If the card
Attributes (If Necessary) is not already in the Active Cards List, you first need to drag it from the
(continued) Available Cards list into the Active Cards List.)

A screen similar to the one shown in Figure 6-20 appears.

Figure 6-20. 4120 Network Card Screen

Step 2. Enter Description The Description field specifies what appears in the DBN Node Listing
Description, shown at the bottom of Figure 6-20.

Continued on next page

6-30

Technical Manuals Online! - http://www.tech-man.com


Programming a 4120 Network Card, Continued

Step 3. Set Node / Loop Choose the appropriate selections for Node Number, Loop Number, and Comm
Number and Comm Style Style, as follows:

Node Number. The Node Number is a unique number used to identify the 4010
panel on the 4120 network. The range for this number is between 1 and 99. If
necessary, first use the Simplex Network Programmer or the network
diagnostics to view the other nodes on the network. Review the node numbers
already in use and select a unique number for this node.

Loop Number. A 4120 network can support up to 4 separate loops, with no


physical bridging or routing of information between loops. Make sure that the
loop number you choose is the same as all other nodes on the loop.

Programming Cards
Comm Style. Style 4 networks represent a single line or star topology. With
these types of networks a single short, ground fault, or open circuit on the
network communications channel reports a trouble and all nodes beyond the
fault operate in local (standalone) mode.

Style 7 networks represent a closed loop ring. With these types of networks, any
single open, short, or ground fault on the network communications channel will
not interrupt communications between nodes on the network.

Step 4. Select Port Media Modular versions of the 4120 card allow the use of either Wired Media (RS485)
(Modular Card Only) or fiber for the cards left and right ports.

1. Click the drop down list box underneath Left Port and select the choice that
represents the type of module used on the cards left port.

2. Click the drop down list box underneath Right Port and select the choice
that represents the type of module used on the cards right port.

6-31

Technical Manuals Online! - http://www.tech-man.com


Programming a 24 Point I/O Card

Introduction A 24 Point I/O card allows 24 additional input (either two or three position
switches) or output devices (lamp, piezo, relay, or on until reset relay) to be
connected to the 4010 FACP.

Double click on the icon that represents the 24 Point I/O card. (If the card is not
already in the Active Cards List, you first need to drag it from the Available
Cards list into the Active Cards List.)

A screen similar to the one shown in Figure 6-21 appears.

Figure 6-21. 24 Point I/O Card Screen

Programming an Input Device 1. Click on the Device Type field and select GRAPHIN device type.
(Two- or Three-Position
Switch) 2. Click on the point type field and select one of the following:

OSWITCH. Specifies a two-position switch, supervised for open


circuits. Requires an EOL resistor.
SSWITCH. Specifies a two-position switch, supervised for open and
short circuits. Requires EOL and current limited (up leg) resistors.
TSWITCH. Three position (SPDT) switch, supervised for open
circuits. Requires EOL and current limited resistors.
USWITCH. Two-position switch, unsupervised. Assumes that no
EOL or current limited resistor is used. For this type of switch,
SHORT = ON and OPEN = OFF.

3. Select the mode (operation) of the switch. Refer to Table 6-11 for specific
information on the modes.

4. Click on the Ref. Addr field and select the point affected by the mode.

Continued on next page

6-32

Technical Manuals Online! - http://www.tech-man.com


Programming a 24 Point I/O Card, Continued

Programming an Input Device


(Two- or Three-Position
Switch) (continued)
Table 6-14. Input Modes

Mode Switch Type Circuit State and Result


Open Acknowledges all alarms and troubles
USWITCH
Normal Mode OFF
Short Acknowledges all alarms and troubles
OSWITCH

Programming Cards
ACK Programs the switch to Normal Mode OFF.
acknowledge all alarms and Limited Acknowledges all alarms and troubles
troubles SSWITCH
Normal Mode OFF
Normal Mode OFF
TSWITCH Short Acknowledges all alarms and troubles
Limited Acknowledges all alarms and troubles

Open Enables the referenced point.


USWITCH
DE -- Programs the switch to Normal Disables the referenced point.
disable or enable a specific point. Short Enables the referenced point.
This mode is typically used with a 2- OSWITCH
position maintained or a 3-position Normal Disables the referenced point.
switch, and is not intended to be Limited Enables the referenced point.
used with a 2-position momentary SSWITCH
Normal Disables the referenced point.
switch. Use TDE (toggle
disable/enable) with a 2-position Normal Mode OFF
momentary. TSWITCH Short Disables the referenced point
Limited Enables the referenced point

Performs the modes action i.e.,


Open
USWITCH acknowledges alarms, performs reset, etc.
LFACK Programs the switch to Normal Mode OFF
acknowledge Fire Alarms.
Performs the modes action i.e.,
Short
LSR Programs the switch to OSWITCH acknowledges alarms, performs reset, etc.
perform a system reset. Normal Mode OFF
Performs the modes action i.e.,
LSS Programs the switch to Limited
SSWITCH acknowledges alarms, performs reset, etc.
perform a signal silence.
Normal Mode OFF
LTACKPrograms the switch to Normal Mode OFF
acknowledge troubles.
Performs the modes action i.e.,
LTEST Programs the switch to Short acknowledges alarms, performs system
TSWITCH
perform a lamp test. reset, etc.
Performs the modes action i.e.,
Limited
acknowledges alarms, performs reset, etc.

Continued on next page

6-33

Technical Manuals Online! - http://www.tech-man.com


Programming a 24 Point I/O Card, Continued

Programming an Input Device


(Two- or Three-Position
Switch) (continued)
Table 6-11. Input Modes (continued)

Mode Switch Type Circuit State and Result


Open Turns point ON
USWITCH
Normal Turns point OFF
ONOFF Programs the switch to Short Turns point ON
turn the referenced point ON or OSWITCH
OFF. This mode is typically used Normal Turns point OFF
with a 2-position maintained or a 3- Limited Turns point ON
position switch, and is not intended SSWITCH
to be used with a 2-position Normal Turns point OFF
momentary switch. Normal Mode OFF
TSWITCH Short Turns point ON
Limited Turns point OFF

Open Turns point ON and holds it ON.


USWITCH
Normal Mode OFF
Short Turns point ON and holds it ON.
PBH Push Button Hold. This OSWITCH
mode programs the switch to turn a Normal Mode OFF
point ON and hold it ON. Point Limited Turns point ON and holds it ON.
must be turned OFF by Custom SSWITCH
Normal Mode OFF
Control or system reset.
Normal Mode OFF
TSWITCH Short Turns point ON and holds it ON.
Limited Turns point ON and holds it ON.

Open Turns referenced point ON.


USWITCH
Normal Turns referenced point OFF
PBT Push Button Track. This
mode allows the reference address Short Turns referenced point ON.
OSWITCH
to track the state of the switch. The Normal Turns referenced point OFF
point turns ON if the switch is active
Limited Turns referenced point ON.
and turns OFF if the switch is not SSWITCH
active. This mode is intended for Normal Turns referenced point OFF
use with a 2 position momentary or Normal Turns referenced point OFF.
push button switch.
TSWITCH Short Turns referenced point ON.
Limited Turns referenced point ON.

Continued on next page

6-34

Technical Manuals Online! - http://www.tech-man.com


Programming a 24 Point I/O Card, Continued

Programming an Input Device


(Two- or Three-Position
Switch) (continued)
Table 6-11. Input Modes (continued)

Mode Switch Type Circuit State and Result

USWITCH Not Applicable

OSWITCH Not Applicable

Programming Cards
SMPL Mode indicates that an
SMPL equation is being used to
program the switch. SSWITCH Not Applicable

TSWITCH Not Applicable

Open Toggles the disable/enable state of point


USWITCH
Normal Mode OFF.
Short Toggles the disable/enable state of point.
TDE Programs the switch to OSWITCH
toggle (reverse) the disable/enable Normal Mode OFF.
state of the point. This mode is Limited Toggles the disable/enable state of point.
intended for use with a 2-position SSWITCH
Normal Mode OFF
momentary switch.
Normal Mode OFF
TSWITCH Short Toggles the disable/enable state of point.
Limited Toggles the disable/enable state of point.

Open Toggles the ON/OFF state of the point.


USWITCH
Normal Mode OFF
Short Toggles the ON/OFF state of the point.
TOF -- Programs the switch to OSWITCH
toggle (reverse) the ON/OFF state Normal Mode OFF
of the point. This mode is intended Limited Toggles the ON/OFF state of the point.
for use with a 2-position momentary SSWITCH
Normal Mode OFF
switch.
Normal Mode OFF
TSWITCH Short Toggles the ON/OFF state of the point.
Limited Toggles the ON/OFF state of the point.

Continued on next page

6-35

Technical Manuals Online! - http://www.tech-man.com


Programming a 24 Point I/O Card, Continued

Programming an Output Point 1. Click on the Device Type field and select the GRAPHOUT device type.

2. Click on the point type field and select one of the following:

LAMP. Specifies that the output is an LED.


PIEZO. Specifies that the output is an audible piezo device. Piezo
beeps to indicate an alarm, and sounds a steady tone to indicate a
trouble or supervisory condition.
RELAY. Specifies that the output is a generic relay.
RRELAY. Specifies that the output is a relay that activates upon
ALARM and turns OFF upon reset.

3. Select the mode (operation) of the output. Refer to Table 6-15 for specific
information on the modes.

4. Click on the Ref Addr field and select the point used to trigger the output.

Table 6-15. Output Device Modes

Mode Application
DISABLE Output activates when the referenced point is
Disabled.
FIRE Output activates when the state of the referenced
point is in an ALARM condition.
LF Output activates when any ALARM condition occurs.
LS Output activates when a Supervisory condition occurs.
LT Output activates when a Trouble condition occurs.
OFF Output activates when the state of the referenced
point is OFF.
ON Output activates when the state of the referenced
point is OFF.
SMPL Output activates when a Custom Control equation
executes.
SUPERV Output activates when a Supervisory condition occurs
to the referenced point.
TROUBLE Output activates when a Trouble condition occurs to
the referenced point.

6-36

Technical Manuals Online! - http://www.tech-man.com


Programming an LCD Annunciator Card

Introduction The 4010 can use either of the following annunciators:

External Graphical LCD Annunciator contains LEDs that can be


programmed to monitor the state of specific points. This product is
available for international systems only.

LCD Annunciator contains LEDs that can be programmed to monitor the


state of specific points.

Step 1. Open the LCD Double click on the card icon that represents the annunciator. A screen similar
Annunciator Card Screen to the following appears. The names of the points differ if you are programming

Programming Cards
an External LCD Annunciator.

Figure 6-22. LCD Annunciator

Step 2. Programming The External LCD Annunciator contains push button switches that can be used
External Graphical LCD to control outputs. Programming these switches involves setting a device type,
Annunciator Switches point type, mode (operation for the switch), and reference point (the point
affected by the switches mode).

1. Click on the Device Type column to the right of the switch that you want to
program and select the LCDIN choice.

Continued on next page

6-37

Technical Manuals Online! - http://www.tech-man.com


Programming an LCD Annunciator Card, Continued

Step 2. Programming 2. Click on the Point Type column and select USWITCH (2-position,
External Graphical LCD unsupervised switch.
Annunciator Switches
(continued) 3. Click on the Mode and select the operation of the switch.

Table 6-16. Modes for External LCD Switches

Mode Application
ACK Programs the switch to acknowledge all alarms and
troubles.
DE Programs one switch position to disable the point and
another switch position to enable the point.
LFACK Programs the switch to acknowledge Fire Alarms.
LSR Programs the switch to perform a system reset.
LSS Programs the switch to perform a signal silence.
LTACK Programs the switch to acknowledge troubles.
LTEST Programs the switch to perform a lamp test.
ONOFF Programs one position of the switch to turn the point ON
and another switch position to turn the point OFF.
PBH Programs the switch to turn the point ON and hold it ON.
Point must be turned off by Custom Control or system
reset.
PBT Programs the referenced address to track the state of
the switch, turning ON when the switch is active and
turning OFF when the switch is inactive.
SMPL Indicates that an SMPL equation is being used to
program the switch.
TDE Programs the switch to toggle the Disable/Enable state
of the point.
TOF Programs the switch to toggle the ON/OFF state of the
point.

4. Click on the Ref. Addr field and select the point affected by the switch.

5. Use the Keyswitch checkboxes, located in the Access Levels panel of


Figure 6-22, if you want to require the use of a key to acknowledge Alarms,
Fire Alarms, Supervisory events, Trouble events, or System events.

Continued on next page

6-38

Technical Manuals Online! - http://www.tech-man.com


Programming an LCD Annunciator Card, Continued

Step 3. Programming LEDs Both the External Graphical LCD Annunciator and the LCD Annuciator contain
LEDs that can be used to monitor the state of a point, illuminating a specific
color when the state of the point is equal to a specific condition.

1. Click on the Device Type field corresponding to the LED that you want to
program and choose Multicolor.

2. Click on the Point Type field and choose one of the following. Note that
LED1 and LED2 illuminate Yellow or Red, whereas LED3 illuminates
either Yellow or Green.

Programming Cards
LED Available Point Types
LED 1 Select Yellow for a Yellow LED
Select Non Yellow for a Red LED
LED 2 Select Yellow for a Yellow LED
Select Non Yellow for a Red LED
LED 3 Select Yellow for a Yellow LED
Select Non Yellow for a Green LED

3. Click on the Mode drop down list box. Choose the mode (State) that must
be true to illuminate the LED. Refer to the following table for details on the
available modes.

Table 6-17. Modes for User-Defined LEDs

Mode Meaning
Disable LED illuminates when the state of the REF ADDR
(point) is DISABLED.
Fire LED illuminates when the state of the REF ADDR
(point) goes into ALARM
LF LED illuminates when the ALARM ACK button on the
panel is pushed.
LS LED illuminates when the SUPV ACK button on the
panel is pushed.
LT LED illuminates when the TROUBLE ACK button on
the panel is pushed.
OFF LED illuminates when the state of the REF ADDR
(point) is OFF.
ON LED illuminates when the state of the REF ADDR
(point) is ON
SMPL LED illuminates when the state of a Custom Control
equation(s) is TRUE.
SUPERV LED illuminates when the state of the REF ADDR
(point) goes into SUPERV.
TROUBLE LED illuminates when the state of the REF ADDR
(point) goes into ALARM

Continued on next page

6-39

Technical Manuals Online! - http://www.tech-man.com


Programming an LCD Annunciator Card, Continued

Step 3. Programming LEDs 4 Click on the Ref Address field and associate a point with the mode you set
(continued) in Step 3. The list that appears depends on the Mode selection. The Ref
Address list contains either physical points, pseudo points, list points, or no
entries.

Programming Events The Event Reporting panel of the LCD Annunciator card programming screen
allows you to select which events are reported at the annunciator.

Click on the check boxes that correspond to the events that should be routed to
the annunciator. The list is as follows:

Silence / Reset Events


SMPL Print Statements
Walk Test Events
Fire Alarm Events
Trouble Events
Supervisory Events

6-40

Technical Manuals Online! - http://www.tech-man.com


Chapter 7
Programming Points
Blank Page

Overview This chapter provides instructions for programming each points device type,
point type, and custom label.

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Overview Point Tab 7-2
Programming a Points Hardware Device Type 7-5
Programming a Points Software Point Type 7-8
Programming Custom Labels 7-11

Programming Points

7-1

Technical Manuals Online! - http://www.tech-man.com


Overview Point Tab

Introduction The Point Tab, shown in Figure 7-1, allows you to view all points in the system,
and to add and edit point information. This section describes the general
features AutoFill, Word Library, etc. of the Point Tab screen.

Splitter
Bar

Figure 7-1. Point Tab

Splitter Bar Use the Splitter Bar to adjust the size of the window containing points. Position
the cursor over the Splitter Bar, click and hold the mouse button, drag the bar to
its new position and release the mouse button.

Site, Card, and Point Views The View panel allows you to view points in three ways. Each view is selected
by clicking on the corresponding radio button in the View panel (top right
Figure 7-1).

Site View uses the site tree to display the points.


Card View breaks down the points by card, listing each cards points
beneath an icon that represents the card.
Point View allows you to see a listing of all points in the system, arranged
numerically.

Sort Order The Sort Order panel, located in the top right of Figure 7-1, allows you to
display points in ascending or descending numerical order. Use the two radio
buttons Ascending and Descending to set the sort order.

Word Library The Custom Label Suggestion box displays suggestions from the programmers
word library as you create custom labels. If you wish to insert the word
displayed in this box, press CTRL + F and the word is inserted in the correct
position in the custom label.

Continued on next page

7-2

Technical Manuals Online! - http://www.tech-man.com


Overview Point Tab, Continued

AutoFill AutoFill allows you to automatically add text to the Custom Label field. It is
possible to select either a single point, a range of adjoining points within the list,
or a group of non-adjoining points.

1. Enter the text that you want to automatically enter in the Custom Label
AutoFill text entry box.

2. Choose the points to which the text will be added, as follows:

Single Point. Click on the point to highlight it. Next, click on the
AutoFill button. The text is added to the Custom Label field of the
selected point.

Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range. Click on the
AutoFill button. The text is added to the Custom Label field for the
range of points.

Range of Non-Adjoining Points. Hold down the CTRL key and click
on the points. Each point highlights to show it is selected. When all
points have been selected, release the CTRL key and click on the
AutoFill button. The text is added to the Custom Label field for all of
the selected points.

Programming Points
Custom Label Spell Check Spell check allows you to validate the spelling of custom labels, and can be used
to check either selected points or all points.

1. Make sure Point View is selected.

2. Select the points to check as follows:

Single Point. Click on the Selected Points button in the Custom Label
Spell Check panel and click on the point to highlight it. Next, click on
the AutoFill button. The text is added to the Custom Label field of the
selected point.

Range of Adjoining Points. Click on the Selected Points button in the


Custom Label Spell Check panel and click on the first point in the
range. Hold down the shift key and click on the last point in the range.
Click on the AutoFill button. The text is added to the Custom Label
field for the range of points.

Range of Non-Adjoining Points. Click on the Selected Points button


in the Custom Label Spell Check panel and hold down the CTRL key
and click on the points. Each point highlights to show it is selected.
When all points have been selected, release the CTRL key and click on
the AutoFill button. The text is added to the Custom Label field for all
of the selected points.

All Points. Click on the All Points button in the Custom Label Spell
Check panel.

Continued on next page

7-3

Technical Manuals Online! - http://www.tech-man.com


Overview Point Tab, Continued

Custom Label Spell Check 3. Click on the rectangular Check button, located in the Custom Label Spell
(continued) Check panel.

Words that are not contained in the programmers dictionary are flagged by
the following dialog.

Figure 7-2. Spell Check Correction Dialog

4. Choose an option, as follows:

Change. Changes spelling of the highlighted word to the suggestion.


Ignore. Treats the word as correct for the one highlighted occurrence.
Change All. Changes all occurrences of the misspelled word to the
suggestion.
Ignore All. Treats all occurrences of the word as correctly spelled.
Add to User Dict. Inserts the word into the dictionary.

7-4

Technical Manuals Online! - http://www.tech-man.com


Programming a Points Hardware Device Type

Introduction A points hardware device type identifies the specific hardware device being
programmed. The programmer supports the following general categories of
hardware device type.

Each hardware device type corresponds to a specific Product ID (PID).


Appendix A of this manual lists the PIDs that apply to each device type.

Procedure 1. Move to the points device type field and double click with the left mouse
button.

A context-sensitive list of device types appears, meaning the list that


appears for an IDNet point is different from the list that appears for a NAC
point.

2. Click on the device type that is appropriate for the point being programmed.
Refer to Table 7-1 for quick reference information, or refer to Appendix A
for detailed information on the hardware device types.

Table 7-1. Device Types Quick Reference

Class Device Type Application


ADRDET Addressable Detector Base

Programming Points
Monitor ADRPUL Addressable Pull Station
CANPUL Canadian 2-stage Pull Station
ISO Communicating Line Powered
ISO
MAZAM Class A Monitor ZAM (T-sense)
MBZAM Class B Monitor ZAM (T-sense)

NAC SIGA Class A signal (1&2, 3&4 in pairs)


SIGB Class B signal (1&2, 3&4 in pairs)

Input INPUT Input


GRAPHIN Graphic I/O input

Output GRAPHOUT Graphic I/O output


OUTPUT Output

Relay RELAY Unsupervised Relay


RIAM Relay IAM

Continued on next page

7-5

Technical Manuals Online! - http://www.tech-man.com


Programming a Points Hardware Device Type, Continued

Procedure (continued)
Table 7-1. Device Types Quick Reference (continued)

Class Device Type Application


SSD Heat Heat
(Simplex IHEAT Heat with Isolator base
Smoke
IION Ion with Isolator base
Detector)
IOHEAT Rate of rise heat with isolator base
ION ION
IPHOTO Photo with Isolator
OHEAT Rate of rise heat
PHOTO Photo
RHEAT Heat with relay
RION ION with relay
ROHEAT Rate of rise heat with relay
RPHOTO Photo with relay
SHEAT Heat with sounder
SION ION with sounder
SOHEAT Rate of rise heat with sounder
SPHOTO Photo with sounder

IDNet 4009A 4009A with 4 NACs


4009A8 4009A with 8 NACs
R4009A 4009A 4 NACs with Repeater
R4009A8 4009A 8 NACs with Repeater
ADRPUL Addressable Pull Station
CANPUL Canadian 2-stage pull station
HEAT Heat Detector
IAM Line Power Sup. IAM with
TrueSense
IHEAT Heat Detector with Isolator
IION ION Detector with Isolator
IOHEAT TureAlarm Heat Detector with ROR
and Isolator
ION Ionization Detector
IPHOTO Photo with Isolator Base
KACPULL KAC Pull Station
MAZAM Class A Monitor ZAM (TrueSense)
MBZAM Class B Monitor ZAM (TrueSense)
OHEAT Heat Detector with ROR
PHOTO Photoelectric Detector
QIPHOTO Quick Connect Photo with Isolator
QPHOTO Quick Connect Photo
QRPHOTO Quick Connect Photo with relay

Continued on next page

7-6

Technical Manuals Online! - http://www.tech-man.com


Programming a Points Hardware Device Type, Continued

Procedure (continued)
Table 7-1. Device Types (continued)

Class Device Type Application


IDNet QSPHOTO Quick Connect Photo with sounder
RHEAT Heat detector with relay
RIAM Relay IAM
RION ION Detector with Relay
ROHEAT Heat Detector with ROR and Relay
RPHOTO Photo with Relay
SHEAT Heat Detector with sounder
SION Ion Detector with sounder
SOHEAT Heat Detector with ROR and
Sounder
SPHOTO Photo with sounder
XIPHOTO Extra-sensitive Photo ISO
XPHOTO Extra-sensitive Photo
XRPHOTO Extra-sensitive Photo with Relay
XSPHOTO Extra-sensitive Photo with
Sounder

Programming Points
Misc. ANALOG Analog Pseudo
Device COMNTBL Network Common Trouble
Types DIGTAL Digital Pseudo
DTMASTERIN Master Switch Input
DTMASTEROUT1 Master LED Output Red/Yellow
DTMASTEROUT2 Master LED Output Red/Green
LIST List
STATUS Status

7-7

Technical Manuals Online! - http://www.tech-man.com


Programming a Points Software Point Type

Introduction A point type determines the following:

The message displayed on the 4010s LCD when changes occur to the state
of the points circuit.

The way in which the system operates (for example, initiate an Alarm,
Trouble, or Supervisory action) when changes occur to the state of the
points circuit.

Example. Compare the FIRE Point type with the SO (normally open sprinkler
monitor) point type. When the circuit state of a point programmed with either type
is Normal, the system operates normally (i.e., no Alarm/Trouble/Supervisory
messages and no system action occurs).

Notice, however, that the operation of the system is different if a Current Limited
condition occurs. When a current limited condition occurs for a device associated
with the FIRE point type, the system displays Fire Monitor Zone on the LCD,
illuminates the FIRE LED, and triggers any automatic and custom Alarm response
(i.e., activate NACs, etc.). Contrast this with what happens when a current limited
condition occurs for a device associated with the SO point type. In this case, an
abnormal physical state exists. To have actions occur as a result of the sprinkler
monitors change in state, you would need to write a Custom Control equation that
monitors the point for this circuit state and then executes specific output actions if
an abnormal physical state occurs.

Circuit LCD Text System Operation


Status
Normal Normal
FIRE Limited Fire Monitor Zone Fire Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Fire Alarm
Normal Normal
SO Limited Sprinkler Monitor Abnormal
Open Sprinkler Monitor Open Trouble
Short Sprinkler Monitor Abnormal

Procedure Follow these steps to define a points software point type.

Note: Do not use the PC Programmer to change the point type of a suppression
release point; doing this causes the PC Programmer to change the point type
back to its default setting. To change the point type of a suppression release
point, you must use the front panel programmer.

1. Click on the point whose point type you want to program.

2. Move to the points Point Type field and double click with the left mouse
button.

3. Click on the appropriate point type. Refer to Table 7-2 for a quick
reference of the point types; refer to Appendix A for detailed descriptions of
the point types.

Continued on next page

7-8

Technical Manuals Online! - http://www.tech-man.com


Programming a Points Software Point Type, Continued

Procedure (continued)
Table 7-2. Point Types

Category Point Type Application


ABORT Abort zone (pre-signal)
DAMPER Damper Monitor (open/closed)
DUCT Duct Detector
EMERG Combination Fire/Emergency Alarm
FIRE Fire Alarm (Generic)
FLAME Flame Detector
FPUMP Fire Pump Monitor
GENMON Generator Monitor
GVMON Generic verified Monitor
HEAT Heat Detector
LATSUPV Latching Supervisory
PULL Manual Pull Station
S2STAGE 2-stage Monitor (abn=presignal;
short=alarm)
SDUCT Supervisory Duct Detector
SFIRE Combination Smoke Fire Zone
SFPUMP Supervisory Fire Pump Monitor
SGENMON Supervisory Generator Monitor

Programming Cards
SMOKE Smoke detector
SO Sprinkler supervisory (normally open)
Monitor SPULL Combination Smoke/Pull Zone
STYLEC Style C Monitor Point (current
limit=fire alarm; short/open=trouble)
SUPABRT Suppression release abort zone
SUPDET Suppression release detector zone
SUPDUMP Suppression release manual dump
SUPPRES Suppression release pressure monitor
SUPV Supervisory (generic)
TROUBLE Trouble Monitor
UTILITY Non-alarm utility with Tri-state ability
VSFIRE Verified Smoke/Fire Zone
VSMOKE Verified Smoke Zone
VSPULL Verified combination Smoke/Pull
Zone
WATER Waterflow Switch
WSO Waterflow Switch/Sprinkler
supervision (Normally Open)

Continued on next page

7-9

Technical Manuals Online! - http://www.tech-man.com


Programming a Points Software Point Type, Continued

Procedure (continued)
Table 7-2. Point Types (continued)

Category Point Type Application


AHUF AHU OFF Relay (Dual Relay
Control)
AHUO AHU ON Relay (Dual Relay
Control)
AHUR AHU ON/OFF Relay (Signal
Relay control)
ALTERN Alternate Elevator Capture
BSIGNAL Trouble/Supervisory Bell Signal
(on until ACK)
Control DHOLDER Door Holder Control
PRIMARY Primary Elevator Capture
RELAY Generic Relay
RSIGNAL Alarm Signal (on until reset)
RVISUAL Visual (on until reset)
RWATER Waterflow Signal (on until reset)
SIGNAL Generic Signal (no default
operation)
SSIGNAL Alarm Signal (on until silence)
SUPREL Suppression (Agent Discharge)
Release Output
SUPV Sprinkler Supervisory Signal (on
until ACK)

LAMP Lamp Output


OSWITCH 2-position switch (open,
supervised)
PIEZO Piezo output
24 Point I/O RELAY Generic Relay
RRELAY Relay (on until reset)
SSWITCH 2-position switch (open/short
supervised)
TSWITCH 3-position switch (open,
supervised)
USWITCH 2-position switch (unsupervised)

7-10

Technical Manuals Online! - http://www.tech-man.com


Programming Custom Labels

Introduction Custom Labels provide a means of adding custom text descriptions to a points
Custom Label field.

Procedure 1. Click on the point whose label you want to program.

2. Move to the points Custom Label field and double click with the left
mouse button.
A flashing cursor appears, indicating that you should enter text.

3. Edit the label. Refer to Overview at the beginning of this chapter for
information on using the AutoFill feature to automatically add text to the
Custom Label field.

Programming Points

7-11

Technical Manuals Online! - http://www.tech-man.com


This page blank

Technical Manuals Online! - http://www.tech-man.com


Chapter 8
Programming Lists

Introduction This chapter describes editing the name of a list, and adding or deleting points
from a list.

In this Chapter Refer to the following page for specific information on a topic.

Topic See Page #


Overview List Tab 8-2
Naming Lists and Adding/Deleting Points 8-4

Programming Lists

8-1

Technical Manuals Online! - http://www.tech-man.com


Overview List Tab

Accessing the List Tab The List Tab allows you to build or edit lists. Click on the List Tab at the top of
the screen to display the list-editing window.

Figure 8-1. List Tab, Showing List Editing Window

The system maintains the following lists:

Lists 1 through 3 use a pre-assigned label and are auto-generated by the


programmer.

Lists 4 through 7 use a pre-assigned label but are not auto-generated.

Lists 8 through 12. These are lists containing suppression release points.

Lists 26 through 50 are available for user-defined requirements.

Icons used within the Screen Three icons are used to show the status of a list. These icons appear to the left
of the lists number.

A page represents a list that contains no points.


A book represents a list containing points.
An open book represents an open list, and displays the contents of the list
immediately below the open book icon.

Continued on next page

8-2

Technical Manuals Online! - http://www.tech-man.com


Overview List Tab, Continued

Sorting the Point Display The right side of the List window contains the points that can be added to
system and user-defined lists. You can sort and filter this list as follows:

1. Click on the View button. A dialog similar to the following appears.

Figure 8-2. Point Display Filter

2. Select the Sort/Filter options as follows:

a. Change the view to a Site-, Card-, or Point-specific view by clicking on


the appropriate radio button in the View panel. Site View shows a list
of the points grouped by site information. Card View organizes the
points according to which card they are associated with. Point View is
the default view. It displays a numerical list of all points.

b. Choose Ascending or Descending order. Ascending order lists the


points from highest number to lowest and descending lists the points
from lowest to highest.

c. Click on the Device drop down list box. This selection allows you to

Programming Lists
display only points with a specific device type. Choose All to see all
points.

d. Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.

8-3

Technical Manuals Online! - http://www.tech-man.com


Naming Lists and Adding/Deleting Points

Naming a List Use the following procedure to edit the name of any user-defined list. (Note that
you cannot change the name of system-defined lists.)

1. Double click on the Description field to the right of the list number that you
want to define.

2. Edit the text as appropriate.

Adding Points Points contained on the right hand side of the List window are added to a list as
follows:

1. Highlight the points that you want to add to the list.

Single Point. Click on the point to highlight it.

Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range.

Range of Non-Adjoining Points. Hold down the CTRL key while


clicking on each point. Each point highlights to show it is selected.
When all points have been selected, release the CTRL key.

2. Hold down the left mouse button and drag the points into the list area.
While continuing to hold down the mouse button, position the cursor
directly over the list to which you want to add the points and release the
mouse button.

Deleting Points Delete points from a list, as follows:

1. Click on the + sign in the box to the left of the book that represents the list
from which you want to delete points.

2. Select the points to delete, as follows:

Single Point. Click on the point to highlight it.

Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range.

Range of Non-Adjoining Points. Hold down the CTRL key while


clicking on each point. Each point highlights to show it is selected.
When all points have been selected, release the CTRL key.

3. Press the Delete key, or hold down the right mouse button and select the
Delete option.

8-4

Technical Manuals Online! - http://www.tech-man.com


Chapter 9
Creating a Site Tree

Creating a Site Tree


Introduction This chapter describes creating a site tree, which is a tree-like representation of
your building and its fire alarm points.

In this Chapter The remainder of this chapter discusses the following topics:

Topic See Page #


Overview 9-2
Building a Site Tree 9-5

9-1

Technical Manuals Online! - http://www.tech-man.com


Overview

Introduction A site tree allows you to create labels for specific, physical areas of a building
and assign fire alarm points to these labels. When complete, a site tree
graphically depicts the layout of the site and gives an indication of every points
location within the site.

A site tree reads from left to right, with general divisions of the site (such as
Building A or West Wing) listed on the left side and specific areas of the site
(such as R&D lab or Boiler) listed on the right side. Points are listed on the far
right of the tree and are the smallest unit that can be added to a site tree.

Figure 9-1 shows a typical site tree.

Figure 9-1. Typical Site Tree

Terms and Concepts Important terms and concepts related to a site tree include:

Book icons represents element of the tree that contain subordinate elements.
In Figure 9-1, for example, the 1ST FLOOR book indicates that some
number of building components (either points or smaller divisions of the
building) are contained within it. A plus (+) sign to the left of a closed book
indicates that the contents of the element are not currently displayed.
Conversely, a minus (-) sign to the left of an open book indicates that the
contents of the element are currently displayed.

A page icon represents an element of the tree that contains no subordinate


elements. Points, which are the smallest division of a site tree, are always
represented by a page.

Continued on next page

9-2

Technical Manuals Online! - http://www.tech-man.com


Overview, Continued

Creating a Site Tree


Terms and Concepts The terms Level and Leaf are used when inserting components into the site
(continued) tree. These are relative terms used to indicate where an element will be
inserted in relation to the currently highlighted element. A level indicates
that the new element will be added at a level equal to the selected element,
whereas leaf indicates that the new element is subordinate to the highlighted
element. In Figure 9-1, for example, the highlight is on OFFICE 2.
Inserting a Level would add an element equal to OFFICE 2. Inserting a
Leaf would add an element that is subordinate to OFFICE 2.

The Site Tab Selecting the Site Tab displays a window similar to the one shown in Figure 9-2.
The left side of the window is the area in which the site tree is created. The
right side of the window lists the points that can be added to the site tree.

Figure 9-2. Site Tab Window

Use the View button shown at the top of the points list to change, filter,
and sort the way in which points are displayed in the list. You can sort and filter
the Points list as follows:

1. Click on the View button. A dialog similar to the one shown in Figure 9-3
appears.

Continued on next page

9-3

Technical Manuals Online! - http://www.tech-man.com


Overview, Continued

The Site Tab (continued)

Figure 9-3

2. Select the Sort/Filter options as follows:

a. Change the view to a Site-, Card-, or Point-specific view by clicking on


the appropriate radio button in the View panel. Site view shows a list
of the points grouped by the Site information. Card View organizes the
points according to which card they are associated with. Point View is
the default view. It displays a numerical list of all points.

b. Choose Ascending or Descending order. Ascending order lists the


points from highest number to lowest and descending lists the points
from lowest to highest.

c. Click on the Device drop down list box. This selection allows you to
display only points with a specific device type. Choose All to see all
points.

d. Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.

9-4

Technical Manuals Online! - http://www.tech-man.com


Building a Site Tree

Creating a Site Tree


Introduction It is helpful to identify the major components of the site before you begin to
create the site tree. At a minimum, you probably want to include entries for
each of the following in the tree.

Each building
Each floor within the building
Each component (office, lab, hallway, duct, etc.) of each floor that contains
points

Step 1. Add the Buildings 1. Right click on the blank portion of the Site screen. When the list of choices
appears, select Insert Level.

An entry, containing a Page icon and the word *Level*, appears.

2. Double click on *Level* and type the building name in the text entry box.
The name must be 10 characters or less.

3. To add an additional building, right click on the entry that you just added
(the building ) and select Insert Level.

Insert Level adds an element to the tree that is equal to the currently
selected element. In this case, another entry that is equal to the building.

4. Double click on *Level* and type a building name.

Step 2. Add Floors Add floors to the building, as follows:

1. Right click on the entry that represents a building. When the list of choices
appears, click on Insert Leaf.

An entry, containing a Page icon and the word *Leaf*, appears. This entry
is indented to the right of the building entry.

2. Double click on *Leaf* and enter the name of the floor. The text
description must be 10 characters or less.

Repeat Steps 3 and 4, highlighting the icons for other buildings as necessary, to
add all other floors.

Continued on next page

9-5

Technical Manuals Online! - http://www.tech-man.com


Building a Site Tree, Continued

Step 3. Add Floor Floor components such as offices, hallways, ducts, etc. are added by first
Components selecting the floor to which you want to add the components and then selecting
Insert Leaf, as follows:

1. Double click on the floor to which you want to add components. A menu of
options appears.

2. Choose Insert Leaf.

A line containing a page icon, followed by the label *Leaf*, appears. This
line is beneath and to the right of the highlighted floor.

3. Double click on *Leaf*. Enter a name for the floor in the text entry box.
The name must be 10 characters or less.

Repeat these steps, choosing different floors as required, to add other floor
components.

Step 4. Add Points Points are added to the tree as follows:

1. Move to the list of points on the right side of the screen. Click on the point.
A page icon, containing a + sign appears.

2. Drag the point into the site tree, positioning it over the floor component to
which it should be added.

3. Release the mouse button. The point is added to the floor component.

Repeat these steps until all points are added to the site tree.

9-6

Technical Manuals Online! - http://www.tech-man.com


Chapter 10
Creating Custom Control Equations

Introduction This chapter provides an overview of the Simplex Multi-functional


Programming Language (SMPL), also known as Custom Control, and describes
using the PC Programmer application to program Custom Control equations.

In this Chapter The remainder of this chapter discusses the following topics:

Topic See Page #

Custom Control
Overview CC Tab 10-2
Overview Components of a CC Equation 10-4
Step 1. Add a New Equation to the User Program 10-6
Step 2. Add Additional Inputs and Outputs to an 10-7
Equation
Step 3. Edit Each Input Statements Properties 10-8
Step 4. Edit an Output Statements Properties 10-19

10-1

Technical Manuals Online! - http://www.tech-man.com


Overview CC Tab

CC Tab The CC Tab, shown in Figure 10-1, provides a graphical means of adding and
editing custom control equations. Points appear in a list on the right side of the
CC window and equations appear on the left side of the window.

Figure 10-1. CC Tab

Use the View button shown at the top of the points list to change, filter,
and sort the way in which points are displayed in the list. You can sort and filter
the Points list as follows:

1. Click on the View button. A dialog similar to the one shown in Figure 10-2
appears.

Figure 10-2. Point Display Filter

Continued on next page

10-2

Technical Manuals Online! - http://www.tech-man.com


Overview CC Tab, Continued

CC Tab (continued) 2. Select the Sort/Filter options as follows:

a. Change the view to a Site-, Card-, or Point-specific view by clicking on


the appropriate radio button in the View panel. Site View shows a list
of the points grouped by the site information. Card View organizes the
points according to which card they are associated with. Point View is
the default view. It displays a numerical list of all points.

b. Choose Ascending or Descending order. Ascending order lists the


points from highest number to lowest and descending lists the points
from lowest to highest.

Custom Control
c. Click on the Device drop down list box. This selection allows you to
display only points with a specific device type. Choose All to see all
points.

d. Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.

10-3

Technical Manuals Online! - http://www.tech-man.com


Overview Components of a CC Equation

Introduction Up to 60 Custom Control equations can be programmed for the 4010. Each
equation consists of two sides: an INPUT SIDE, containing one or more Input
Statements and an OUTPUT SIDE, containing one or more Output Statements.
The total number of statements, both input and output must be 6 or less.

An equation can be better understood as an IF/THEN command. IF the


INPUT SIDE is true, THEN execute the OUTPUT SIDE.

Input Statement
Input Statement
Equation End of Inputs

Output Statement
Output Statement
End of Outputs

Figure 10-3. Example Equation

Input Statements Input Statements can do either of the following:

Monitor the status of a point, set of points, or list.

Perform a function, such as Delay, Cycle, Compare two values, or


Save/Recall values.

Multiple input statements, located within the same equation, must be separated
by a logical operator (AND or OR). These operators function as follows:

AND Operator. Use the AND Logical operator to link the current input
statement in Series with all previous input statements in an equation. In the
example below, IF the condition of M1-1 is Fire AND the condition of M1-
2 is Fire, then the INPUT SIDE is true and the Output statements (not
shown) execute. If, however, only M1-1 or M1-2 (not both) is in a Fire
state, the INPUT side is not true and the output statements do not execute.

Continued on next page

10-4

Technical Manuals Online! - http://www.tech-man.com


Overview Components of a CC Equation, Continued

Input Statements (continued) OR Operator. The OR Logical operator links the current statement in
Parallel with all previous statements in an equation. In the example below,
IF the condition of M1-1 is Fire OR the condition of M1-2 is Fire, then the
INPUT SIDE is true. In other words, when the status of either M1-1 or M1-
2 becomes Fire, the output statements execute.

Custom Control
Output Statements Output statements are the actions that occur when the INPUT Side of an
equation is true. An output consists of an Opcode, the point associated with the
Opcode, and a priority.

10-5

Technical Manuals Online! - http://www.tech-man.com


Step 1. Add a New Equation to the User Program

Procedure All user-defined CC equations are stored within the User Program, which is
represented by an icon on the left side of the screen. Follow these steps to add a
new equation to the User Program.

1. Right click on the User icon. See Figure 10-4 for its location.

2. Highlight Add Equation and click the left mouse button.

An entry similar to the following appears beneath the user program.

Figure 10-4. Adding an Equation

10-6

Technical Manuals Online! - http://www.tech-man.com


Step 2. Add Additional Inputs and Outputs to an Equation

Introduction Each equation can have up to 6 inputs or outputs in it. Follow these steps to add
additional inputs/outputs to the equation. If the equation appears as a book with
a plus (+) sign to the left of it, click on the + sign to expand the equation.

Adding Additional Inputs 1. Highlight one of the equations existing input statements and click the right
mouse button.

2. Click on Add Input.

An additional input appears beneath the highlighted input statement.

Custom Control
Adding Additional Outputs 1. Highlight one of the equations existing output statements and click the
right mouse button.

2. Click on Add Output.

An additional output appears beneath the highlighted output statement.

10-7

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties

Introduction An inputs properties specify the behavior of the input (i.e. what operation or
function does the input perform). Properties also define how inputs function in
relation to other inputs. Input Properties are set through the Custom Control
Input dialog. Follow these steps to open this dialog.

1. Highlight one of the equations input qualifiers and click the right mouse
button. A menu of choices appears.

2. Click on Properties. A dialog similar to Figure 10-5 appears.

Figure 10-5. Custom Control Input Dialog

3. Use the AND / OR logical operators to specify whether the input is in series
(AND radio button) or parallel (OR radio button) with all other inputs. If
the Equation has only a single input, skip this step.

4. Use the NOT Operator to specify that the condition must not be true for the
output to execute. In the following example, the input side of the equation
is true if the condition of M1-1 is Fire and the condition of M1-2 is NOT
fire.

5. Click on the Opcode and Qualifier list boxes and choose an Opcode and
qualifier. Refer to Table 10-1 for a list of Opcodes and qualifiers.

Continued on next page

10-8

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Associating Points with Input After defining the Opcode and Qualifier for an input statement, you need to
Statements associate a point with the statement. To do this, follow these steps.

1. In the list on the right side of the screen, click on the name of the point.

2. Hold down the left mouse button and drag the highlighted point from the
list to the appropriate Input Statement.

3. Release the mouse button.

Continued on next page

Custom Control

10-9

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers Table 10-1 lists the opcodes and their qualifiers and explains their use.

Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


When the referenced point (for example a smoke, flame,
heat detector) enters an alarm condition, the input condition
is TRUE for approximately second. Any NACs triggered
on the output side of the equation sound until signal
silence. Should another detector then sound, it would
Fire Detect trigger its NACs, allowing the fire condition to be tracked
from one area to another. This functionality is known as
resound.
Refer to the ANY opcode later in this table for information
on using Fire Detect with lists.
When the referenced point (either a pull station or detector
Fire type device) enters an alarm condition, the input condition
is TRUE until a System Reset is performed.
When the referenced point enters an alarm condition, the
Fire Ack
input condition is TRUE until the alarm is acknowledged.
When the referenced point enters a trouble condition, the
Point Status Trouble input condition is TRUE until the trouble condition is
Allows the status of acknowledged.
a specific point to be
tested for a specific When the referenced point enters a supervisory condition,
condition. the input condition is TRUE until the problem condition is
fixed.
Supervisory For example, turning a sprinkler system OS&Y valve
changes the state of the contacts being monitored and
triggers a Supervisory condition. Although this condition
can be acknowledged, the supervisory condition cannot be
cleared until the OS&Y is restored to its original position.
When the referenced point enters a supervisory condition,
the input condition is TRUE until the supervisory condition
is acknowledged. One way this qualifier might be used
would be to sound a bell in a control room when a point (a
list containing all waterflow points for example) enters a
Supervisory Ack supervisory condition. In this case, the bell would connect
to a relay that would be referenced on the output side of the
equation, and the input side of the equation would monitor
the list with the Supervisory ACK qualifier. The output (bell)
would turn off only when the supervisory condition is
acknowledged.

Continued on next page

10-10

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued) Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


When the referenced point enters a trouble condition, the
input condition is TRUE until the trouble condition is
Trouble Ack
acknowledged. Typically used in a similar way to the
Supervisory ACK qualifier.
The input condition is TRUE when the physical state of the
Physical Normal
referenced point is normal.

Custom Control
The input condition is TRUE when the physical state of the
referenced point is abnormal (current limited). One typical
use for this qualifier is to verify the physical location of a fire
in high-rise building. Once the location of the fire is
Physical Abnormal determined (i.e., locate the detectors with a Physical
Abnormal state), the output side of the equation can be
used to pressurize only the floor(s) with detectors in this
state, and ignore any pull stations (which may or may not
be on the fire floor).
The input condition is TRUE when the physical state of the
Physical Open
referenced point (or its wiring) is open.
The input condition is TRUE when the physical state of the
Point Status Physical Short
referenced point (or its wiring) is short.
Allows the status of
a specific point to be The input condition is TRUE when the state of the
Disable
tested for a specific referenced point is disabled.
condition.
The input condition is TRUE when the state of the
Class A Trouble
referenced point is a Class A Trouble.
The input condition is TRUE when a signal circuit (NAC) or
relay is ON or coding (i.e., sounding/flashing in march time,
ON / Coding
temporal, etc.). A typical use for this qualifier is to use the
relay or NAC as a switch for some other action.
The input condition is TRUE when a signal circuit (NAC) or
OFF
relay is OFF. Also used as a switch for some other action.
The input condition is TRUE when an IDNet sounder or
Control On
relay base is ON.
The input condition is TRUE when an IDNet sounder or
Control Off
relay base is OFF.
Input condition is TRUE when the average value for the
Dirty referenced point exceeds the fixed threshold (120 analog
units).
Input condition is TRUE if the referenced point is a list and
Empty
it is empty.

Continued on next page

10-11

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


When the referenced point enters an abnormal condition,
the input condition is TRUE for approximately second.
Abnormal Detect
Any NACs triggered on the output side of the equation
sound until signal silence.
Point Status
When an open condition occurs to the referenced point, or
Allows the status of
its circuit, the input condition is TRUE for approximately
a specific point to be Open Detect
second. Any NACs triggered on the output side of the
tested for a specific
equation sound until signal silence.
condition.
When a short condition occurs to the referenced point, or its
circuit, the input condition is TRUE for approximately
Short Detect
second. Any NACs triggered on the output side of the
equation sound until signal silence.

ANY Opcode. Input condition is TRUE for second if any


point within the list enters an alarm condition. Any NACs
triggered on the output side of the equation sound until
system silence. Should another detector then sound, it
would trigger its NACs, allowing the fire condition to be
tracked from one area to another. This functionality is
known as resound.

Fire Detect
ANY/ALL Used Using a list to implement resound allows a large number of
only with Lists. Note devices to be monitored by a limited number of equations.
that with the ANY Since the maximum number of equations is limited to 60,
Opcode you can lists provide an efficient way of implementing many system
specify how many features.
points within the list
must meet the ALL Opcode. Input condition is TRUE for second only if
criteria for the input ALL points within the list are in alarm.
condition to be true.
ANY Opcode. When any point within the list (pull stations
or detector type device) enters an alarm condition, the input
condition is TRUE until a System Reset is performed.

Fire
ALL Opcode. All devices within the list must enter an
alarm condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until a System Reset is
performed.

Continued on next page

10-12

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


ANY Opcode. When any point with the list enters a
supervisory condition, the input condition is TRUE until the
problem condition is fixed.
Supervisory
ALL Opcode. All devices within the list must enter an

Custom Control
supervisory condition for the input condition to be TRUE. If
this occurs, the input condition is TRUE until all problem
conditions are fixed.
ANY Opcode. When any point within the list enters an
alarm condition, the input condition is TRUE until the alarm
is acknowledged.
Fire Ack
ALL Opcode. All devices within the list must enter an
alarm condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until the alarms are
acknowledged.
ANY/ALL Used ANY Opcode. When any point with the list enters a
only with Lists. Note supervisory condition, the input condition is TRUE until the
that with the ANY problem condition is fixed.
Opcode you can
Supervisory
specify how many ALL Opcode. All devices within the list must enter an
points within the list supervisory condition for the input condition to be TRUE. If
must meet the this occurs, the input condition is TRUE until all problem
criteria for the input conditions are fixed.
condition to be true.
ANY Opcode. When any point within the list enters a
trouble condition, the input condition is TRUE until the
trouble condition is fixed.
Trouble
ALL Opcode. All devices within the list must enter a
trouble condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until all trouble conditions are
fixed.
ANY Opcode. When any point within the list enters a
supervisory condition, the input condition is TRUE until the
supervisory condition is acknowledged.
Supervisory Ack
ALL Opcode. All devices within the list must enter a
supervisory condition for the input condition to be TRUE. If
this occurs, the condition is TRUE until all alarms are
acknowledged.

Continued on next page

10-13

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application

ANY Opcode. When any point within the list enters a


trouble condition, the input condition is TRUE until the
troubles are acknowledged.
Trouble Ack
ALL Opcode. All devices within the list must enter a
trouble condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until all troubles are
acknowledged.

ANY Opcode. The input condition is TRUE when the


physical state of any point within the list is normal.
Physical Normal
ALL Opcode. The input condition is TRUE when the
physical state of all points within the list is normal.
ANY Opcode. The input condition is TRUE when the
ANY/ALL Used
physical state of any point within the list is abnormal
only with Lists. Note
(current limited). One typical use for this qualifier is to
that with the ANY
verify the physical location of a fire in high-rise building.
Opcode you can
Once the location of the fire is determined (i.e., locate the
specify how many
detectors with a Physical Abnormal state), the output side
points within the list
Physical Abnormal of the equation can be used to pressurize only the floor(s)
must meet the
with detectors in this state, and ignore any pull stations that
criteria for the input
may have been pulled (and may or may not be on the fire
condition to be true.
floor).

ALL Opcode. The state of all devices within the list must
be Physical Abnormal for the input condition to be TRUE.
Physical Open ANY Opcode. The input condition is TRUE when the
physical state of any point within the list (or any points
wiring) is open.
ALL Opcode. The circuit state of all devices within the list
must be open for the input condition to be TRUE
Physical Short ANY Opcode. The input condition is TRUE when the
physical state of any point within the list (or any points
wiring) is shorted.
ALL Opcode. The circuit state of all devices within the list
must be shorted for the input condition to be TRUE

Continued on next page

10-14

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


ANY Opcode. The input condition is TRUE when any point
within the list is disabled.
Disable
ALL Opcode. All points within the list must be disabled for
the input condition to be TRUE.

Custom Control
ANY Opcode. The input condition is TRUE when any
signal circuit (NAC) or relay within a list is ON or coding
(i.e., sounding/flashing in march time, temporal, etc.). A
On/Coding typical use for this qualifier is to use the relay or NAC as a
switch for some other action.
ALL Opcode. All signal circuits or NACs within the list
ANY / ALL Used must be ON or coding for the input condition to be TRUE.
only with Lists. Note
that with the ANY ANY Opcode. Used to override any programming in the
Opcode you can system. Typically used by inspectors to override
specify how many programming that triggers signals, elevator capture, door
points within the list drop, etc. The input condition is TRUE if any point within
must meet the the list is ON.
On Input
criteria for the input All Opcode. Used to override any programming in the
condition to be true. system. Typically used by inspectors to override
programming that triggers signals, elevator capture, door
drop, etc. The input condition is TRUE if all points within
the list are ON.
Any Opcode. The input is TRUE if any point within the list
has been manually overridden (i.e., controlled from the
panel).
Manual Override
All Opcode. The input is TRUE if all points within the list
have been manually overridden (i.e., controlled from the
panel).

Allows the Custom Control input condition to set a delay


Constant
equal to a constant value.
Allows the Custom Control input condition to reference a
Delay value contained in an analog pseudo point. This value can
Variable
periodically change, allowing the amount of delay to
change as required by the application.

Continued on next page

10-15

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued) Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


Allows the Custom Control output condition to periodically
execute. The frequency at which the statement executes is
Constant determined by the value of the constant. For example, the
output side of the equation could periodically (every 15
minutes for example) turn a heat pump on if necessary.
Cycle Allows the Custom Control input condition to periodically
execute. The frequency at which the statement executes is
determined by the value of an analog pseudo point. This
Variable
analog value can periodically change, allowing the
frequency of the cycle to change as required by the
application.

Allows a time value (for example, an analog pseudo point


timer) to be compared against a constant value (threshold).
Seconds (constant) This allows some output to be executed as the threshold is
approached (less than), met (equal to), or exceeded
(greater than).
Allows a counter (for example, an analog pseudo point
counter) to be compared against a constant value
Counts (constant) (threshold). This allows some output to be executed as the
Compare threshold is approached (less than), met (equal to), or
exceeded (greater than).
Allows a variable counter (an analog pseudo point counter)
to be compared against another variable counter (another
analog pseudo point counter used as a threshold). This
Counts (variable)
allows some output to be executed as the threshold is
approached (less than), met (equal to), or exceeded
(greater than).

SAVE. Allows an input condition to be evaluated and its


result stored in a register as a 1 (true) or 0 (false). There
are six registers available for use.
Save/Recall
Save/Recall RECALL. Allows an input to recall the value of a register
Register #
and use it beside other input conditions. If the recalled
value is false, it prevents the input from being TRUE. If the
recalled value is true (and all other parts of the input are
TRUE), the input condition is TRUE.

Continued on next page

10-16

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued) Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


Smoke level 0.5 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 0.5 %.
Smoke level 1.0 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 1.0 %.
PHOTO Smoke
Level Smoke level 1.5 Input condition is TRUE when the smoke level for the

Custom Control
referenced photo smoke detector exceeds 1.5 %.
Smoke level 2.0 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 2.0 %.
Smoke level 2.5 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 2.5 %.
Smoke level 3.0 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 3.0 %.
Smoke level 3.7 Input condition is TRUE when the smoke level for the
referenced photo smoke detector exceeds 3.7 %.

Smoke level 0.5 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 0.5 %.
ION Smoke Level
Smoke level 0.9 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 0.9 %.
Smoke level 1.3 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 1.3 %.
Smoke level 1.7 Input statement is TRUE when the smoke level for the
referenced ion smoke detector exceeds 1.7 %.

Smoke level 0.2 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
XPHOTO Smoke 0.2 %.
Level
Smoke level 0.5 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
0.5 %.
Smoke level 1.0 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
1.0 %.
Smoke level 1.5 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
1.5 %.

Continued on next page

10-17

Technical Manuals Online! - http://www.tech-man.com


Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers

Opcode Qualifier Application


Smoke level 2.0 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
2.0 %.

XPHOTO Smoke Smoke level 2.5 Input statement is TRUE when the smoke level for the
Level referenced extra-sensitive photo smoke detector exceeds
2.5 %.
Smoke level 3.7 Input statement is TRUE when the smoke level for the
referenced extra-sensitive photo smoke detector exceeds
3.7 %.

10-18

Technical Manuals Online! - http://www.tech-man.com


Step 4. Edit Each Output Statements Properties

Procedure An outputs properties specify what occurs (for example, a limited set of
strobes/horns activate) when the Input Side of the CC Equation is True. Output
Properties are set through the Custom Control output dialog. Follow these steps
to open this dialog.

1. Highlight one of the equations output qualifiers and click the right mouse
button. A menu of choices appears.

2. Click on Properties. A dialog similar to the following appears.

Custom Control
Figure 10-6. Custom Control Output Dialog

3. Use Table 10-2 to set the Opcode and Qualifier.

Table 10-2. Output Opcodes and Qualifiers

Opcode Qualifier Application


ON When the input side of the equation is true, Hold ON turns
the referenced output point ON. The output remains ON
until another equation turns the output OFF or the system is
reset. List L7 (Control Points, Off with Reset) is useful for
Hold turning OFF a number of points simultaneously.
OFF When the input side of the equation is true, Hold OFF turns
the referenced output point OFF. The output point remains
OFF until another equation turns the output point ON or the
system is reset.

Continued on next page

10-19

Technical Manuals Online! - http://www.tech-man.com


Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)
Table 10-2. Output Opcodes and Qualifiers (continued)

Opcode Qualifier Application


PRI When the input side of the equation is true, the priority is
reset to the value specified until a system reset is
performed.
Slow March Time When the input side of the equation is true, the output
cycles at 20 beats per minute (bpm) until a system reset is
performed.
Hold Fast March Time When the input side of the equation is true, the output
cycles at 120 beats per minute (bpm) until a system reset is
performed.
Temporal When the input side of the equation is true, the output
pattern consists of three second pulses, each separated
by second of silence. Each group of three cycles is
separated by 1.5 seconds of silence. The output cycles
until a system reset is performed.

ON When the input side of the equation is true, the output turns
ON. When the input is false, the output turns OFF.
OFF When the input side of the equation is true, the output turns
Track OFF. When the input is false, the output turns ON.
PRI When the input side of the equation is true, the priority is
changed to a value that you specify. When the input is
false, the priority returns to its original value.

On When the input side of the equation is True, Set turns the
point referenced on the output side of the equation ON.
The point stays ON until a Set OFF command occurs.
OFF When the input side of the equation is True, Set turns the
Set point referenced on the output side of the equation OFF.
The point stays OFF until a Set ON command occurs.
PRI When the input side of the equation is True, Set turns the
point referenced on the output side of the equation ON.
The point stays ON until a Set OFF command occurs.

On When the input side of the equation is true, the


enable/disable state of the point is set to ON, which
disables the point.
Enable/Disable
OFF When the input side of the equation is true, the
enable/disable state of the point is set to OFF, which
enables the point.

Continued on next page

10-20

Technical Manuals Online! - http://www.tech-man.com


Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)

Table 10-2. Output Opcodes and Qualifiers (continued)

Opcode Qualifier Application


Constant When the input side of the equation is true, the value of an
Set Analog Value analog pseudo point is set to a constant value.
Variable When the input side of the equation is true, the value of an
analog pseudo point is set to a variable value.

Custom Control
Constant When the input side of the equation is true, the referenced
Pulse point pulses for the specified amount of time (constant
value).
Variable When the input side of the equation is true, the referenced
point pulses for the specified amount of time (variable).

ON When the input side of the equation is true, the referenced


LED is turned ON. Note you must use LED OFF to turn the
LED OFF.
LED
OFF When the input side of the equation is true, the referenced
LED is turned OFF.
Slow When the input side of the equation is true, the referenced
LED flashes Slow.
Fast When the input side of the equation is true, the referenced
LED flashes Fast.

Print All Ports / Displays Prints a message to the referenced ports/displays.

ON When the input side of the equation is true, all devices on


the IDNet channel are turned ON. Note that this includes
all relays, door holders, etc.
Channel Code
OFF When the input side of the equation is true, all devices on
the IDNet channel are turned OFF. Note that this includes
all relays, door holders, etc.
Fast March Time When the input side of the equation is true, all devices on
the IDNet channel turn on and off in fast march time.
Temporal When the input side of the equation is true, all devices on
the IDNet channel turn on and off in a temporal pattern.
March Time When the input side of the equation is true, all devices on
the IDNet channel turn on and off in standard march time.

Continued on next page

10-21

Technical Manuals Online! - http://www.tech-man.com


Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)
Table 10-2. Output Opcodes and Qualifiers (continued)

Opcode Qualifier Application


Smoke Level 0.5 When the input side of the equation is true, the threshold
level for the photo smoke detector is set to 0.5.
Smoke Level 1.0 When the input side of the equation is true, the threshold
level for the photo smoke detector is set to 1.0.
Set Photo Smoke Level 1.5 When the input side of the equation is true, the threshold
Threshold level for the photo smoke detector is set to 1.5.
Smoke Level 2.0 When the input side of the equation is true, the threshold
level for the photo smoke detector is set to 2.0.
Smoke Level 2.5 When the input side of the equation is true, the threshold
level for the photo smoke detector is set to 2.5.

117 Fahrenheit When the input side of the equation is true, the threshold
level for the heat detector is set to 117 degrees F.
135 Fahrenheit When the input side of the equation is true, the threshold
Set Heat Threshold
level for the heat detector is set to 135 degrees F.
155 Fahrenheit When the input side of the equation is true, the threshold
level for the heat detector is set to 155 degrees F.

3 C / minute When the input side of the equation is true, the threshold
level for the ROR heat detector is set to 3 C / minute.
15 F / minute When the input side of the equation is true, the threshold
Set ROR
level for the ROR heat detector is set to 15 C / minute.
20 F / minute When the input side of the equation is true, the threshold
level for the ROR heat detector is set to 20 C / minute.

Smoke Level 0.5 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 0.5.
Smoke Level 0.9 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 0.9.
Set ION Threshold
Smoke Level 1.3 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 1.3.
Smoke Level 1.7 When the input side of the equation is true, the threshold
level for the ION smoke detector is set to 1.7.

Continued on next page

10-22

Technical Manuals Online! - http://www.tech-man.com


Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)
(continued) Table 10-2. Output Opcodes and Qualifiers (continued)

Opcode Qualifier Application


When the input side of the equation is true, the threshold
Smoke Level 0.2 level for the extra-sensitive photo smoke detector is set to
0.2.
When the input side of the equation is true, the threshold
Smoke Level 0.5 level for the extra-sensitive photo smoke detector is set to
0.5.

Custom Control
Set XPHOTO When the input side of the equation is true, the threshold
Threshold Smoke Level 1.0 level for the extra-sensitive photo smoke detector is set to
1.0.
When the input side of the equation is true, the threshold
Smoke Level 1.5 level for the extra-sensitive photo smoke detector is set to
1.5.
When the input side of the equation is true, the threshold
Smoke Level 2.0 level for the extra-sensitive photo smoke detector is set to
2.0.

Used with TrueAlert Non-Addressable Horns. When the


HORN OFF input side of the equation is true, Horn OFF turns TrueAlert
Non-Addressable horns off.

Associating Points with After defining the Opcode and Qualifier for an output statement, you need to
Output Statements associate a point with the statement. To do this, follow these steps.

1. In the list on the right side of the screen, click on the name of the point.

2. Hold down the left mouse button and drag the highlighted point from the
list to the appropriate output Statement.

3. Release the mouse button.

10-23

Technical Manuals Online! - http://www.tech-man.com


White text

Technical Manuals Online! - http://www.tech-man.com


Chapter 11
Building and Downloading a Job

Introduction This chapter describes building a 4010 job and downloading it to the 4010 panel.

In this Chapter The remainder of this chapter discusses the following topics:

Topic See Page #


Building a Job 11-2
Downloading a CFG File to the Panel 11-3

Building/Downloading Jobs

11-1

Technical Manuals Online! - http://www.tech-man.com


Building a Job

Introduction This section describes using the PC Programmers Job Builder utility to create a
Configuration Data file (CFIG), and download it to the 4010 FACP.

Using Job Builder The Job Builder utility does the following:

Automatically saves the job being built.


Verifies that the hardware and the configured points are accurate.
Produce the CFG file.

To build a job, follow these steps:

1. Click on the Build menu and choose the Build option.

The Job Builder dialog appears, displaying the progress of the job build in
the window.

2. Click on OK when the job is finished building.

Figure 11-1. Job Builder Dialog

11-2

Technical Manuals Online! - http://www.tech-man.com


Downloading a CFG File to the Panel

Introduction This section describes downloading a CFG file (built job file) from a service PC
to the 4010 FACP. A download occurs over a serial link running between the
panel and the PC. Follow the steps outlined in the following sections to link the
PC to the panel and download the job.

Step 1. Set Panel and PC 1. Set switches SW1 and SW2 to the positions shown in Figure 11-2. These
Serial Communication positions enable a baud rate of 19,200 on the 4010 FACP.
Parameters

Black indicates switch position

19,200

Figure 11-2. Switch Position for 19,200 Baud

Building/Downloading Jobs
2. Start the 4010 Programmer application.

Click on the Transfer menu and select Settings.

A dialog similar to the one shown in Figure 11-3 appears.

Figure 11-3. Setting PC Transfer Rate to 19,200

3. Set the parameters in this dialog as follows:

Port. Set this radio button to the setting that corresponds to the serial
port on the PC to which the serial cable will be connected. In most
cases, this will be COM1.
Baud Rate. Set to 19,200.
Parity. Set to None.
Stop Bits. Set to 1.
Data Bits. Set to 8.

Continued on next page

11-3

Technical Manuals Online! - http://www.tech-man.com


Downloading a CFG File to the Panel, Continued

Step 2. Connect Serial Cable Connect a 733-794 serial cable between a free serial port on the service PC and
between PC and Panel the service port of the 4010 FACP.

1. Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 11-4 to the PC.

2. Connect the other end to the service port on the 4010 FACP. Make sure that
the red stripe is aligned to the left as you connect the cable.

Align Red Stripe


to the Left

9-Pin Connector
goes to PC

Figure 11-4. Connecting Serial Cable

Step 3. Enable Download on 1. Login to the 4010 at Access Level 4.


Panel 2. Press <MENU>.
3. Press <NEXT> until [UPLOAD/DOWNLOAD] is displayed.

<ENTER> to Accept <NEXT/PREV to Scroll


Menu: [Upload/Download]

4. Press <ENTER>. A screen similar to the following appears.

<ENTER> to Accept <NEXT/PREV> to Scroll


Prog. Interface: [Initialize Up/Dwnload]

5. Press the <NEXT> or <PREV> keys until [Initialize Up/Dwnload] is


displayed and press <ENTER>.

Continued on next page

11-4

Technical Manuals Online! - http://www.tech-man.com


Downloading a CFG File to the Panel, Continued

Step 3. Enable Download on The 4010 displays the following message to indicate that the panel is ready to
Panel (continued) accept a download.

*** File Transfer Initialized ***


*** Check Programming Unit **

Step 4. Start Download at PC 1. Click on the Transfer menu. When the selections appear, choose Transfer.
A window similar to the one shown in Figure 11-5 appears.

Building/Downloading Jobs
Figure 11-5. Upload/Download Dialog
2. Select the following radio button options in the windows panels.
Download
Direct
Panel CFIG
3. Click OK.

The dialog shown in Figure 11-6 appears, prompting you to begin the
download.

Figure 11-6. Download Dialog


4. Click on the Start button to begin the download.

A progress thermometer appears, tracking the progress of the download.

Continued on next page

11-5

Technical Manuals Online! - http://www.tech-man.com


Downloading a CFG File to the Panel, Continued

Step 4. Start Download at PC


(continued)

Figure 11-7. Transfer in Progress

7. When the following prompt appears, choose Yes to restart the panel.

Note: You must restart the panel from the PC, not the panel. Pressing the
panels warm start button causes all downloaded information to be lost.

Figure 11-8. Restart Panel Prompt

11-6

Technical Manuals Online! - http://www.tech-man.com


Appendix A
Hardware Device Types,
Software Point Types, and Point Addresses

Introduction This appendix lists and explains the following:

Hardware Device Types. 4010 hardware device types are listed with their
corresponding PIDs, allowing you to exactly match the equipment used
with the available device types.

Software Point Types. 4010 point types are grouped into two general
categories:

- Monitor point types are used with monitoring devices, such as smoke
detectors, pull stations, heat detectors, fire pump monitors, etc.

- Control point types are used with signal (notification appliance) and
relay devices.

Point Addresses and definitions. Each 4010 point has a point address, such
as 1-1 (NAC card signal 1 address). A point address and an understanding
of when the point turns ON and OFF are necessary for referencing points in
Custom Control equations.

In this Chapter This appendix discusses the following topics:

Topic See Page #


Device Types A-2
Control Point Types A-3

Device Types/Point Types


Monitor Point Types A-9
24-Point I/O Point Types A-17
Addresses for Hardware Points A-18
Addresses for Pseudo Points A-25

A-1

Technical Manuals Online! - http://www.tech-man.com


Device Types

Sensor/Base Device Types The hardware device type used for a specific sensor/base combination depends
on the combination. The following table summarizes which point types can be
used with the various combinations of sensor and base.

To use this table, first identify the exact sensor/base combination in use for each
IDNet point. The point at which the column (base) and row (sensor) intersect
contains the device type that you should use for that sensor/base combination.

Standard LED Sounder Isolator External Internal Relay


Base Base Base Base Duct Base Duct Base Base
4098-9792 4098-9789 4098-9793 4098-9750 4098-9752 4098-9791
4098-9751 4098-9753

Photo PHOTO SPHOTO IPHOTO PHOTO PHOTO RPHOTO


Sensor XPHOTO XSPHOTO XIPHOTO RPHOTO RPHOTO XRPHOTO
4098-9714 XPHOTO? XPHOTO?

Ion
ION SION IION N/A N/A RION
Sensor
4098-9717
Heat
HEAT SHEAT IHEAT N/A N/A RHEAT
Sensor
OHEAT SOHEAT IOHEAT ROHEAT
4098-9733

IAMs / ZAMs / IDNet The following table lists the PIDs and corresponding device types for IAMs,
Addressable Device Types ZAMS, and IDNet Addressable devices.

Device PID Device Type


IDNet Class A Monitor ZAM 4090-9106 MAZAM

IDNet Class B Monitor ZAM 4090-9101 MBZAM


International Pull Station International Only KACPUL
Canadian Pull Station Canadian Only CANPUL
IDNet Single Action Pull Station Standard -- 4090-9001 ADRPUL
Break Glass -- 4090-9002
Double Action -- 4090-9003
IDNet Supervised IAM 4090-9001 IAM
IDNet Relay IAM 4090-9002 RIAM
4009A IDNet Addressable NAC Device with 4 NACs 4009-9201 4009A
4009A IDNet Addressable NAC Device with 8 NACs 4009-9201 and 4009 9807 4009A8
4009A IDNet Addressable NAC Device with 4 NACs 4009-9201 and 4009-9809 R4009A
and a Repeater
4009A IDNet Addressable and a Repeater NAC 4009-9201 and 4009 9807 R4009A8
Device with 4 NACs and 4009-9809

A-2

Technical Manuals Online! - http://www.tech-man.com


Control Point Types

AHUF AHU off relay dual relay control. This point type is used with applications
that use two auxiliary relays for AHU control one relay for ON and one relay
for OFF. Use this point type for the OFF relay. See AHUO also. If you have a
single relay that performs both ON and OFF functions, see AHUR.

Circuit Status LCD Display System Status


ON AHU OFF Relay ON
OFF AHU OFF Relay OFF
AHU OFF Relay CODING
Disabled TBL AHU OFF Relay TROUBLE
OFF AUTO TBL AHU OFF Relay TROUBLE

AHUO AHU on relay dual relay control. This point type is used with applications that
use two auxiliary relays for AHU control one relay for ON and one relay for
OFF. Use this point type for the ON relay. Points assigned with this type
operate on general alarm. See AHUF also. If you have a single relay that
performs both ON and OFF functions, see AHUR.

Circuit Status LCD Display System Status


ON AHU ON Relay ON
OFF AHU ON Relay OFF
AHU ON Relay CODING
Disabled TBL AHU ON Relay TROUBLE
OFF AUTO TBL AHU ON Relay TROUBLE

AHUR AHU on/off relay single relay control. This point type is used with
applications in which a single relay performs AHU ON and OFF control. Points
assigned with this type operate on general alarm.

Device Types/Point Types


Circuit Status LCD Display System Status
ON AHU Relay ON
OFF AHU Relay OFF
AHU Relay CODING
Disabled TBL AHU Relay TROUBLE
OFF AUTO TBL AHU Relay TROUBLE

Continued on next page

A-3

Technical Manuals Online! - http://www.tech-man.com


Control Point Types, Continued

ALTERN Elevator capture alternate. Used for a relay connected to the elevator controls
to provide alternate floor elevator recall.

Circuit Status LCD Display System Status


ON ALT Elevator Recall ON
OFF ALT Elevator Recall OFF
ALT Elevator Recall CODING
Disabled TBL ALT Elevator Recall TROUBLE
OFF AUTO TBL ALT Elevator Recall TROUBLE

BSIGNAL Trouble/supervisory bell signal. Used when an audible signal should activate
on any supervisory or trouble condition and remain ON until the condition has
been acknowledged.

Circuit Status LCD Display System Status


ON Trouble Signal ON
OFF Trouble Signal OFF
Trouble Signal CODING
Disable TBL Trouble Signal TROUBLE
OFF AUTO TBL Trouble Signal TROUBLE

DHOLDER Door holder control (normally off). Used when the auxiliary relay is connected
to door holders. The relay energizes on alarm, loss of AC Power, or when
programmed.

Circuit Status LCD Display System Status


ON Door Holder ON
OFF Door Holder OFF
Door Holder CODING
Disable TBL Door Holder TROUBLE
OFF AUTO TBL Door Holder TROUBLE

Continued on next page

A-4

Technical Manuals Online! - http://www.tech-man.com


Control Point Types, Continued

PRIMARY Elevator capture primary. Used for any relay connected to the elevator
controls to provide primary floor elevator recall. By default, these relays pick
on any alarm.

Circuit Status LCD Display System Status


ON Pri Elevator Capture ON
OFF Pri Elevator Capture OFF
Pri Elevator Capture CODING
Disable TBL Pri Elevator Capture TROUBLE
OFF AUTO TBL Pri Elevator Capture TROUBLE

QALERT TrueAlert Non-Addressable signal. QALERT device type has no automatic


operation. All operations for this type of device type must be programmed with
Custom Control.

SQALERT SQALERT device type automatically turns on the designated circuit on alarm
detect (general alarm), issues the horn silence command upon Alarm Silence,
and turns off the circuit at the completion of System Reset. Any point
programmed with the SQALERT point type is not available for use in Custom
Control programming.

RELAY Generic relay no default operation. Used for any relay application that is not
defined by a specific point type.

Circuit Status LCD Display System Status


ON Auxiliary Relay ON
OFF Auxiliary Relay OFF
Auxiliary Relay CODING

Device Types/Point Types


Disable TBL Auxiliary Relay TROUBLE
OFF AUTO TBL Auxiliary Relay TROUBLE

RSIGNAL Alarm signal on until reset. Used for any signaling device (such as an audible
or visible notification appliance) that is required to be on until a system reset is
performed. Points assigned with this type operate on general alarm.

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
OFF AUTO TBLE Signal Circuit TROUBLE

Continued on next page

A-5

Technical Manuals Online! - http://www.tech-man.com


Control Point Types, Continued

RVISUAL Used only with visual notification appliances that must be ON until a system
reset is performed. Points assigned with this type operate on general alarm.

Circuit Status LCD Display System Status


ON Visual ON
OFF Visual OFF
Visual CODING
Disable TBL Visual TROUBLE
Off Auto TBL Visual TROUBLE

RWATER Waterflow signal on until reset.

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Off Auto TBL Visual TROUBLE

SIGNAL Generic Alarm Signal on until reset. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm.

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
OFF AUTO TBLE Signal Circuit TROUBLE

Continued on next page

A-6

Technical Manuals Online! - http://www.tech-man.com


Control Point Types, Continued

SSIGNAL Alarm signal on until silence. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm.

Circuit Status LCD Display System Status


Normal Signal Circuit ON
Normal Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
OFF AUTO TBLE Signal Circuit TROUBLE

SUPREL Suppression release output.

Circuit Status LCD Display System Status


Normal Signal Circuit ON
Normal Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE

SUPV Sprinkler supervisory signal. Turns ON with a SO or WSO supervisory alarm.


Turns OFF on ACK or when the supervisory clears. Example: Have a relay and
its point type is SUPV, used to set off a bell when a tamper is triggered or a gate
valve is opened.

Circuit Status LCD Display System Status


Normal Signal Circuit ON
Normal Signal Circuit OFF

Device Types/Point Types


Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE

SVISUAL Visual on until silence. Used only with visual notification appliances that
must remain ON until an Alarm Silence is performed.

Circuit Status LCD Display System Status


Normal Visual ON
Normal Visual OFF
Visual CODING
Disable TBL Visual TROUBLE
OFF AUTO TBL Visual TROUBLE

Continued on next page

A-7

Technical Manuals Online! - http://www.tech-man.com


Control Point Types, Continued

SWATER Waterflow signal on until silence. Used in applications where a waterflow


signal circuit is required to remain activated until the Alarm Silence key is
pressed.

Circuit Status LCD Display System Status


ON Signal Circuit ON
OFF Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Disable TBL Signal Circuit TROUBLE

TSIGNAL Trouble/supervisory signal.

Circuit Status LCD Display System Status


ON Signal Circuit ON
ON Signal Circuit OFF
Signal Circuit CODING
Disable TBL Signal Circuit TROUBLE
Disable TBL Signal Circuit TROUBLE

A-8

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types

FIRE This is a generic fire alarm point type. A typical application for this point type
is a fire alarm zone containing more than one type of device. For example,
when a combination of smoke detectors, pull stations, waterflow monitors, and
heat detectors is connected to an IAM or ZAM, this point type allows alarms to
report as originating from a zone.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Fire Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Fire Alarm

When an Alarm or Trouble condition occurs, press Enter to view specific


information for the Fire Monitor Zone

WATER Used to define the operation of a waterflow monitor for all possible circuit
states.

Circuit Status LCD Text Status


Normal Normal
Limited Waterflow Monitor Fire Alarm
Open Waterflow Monitor Open Trouble
Short Waterflow Monitor Fire Alarm

DUCT Used to define the operation of a duct detector for all possible circuit states.

Circuit Status LCD Text Status


Normal Normal
Limited Duct Detector Fire Alarm
Open Duct Detector Open Trouble
Short Duct Detector Fire Alarm

Device Types/Point Types


HEAT Defines the operation of a duct detector for all possible circuit states.

Circuit Status LCD Text Status


Normal Normal
Limited Heat Detector Fire Alarm
Open Heat Detector Open Trouble
Short Heat Detector Fire Alarm

Continued on next page

A-9

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types, Continued

FLAME Use for flame detectors.

Circuit Status LCD Text Status


Normal Normal
Limited Flame Detector Fire Alarm
Open Flame Detector Open Trouble
Short Flame Detector Fire Alarm

PULL Use with manual pull stations.

Circuit Status LCD Text Status


Normal Normal
Limited Manual Pull Station Fire Alarm
Open Manual Pull Station Open Trouble
Short Manual Pull Station Fire Alarm

SMOKE Use for 2- and 4-wire smoke detectors.

Circuit Status LCD Text Status


Normal Normal
Limited Smoke Detector Fire Alarm
Open Smoke Detector Open Trouble
Short Smoke Detector Fire Alarm

EMERG Use for an emergency monitor zone in which two types of alarm devices for
example, emergency alarm devices such as Nurse Call and fire alarm devices --
are connected to an IAM or ZAM. Emergency devices require the use of a
current limiting resistor. These devices generate an Emergency Alarm condition
at the panel.

Circuit Status LCD Text Status


Normal Normal
Limited Monitor Zone Emergency Alarm
Open Monitor Zone Open Trouble
Short Monitor Zone Fire Alarm

SFIRE Used when smoke detectors and shorting type devices are connected to an IAM
or ZAM.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Smoke Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Fire Alarm

Continued on next page

A-10

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types, Continued

VFIRE Used to activate the alarm verification software for all smoke detectors
connected to an IAM or ZAM. Shorting type devices cause an immediate alarm.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Verified Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Fire Alarm

SPULL Used when smoke detectors and pull stations are connected to an IAM or ZAM.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Smoke Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Manual Alarm

VSPULL Used when smoke detectors that must be verified and pull stations are connected
to an IAM or ZAM.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Verified Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Manual Alarm

GENMON Used when emergency generator monitoring is required. The shorted condition
of the circuit indicates an abnormal status and is indicated by the Supervisory
Service LED. The current limited condition of the circuit indicates that the
generator is running, and can be tracked with an LED (must be programmed). A
current limiting resistor must be installed for this to happen.

Device Types/Point Types


Circuit Status LCD Text Status
Normal Normal
Limited Generator Monitor Running
Open Generator Monitor Open Trouble
Short Generator Monitor Abnormal

SGENMON Same operation as the GENMON point type, but the generator running condition
automatically displays and requires operator acknowledgment.

Circuit Status LCD Text Status


Normal Normal
Limited Generator Monitor Running
Open Generator Monitor Open Trouble
Short Generator Monitor Abnormal

Continued on next page

A-11

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types, Continued

FPUMP Used to monitor fire pump conditions. The shorted condition indicates that the
fire pump is abnormal. The current limited condition indicates that the fire
pump is running.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Pump Monitor Running
Open Fire Pump Monitor Open Trouble
Short Fire Pump Monitor Abnormal

SFPUMP Same as the FPUMP point type, except that the fire pump running condition
requires operator acknowledgment.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Pump Monitor Running
Open Fire Pump Monitor Open Trouble
Short Fire Pump Monitor Abnormal

S2STAGE Used for 2-stage alarms. The current limited operation of any device indicate a
Stage 1 Alarm. A short on the points circuit, such as a key switch operation,
causes a Stage 2 Alarm.

Circuit Status LCD Text Status


Normal Normal
Limited 2 Stage Monitor Stage 1 Alarm
Open 2 Stage Monitor Open Trouble
Short 2 Stage Monitor Stage 2 Alarm

SO Used to indicate abnormal sprinkler conditions, such as the opening of a PIV or


OS&Y tamper switch. This point type must be used with normally open
contacts only.

Circuit Status LCD Text Status


Normal Normal
Limited Sprinkler Monitor Abnormal
Open Sprinkler Monitor Open Trouble
Short Sprinkler Monitor Abnormal

Continued on next page

A-12

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types, Continued

WSO Combination Waterflow/Sprinkler Monitor (NO). Where permitted by the AHJ,


this circuit operates both waterflow monitors and PIV/OS&Y tampers on the
same circuit. All tamper switches (N.O. contacts) must be connected with a
current limiting resistor. Refer to the 4010 field wiring diagrams. A short
condition indicates waterflow alarms.

Circuit Status LCD Text Status


Normal Normal
Limited Sprinkler Monitor Abnormal
Open Sprinkler Monitor Open Trouble
Short Sprinkler Monitor Waterflow Alarm

SUPDET Suppression (Agent Discharge) Monitor.

Circuit Status LCD Text Status


Normal Normal
Limited Suppression Detector Fire Alarm
Open Suppression Detector Open Trouble
Short Suppression Detector Fire Alarm

SUPABRT Suppression Abort (supervised).

Circuit Status LCD Text Status


Normal Normal
Limited Suppression Abort Activated
Open Suppression Abort Open Trouble
Short Suppression Abort Short Trouble

SUPDUMP Manual suppression agent discharge .

Circuit Status LCD Text Status

Device Types/Point Types


Normal Normal
Limited Suppression Manual Dump Activated
Open Suppression Manual Dump Open Trouble
Short Suppression Manual Dump Short Trouble

SUPPRES Suppression agent pressure switch monitor.

Circuit Status LCD Text Status


Normal Normal
Limited Suppression Pressure Discharge
Open Suppression Pressure Open Trouble
Short Suppression Pressure Short Trouble

Continued on next page

A-13

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types, Continued

SUPV Used to monitor any supervisory type device where operator acknowledgment is
required.

Circuit Status LCD Text Status


Normal Normal
Limited Supervisory Monitor Abnormal
Open Supervisory Monitor Open Trouble
Short Supervisory Monitor Abnormal

UTIL Used to monitor and supervise any condition; operator acknowledgment is not
required. No alarm is generated by this point type.

Circuit Status LCD Text Status


Normal Normal
Limited Utility Monitor Abnormal
Open Utility Monitor Open Trouble
Short Utility Monitor Abnormal

TROUBLE Used for trouble monitoring only. No alarm is generated by this point type.

Circuit Status LCD Text Status


Normal Normal
Limited Trouble Monitor Abnormal
Open Trouble Monitor Open Trouble
Short Trouble Monitor Abnormal

VSMOKE Used with smoke detectors whose alarm status must be verified.

Circuit Status LCD Text Status


Normal Normal
Limited Smoke Detector Verified Alarm
Open Smoke Detector Open Trouble
Short Smoke Detector Fire Alarm

GVMON Used when the abnormal condition of the circuit must be verified.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Verified Alarm
Open Fire Monitor Open Trouble
Short Fire Monitor Fire Alarm

Continued on next page

A-14

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types, Continued

LATSUPV Supervisory Monitor latch until reset. Used for generic supervisory alarm.

Circuit Status LCD Text Status


Normal Normal
Limited Supervisory Alarm Abnormal
Open Supervisory Alarm Open Trouble
Short Supervisory Alarm Abnormal

STYLEC Style-C Fire Alarm Monitor. Used when only current limited devices are
connected to the zone. A short circuit is reported as a Trouble.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Monitor Zone Fire Alarm
Open Fire Monitor Zone Open Trouble
Short Fire Monitor Zone Short Trouble

SDUCT Supervisory Duct Detector.

Circuit Status LCD Text Status


Normal Normal
Limited Flame Detector Abnormal
Open Flame Detector Open Trouble
Short Flame Detector Abnormal

ABORT Abort zone.

Circuit Status LCD Text Status


Normal Normal
Limited Fire Alarm Abort Abnormal
Open Fire Alarm Abort Open Trouble

Device Types/Point Types


Short Fire Alarm Abort Abnormal

DAMPER Damper Monitor.

Circuit Status LCD Text Status


Normal Normal
Limited Damper Monitor Abnormal
Open Damper Monitor Open Trouble
Short Damper Monitor Abnormal

Continued on next page

A-15

Technical Manuals Online! - http://www.tech-man.com


Monitor Point Types, Continued

4009A 4009A Point Type.

Circuit Status LCD Text Status


Normal Normal
Limited 4009A Abnormal
Open 4009A Open Trouble
Short 4009A Abnormal

A-16

Technical Manuals Online! - http://www.tech-man.com


24 Point I/O Point Types

USWITCH 2-position switch, unsupervised. Used for a 2-position switch without an EOL
or current limited resistor.

Circuit Status LCD Text Status


Normal OFF
Limited 2-Position Switch Invalid State TBL
Open 2-Position Switch ON
Disable TBL 2-Position Switch Disable TBL

OSWITCH 2-position switch, supervised for opens. Requires an EOL resistor.

Circuit Status LCD Text Status


Normal OFF
Limited 2-Position Switch Invalid State TBL
Open 2-Position Switch Open CKT TBL
Short 2-Position Switch ON
Disable TBL 2-Position Switch Disable TBL

SSWITCH 2-position switch, supervised for opens and shorts. Requires EOL and current
limited resistors.

Circuit Status LCD Text Status


Normal OFF
Limited 2-Position Switch ON
Open 2-Position Switch Open CKT TBL
Short 2-Position Switch SHORT CKT TBL
Disable TBL 2-Position Switch Disable TBL

TSWITCH 3-position (SPDT) switch, supervised for opens. Requires EOL and series
current limiting resistors (up leg).

Device Types/Point Types


Circuit Status LCD Text Status
Normal CENTER
Limited 3-Position Switch UP
Open 3-Position Switch Open CKT TBL
Short 3-Position Switch DOWN
Disable TBL 3-Position Switch Disable TBL

A-17

Technical Manuals Online! - http://www.tech-man.com


Addresses for Hardware Points

The 4010 FACP contains many different types of points -- including read-only
system points, IDNet channel points, points on optional cards, digital and analog
pseudo points, list points, and card status (trouble) points. Many of these points
may be referenced , using the points address, in Custom Control equations.

This section provides a card-by-card description of the 4010s hardware, pseudo,


and list points. Card Status points, which may only be viewed from the Active
Trouble List, the Historical Logs, or on an RS-232 port (if available), are not
discussed in this section.

Master Controller (SFIO) The Master Controller (SFIO) card resides at card address 0 and contains 13
Hardware Points hardware points. In the table, each point has a type of R or U. Points listed with
a type of R are reserved system points. Points with a type of U are user-
configurable.

Point Type Label Description


0-1 R Front Panel Indicates the status of the piezo sounder on
Piezo the 4010 Master.
0-2 R External N2 Indicates the status of the External N2
Disconnect Disconnect Relay. Turns on when no slaves
Relay are communicating; turns off on System
Reset.
0-3 R Fire LED Status of the front panel Alarm LED.
0-4 R Supervisory Status of the front panel Supervisory LED.
LED
0-5 R Trouble Status of the front panel Trouble LED.
LED
0-6 R Alarm Status of the front panel Alarm Silence LED.
Silence LED
0-7 R AC Power Status of the front panel AC Power LED.
LED
0-8 U User LED 1 This point indicates the status and
configuration of the first user programmable
LED on the front panel.
0-9 U User LED 2 This point indicates the status and
configuration of the second user
programmable LED on the front panel.
0-10 U User LED 3 This point indicates the status and
configuration of the third user programmable
LED on the front panel.
0-11 U User This point indicates the status and
Defined Key configuration of the first user programmable
1 key (in the function menu).
0-12 U User This point indicates the status and
Defined Key configuration of the second user
2 programmable key (in the function menu).
0-13 R LCD Indicates the status of the LCD backlight on
Backlight the front panel.

Continued on next page

A-18

Technical Manuals Online! - http://www.tech-man.com


Addresses for Hardware Points, Continued

NAC Card Hardware Points The NAC has 7 hardware points associated with it. Of the 7 hardware points, 6
are points which may be programmed by the user. The other point is the City
Circuit point which is not available for programming or viewing by the user.
The following table is a list of the points on the NAC card. The type field
denotes which class the point falls into (S=System point that is not available to
the user for viewing or programming , U=User Configurable Points).

Point Type Label Description


(default)
1-1 U NAC NAC card Signal 1 status and configuration.
Circuit: SIG
1
1-2 U NAC NAC card Signal 2 status and configuration.
Circuit: SIG
2
1-3 U NAC NAC card Signal 3 status and configuration.
Circuit: SIG
3
1-4 U NAC NAC card Signal 4 status and configuration.
Circuit: SIG
4
1-5 U AUX NAC card Relay 1 status and configuration.
Circuit:
AUX 1
1-6 U AUX NAC card Relay 2 status and configuration.
Circuit:
AUX 2
1-7 S City Circuit Interface 4004 / 4005 / 4010 City Module.

Power Supply Card The Power Supply Card is required for all 4010 configurations, and is located at
card address 2. There are 9 hardware points associated with the Power Supply
card, all of which are system points that cannot be modified by the user. The

Device Types/Point Types


following table is a list of the points on the Power Supply card.

Point Label Description


2-1 AC Power This trouble point will indicate that the AC
line voltage is too low for proper system
operation.
2-2 Positive Earth This trouble point indicates that there is a
Ground fault condition between +24V and earth.
2-3 Negative Earth This trouble point indicates that there is a
Ground fault condition between 0V and earth.
2-4 Expansion Power This trouble point indicates Expansion Power
Supply Supply trouble. Only occurs if expansion
supply is configured.
2-5 Expansion Power This trouble point indicates Expansion Power
Supply Battery Supply AUX Power trouble. Only occurs if
expansion supply is configured.

Continued on next page

A-19

Technical Manuals Online! - http://www.tech-man.com


Addresses for Hardware Points, Continued

Power Supply Card


(continued) Point Label Description
2-6 Battery Low This trouble point indicates that the battery
has a voltage less than 22.8V.
2-7 Battery This trouble point indicates that the battery
Depleted/Disconnected has a voltage less than 19.5V.
2-8 Battery Low Cutout This trouble point indicates that the
batteries have reached a depleted state, and
the system will shut itself off.
2-9 Battery Charger This trouble point indicates that the battery
Trouble charger has failed. Set if hardware
indicates trouble and AC fail has not
occurred in the previous 24 hours.
2-10 Battery Charger This output point controls the status of the
battery charger (on/off).

IDNet Card The IDNet Card is required for all 4010 configurations, and is located at card
address 3. The IDNet Card defaults to a configuration with no hardware points
(devices). However, up to 250 devices may be programmed for the IDNet Card.
The IDNet Card also includes eight card status points.

The IDNet card can have up to 250 devices configured. All of the IDNet
devices can be modified by the user. How the point is configured (i.e. software
point type) will determine what action will be taken (trouble, alarm, etc.) when
the point changes state. The following table is a list of the points that may be
included on the IDNet card. The labels indicated for the points are the default
labels assigned when the point is added from the front panel.

Point Label (default) Description


3-1 IDNet Device: M1-1 The point on the IDNet card configured for
address 1.
3-2 IDNet Device: M1-2 The point on the IDNet card configured for
address 2.
3-3 IDNet Device: M1-3 The point on the IDNet card configured for
address 3.
3-249 IDNet Device: M1- The point on the IDNet card configured for
249 address 249.
3-250 IDNet Device: M1- The point on the IDNet card configured for
250 address 250.

RS232\Modem Card Either an RS232 Card or Modem Card may be added to the 4010 system. Even
though these cards are optional, if an RS232 or Modem card is configured, it
must reside at card address 4. There are two hardware points associated with
them. Both of the RS232/Modem points are user configurable. However, the
points have no labels associated with them, because they cannot be viewed on
the front panel. The following table is a list of the points on the RS232/Modem
cards.

Continued on next page

A-20

Technical Manuals Online! - http://www.tech-man.com


Addresses for Hardware Points, Continued

RS232\Modem Card
(continued) Point Label Description
4-1 None Port A point. Default to unsupervised 80
character Printer port.
4-2 None Port B point. Default to command line port.

SDACT Card The SDACT card is an optional card that may be added to the 4010 system. The
SDACT card is mutually exclusive with the Network card, and if configured,
must reside at address 8. There is one hardware point associated with the
SDACT card. The point does not have a label, and cannot be viewed from the
front panel.

Point Label Description


8-1 None SDACT Port.

Network Card The Network card is an optional card that may be added to the 4010 system.
The Network card is mutually exclusive with the SDACT card, and if
configured, must reside at address 8. The network card allows the 4010 to serve
as a network node for a 4120 network. Points on the 4010 may be declared
public to the 4120 network. These points are the Network Status points, and
will be described in this section.

The Network card can have up to 511 Network points configured. The
following table is a list of the points that may be configured on the Network
card. The Common Trouble Point is the only default point for the Network card.

Point Label Description


NetPt1 None This point is the Network Common Trouble
Point. This point is public on the network.

Device Types/Point Types


NetPt2 None This point contains the Network Type, Class,
Destination, and Reference for the second
network public point.
NetPt3 None This point contains the Network Type, Class,
Destination, and Reference for the third
network public point.
NetPt510 None This point contains the Network Type, Class,
Destination, and Reference for the 510th
network public point.
NetPt511 None This point contains the Network Type, Class,
Destination, and Reference for the 511th
network public point.

Continued on next page

A-21

Technical Manuals Online! - http://www.tech-man.com


Addresses for Hardware Points, Continued

24 Point I/O Card The 4010 can have up to six annunciator cards added to the system. One of
these cards is the 24IO card. The 24IO card can reside at addresses 9 through
14.

Each 24I/O card has 24 hardware points associated with it. The user can
program all hardware points on the 24I/O card. The functionality of the point
depends on the device type (Input or Output), the point type, and modes
programmed against it. The labels for the points on the 24I/O card are default
labels, and cannot be changed by the user. The following table describes the
organization of points on the 24I/O card. In this table, card represents the card
address (9-14) of the 24 I/O card.

Point Label Description


card-1 I/O Card #, Point 1 The 1st point on the 24IO card.
card-2 I/O Card #, Point 2 The 2nd point on the 24IO card.
card-3 I/O Card #, Point 3 The 3rd point on the 24IO card.
card-23 I/O Card #, Point 23 The 23rd point on the 24IO card.
card-24 I/O Card #, Point 24 The 24th point on the 24IO card.

LCD Card The 4010 can have up to six annunciator cards added to the system. One of
these cards is the LCD card. The LCD card can reside at addresses 9 through
14. The LCD card has five hardware points associated with it. Only the first
three hardware points (user LEDs) on the LCD card can be programmed by the
user. The labels for the points on the LCD card are default labels, and cannot be
changed by the user. The following table describes the points included on the
LCD card. In this table, card represents the card address (9-14) of the LCD
Annunciator card.

Point Label Description


card-1 LCD Card #, Point 1 The status of the First User LED on the LCD
card. Programmable for color and mode.
card-2 LCD Card #, Point 2 The status of the Second User LED on the
LCD card. Programmable for color and
mode.
card-3 LCD Card #, Point 3 The status of the Third User LED on the
LCD card. Programmable for color and
mode.
card-4 LCD Card #, Point 4 The status of the Alarm Silence LED on the
LCD card.
card-5 LCD Card #, Point 5 The status of the Piezo sounder on the LCD
card.

Continued on next page

A-22

Technical Manuals Online! - http://www.tech-man.com


Addresses for Hardware Points, Continued

4009A Card The 4009A Card, which always resides at card address 17, is a very unique card
in the 4010 system. The 4009A card itself is a pseudo card, which means that
an actual hardware card does not exist at address 17. However, unlike other
pseudo cards in the system, the points on the 4009A pseudo card track the status
of actual hardware points. The points on the 4009A Card are used to control and
track the status of the NAC circuits found on all of the 4009A devices
configured in the system. Therefore, the number of configured points on the
4009A Card may vary, depending on the number of 4009A devices configured
in the system. The 4010 can have up to five 4009A devices programmed into
the system, with each 4009A device having up to 8 NAC points, and 8 card
status points associated with it. An overview of how the 4009A points are
configured, and how these points are associated with a specific 4009A device, is
provided in the following sections.

The 4009A card can have up to five 4009A devices associated with it. Each
of the 4009A devices can be configured to have 4 or 8 NACs. Regardless of the
configuration of the 4009A device, the 4009A card always has room provided
for 8 NACs per device. The labels shown for the points on the 4009A card are
default labels. However, these labels may be changed by the user. The
following table describes the points included on the 4009A card. (S=System
point that is not available to the user for viewing or programming , U=User
Configurable Points.)

Point Type Label Description


(default)
17-1 U IDNet M1- The status of the first NAC on the first
#: 4009A 4009A device configured in the system. The
NAC 1 device is indicated by the IDNet address
provided.
17-2 U IDNet M1- The status of the second NAC on the first
#: 4009A 4009A device configured in the system. The
NAC 2 device is indicated by the IDNet address
provided.
17-3 U IDNet M1- The status of the third NAC on the first

Device Types/Point Types


#: 4009A 4009A device configured in the system. The
NAC 3 device is indicated by the IDNet address
provided.
17-4 U IDNet M1- The status of the fourth NAC on the first
#: 4009A 4009A device configured in the system. The
NAC 4 device is indicated by the IDNet address
provided.
17-5 U IDNet M1- The status of the fifth NAC on the first
#: 4009A 4009A device configured in the system. The
NAC 5 device is indicated by the IDNet address
provided.
17-6 U IDNet M1- The status of the sixth NAC on the first
#: 4009A 4009A device configured in the system. The
NAC 6 device is indicated by the IDNet address
provided.

Continued on next page

A-23

Technical Manuals Online! - http://www.tech-man.com


Addresses for Hardware Points, Continued

4009A Card (continued)


Point Type Label Description
(default)
17-8 U IDNet M1- The status of the eighth NAC on the first
#: 4009A 4009A device configured in the system. The
NAC 8 device is indicated by the IDNet address
provided.
17-9 U IDNet M1- The status of the first NAC on the second
#: 4009A 4009A device configured in the system. The
NAC 1 device is indicated by the IDNet address
provided.
17-33 U IDNet M1- The status of the first NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 1 device is indicated by the IDNet address
provided.
17-34 U IDNet M1- The status of the second NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 2 device is indicated by the IDNet address
provided.
17-35 U IDNet M1- The status of the third NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 3 device is indicated by the IDNet address
provided.
17-36 U IDNet M1- The status of the fourth NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 4 device is indicated by the IDNet address
provided.
17-37 U IDNet M1- The status of the fifth NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 5 device is indicated by the IDNet address
provided.
17-38 U IDNet M1- The status of the sixth NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 6 device is indicated by the IDNet address
provided
17-39 U IDNet M1- The status of the seventh NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 7 device is indicated by the IDNet address
provided.
17-40 U IDNet M1- The status of the eighth NAC on the fifth
#: 4009A 4009A device configured in the system. The
NAC 8 device is indicated by the IDNet address
provided.

A-24

Technical Manuals Online! - http://www.tech-man.com


Addresses for Pseudo Points

Introduction There are three types of pseudo points that exist in every system. They include
digital, analog, and list pseudo. Each of these types may be referenced in
Custom Control in both the input and output sides of an equation. Reserved
system pseudo points are used to indicate system trouble or alarm indications,
control diagnostics or other system functions, and to communicate information
between the 4010 Master and SMPL. Some pseudos are set by the system and
are read only to the user. Other pseudos are either set from SMPL or from the
front panel as a cue for the system to perform some operation.

Digital Pseudo Points Every 4010 system has two Digital Pseudo cards at addresses 18 and 19. The
first card is reserved for system pseudo points while the second is available to
the user. Each contains 75 digital pseudo points which may be programmed as
follows:

Type Description
UTILITY Utility point (ON/OFF - no acknowledge required)
ALARM Fire alarm point. Turning the point on causes an ALARM
condition.
SUPV Supervisory point.
TROUBLE Trouble point.

Each system digital pseudo point falls into one of the following categories:

Class Description
R Point is controlled by the 4010 master and is read only to the
end user.
RW Point is controlled by the 4010 master, but may also be
controlled by the end user (front panel or SMPL).
W Point is controlled by the end user and is read by the 4010
Master in order to accomplish some function or operation.

Device Types/Point Types


The system digital pseudo card in the 4010 system is located at address 18. It
contains a total of 75 reserved system pseudo points that cannot be edited. The
following table list the system pseudo points. The type field denotes which class
(see above) the point falls into, and what its type is (U=UTIL, F=FIRE,
T=TROUBLE, S=SUPERVISORY).

Continued on next page

A-25

Technical Manuals Online! - http://www.tech-man.com


Addresses for Pseudo Points, Continued

Digital Pseudo Points


(continued) Point Type Label Description
D1 R U Unacked On if unacked fire exists in system.
Fire in
System
D2 R U Unacked On if unacked supervisory exists in system.
Supervisory
in System
D3 R U Unacked On if unacked trouble exists in system.
Trouble in
System
D4 R T Extra N2 Turned on at panel startup if an
Card unprogrammed N2 slave card is detected.
Only clears on panel restart.
D5 R T External N2 Turns on when panel is no longer
Trouble communicating with ALL slave cards. Turns
off on a System Reset.
D6 RW User SMPL On when User SMPL program is active.
U Program
D7 R T Cold Start Indicates that panel has performed a cold start.
Turns of when acknowledged.
D8 R T Warm Start / Indicates that panel has performed a warm
Check Time start. Turns off when acknowledged.
and Date
D9 RW Manual Turns on when Manual Evacuation is selected.
F Evacuation Turns off on a System Reset.
D10 R T System Indicates that the time and date is incorrect.
Time and Turns off when time and date is updated.
Date
D11 R T Simplex Indicates that the panel is in Service Mode.
Service Turns off only on a panel restart.
Mode
D12 RW Keypad Disables Keypad Inactivity timer.
U Inactivity
Timer
Disable
D13 R T Active List Turns on when the number of alarms,
Overflow supervisories, or troubles is greater than the
system active list size (50 fires, 50 supv, 100
troubles). Turns off on a panel restart.
D14 RW City On if city circuit is disconnected.
T Disconnect
D15 R T City Circuit On if city circuit is in trouble.
Trouble
D16 RW AHJ City During a system reset, if this pseudo is On, a
U Reset point will reset unless it is in an ALARM
state. A point has to be in a NORMAL state
to reset, when the AHJ pseudo is off.

Continued on next page

A-26

Technical Manuals Online! - http://www.tech-man.com


Addresses for Pseudo Points, Continued

Digital Pseudo Points


(continued) Point Type Label Description
D17 RW Control On if control points are bypassed.
T Point
Bypass
D18 RW Elevator On if elevator recall points are bypassed.
T Bypass
D19 RW Doorholder On if doorholder points are bypassed.
T Bypass
D20 RW Verification On when any verified points tally limit
T Tally Limit exceeds 10. Off when all points tally limit is
Exceeded below 10.
D21 R T Walk Test On when Walk Test is active.
Active in
System
D22 R U Earth Fault On when Earth Fault Latch diagnostic is
Latch active.
D23 R T TrueTest On when TrueTest is active.
Active in
System
D24 R T Programmin On when Programming or Quick-CFIG is
g Mode - entered. Panel is no longer operational.
System
Disabled
D25 RW System This point is turned on when a system reset is
U Reset initiated. The point may be turned off using
Activated SMPL.
D26 RW Alarm This point is turned on when an alarm silence
U Silence is initiated. The point may be turned off using
Activated SMPL.
D27- - Reserved unused
D30 System
Pseudo

Device Types/Point Types


Point
D31 R U Network On if network is in running in degraded Style-
Style 7 4.
Abnormal
D32- - Reserved unused
D35 System
Pseudo
Point
D36 R U No CRT On if no set-host session is active on network
Connected card.
D37- - Reserved unused
D44 System
Pseudo
Point

Continued on next page

A-27

Technical Manuals Online! - http://www.tech-man.com


Addresses for Pseudo Points, Continued

Digital Pseudo Points


(continued) Point Type Label Description
D45 W T Duplicate When on (either through front panel or
IDNet SMPL) it enables the duplicate device
Device detection diagnostic on the IDNet card.
Detection
Active
D46 WT IDNet Weak When on (either through front panel or
Answer SMPL) it enables the weak answer detection
Detection diagnostic on the IDNet card.
Active
D47 R T Event Queue On when the RS232/LCD annunciator event
Overflow queue is overflowed and events have been
missed. Panel restart clears the trouble.
D48 W T LCD When on the panel tells all LCD Annunciators
Annunciator to disable their local sounder. Turning pseudo
Sounder off will enable the sounders. Controllable
Disable from front panel only - not SMPL.
D49 W U IDNet Boost When on it boosts the IDNet levels.
D50 W U Device When active it forces IDNet almost dirty
Almost troubles to report.
Dirty
D51 W U Peak Log When on any peak value change recorded on
Enable IDNet devices is sent to the Trouble Log.
D52 R U RS232 Port On whenever nothing is connected to Port A
A on the RS232 or RS232/Modem card.
Disconnecte
d
D53 R U RS232 Port On whenever nothing is connected to Port B
B on the RS232 or RS232/Modem card.
Disconnecte
d
D54- - Reserved unused
D57 System
Pseudo
Point
D58 R U Network Used in 4120 Network programming to
System perform a 4010 System Reset from another
Reset node.
D59 R U Network Used in 4120 Network programming to
Signal perform a 4010 Alarm Silence from another
Silence node.
D60 - Digital: P60 unused
D75 - Digital: P75 unused

Continued on next page

A-28

Technical Manuals Online! - http://www.tech-man.com


Addresses for Pseudo Points, Continued

4010 User Digital Pseudos The user digital pseudo card in the 4010 is at address 19. It has 75 points
available for specialized applications programming. Any point may be
programmed as one of the four types of digital pseudos (i.e. UTILITY, FIRE,
etc.), and each may be assigned a 40 character custom label.

Note that any user pseudo points defined as FIRE type are not auto-generated in
the General Alarm List (L1), and SUPERVISORY points are not generated into
the Supervisory Monitor List (L8).

Analog Pseudo Points Analog pseudo points exist as counters or timers in the 4010 system. SMPL
delay and cycle equations may be written referencing the user Analog pseudo
points on the output side (for delay/cycle operations). Each analog point may
contain a value from 0-65,535 and the point is considered ON when the value is
non-zero. For delay and cycle purposes, the maximum allowable value gives a
real-time range of just over 18 hours. There are two analog pseudo cards in the
4010 system - one reserved for system analogs, and one reserved for user points.

4010 System Analog Pseudos The 4010 system has one analog pseudo card reserved for system use at address
20. It contains a total of 25 points. At present, only the first 12 are used but the
remainder are reserved for future expansion.

Point Label Description


A1 Fire Count Number of fire alarms active in system.
A2 Supervisory Count Number of supervisory alarms active in system.
A3 Trouble Count Number of troubles active in system.
A4 System Startup Pulsed for one poll cycle during system startup.
A5 Almost Dirty Total number of devices that have an almost
Device Count dirty status (not necessarily a trouble).
A6 Dirty Device Count Total number of devices that are in Dirty
Trouble.
A7 Excessively Dirty Total number of devices that are in Excessively
Device Count Dirty Trouble.

Device Types/Point Types


A8 Current Year Numeric representation of the current calendar
year. (Example: the year 1998 is shown as 98).
A9 Current Month Numeric representation of the current calendar
month (1 - 12).
A10 Current Day Numeric representation of the current calendar
day.
A11 Current Hour Current hour (0 - 23).
A12 Current Minute Current minute (0 - 59).

4010 User Analog Pseudos The user analog pseudo card in the 4010 is at address 21. It has 25 points
available for specialized applications programming. The analog user pseudos
can have custom labels assigned to them.

Continued on next page

A-29

Technical Manuals Online! - http://www.tech-man.com


Addresses for Pseudo Points, Continued

List Pseudo Points List psuedo points provide a convenient way to group points in any manner the
user desires. The 4010 contains two list pseudo cards - one reserved for the
system and one for the user. The status of the list is determined by counts which
are maintained for the following states:

Fire Count
Trouble Count
Supervisory Count
Normal
Open
Limited
Short
Fire Ack
Trouble Ack
Supervisory Ack
Disable
On/Input
On/Coding
Manual Control

The 4010 restricts the total number of points in any one list to 255. It also
restricts the total number of points available on any one list card to 500 (the total
number of points in all lists on one list card cannot exceed 500).

4010 System Lists The 4010 system reserves one list card at address 22 for system use. Currently,
12 of the 25 system lists are used by the 4010 application. All of these lists
control application specific operation of the 4010 panel. Some are auto-
generated by the system as points are added and may not be edited, while the
remainder are filled by the user to activate pre-defined applications. The system
lists are shown below:

Point Label Description


L1 General Alarm Auto-generated by the panel and not
Monitor Points editable. Contains all fire-alarm monitor
points in the system plus the Manual Evac
pseudo. User FIRE digital pseudos are not
auto-generated here.
L2 Waterflow Alarm Auto-generated by the panel and not
Monitor Zones editable. Contains all waterflow-type
monitor points (WSO)
L3 Sprinkler Supervisory Auto-generated by the panel and not
Monitor Zones editable. Contains all sprinkler-type monitor
points (SO)
L4 Primary Elevator Filled by the user. When in fire state, will
Recall Monitors activate the primary elevator recall function.
L5 Alternate Elevator Filled by the user. When in fire state, will
Recall Monitors activate the alternate elevator recall function.

Continued on next page

A-30

Technical Manuals Online! - http://www.tech-man.com


Addresses for Pseudo Points, Continued

4010 System Lists (continued)


Point Label Description
L6 Control Points, Off Filled by the user. Turns on when L1 is in
With Silence FIRE detect, turns off with alarm silence.
L7 Control Points, Off Filled by the user. Turns on when L1 is in
With Reset FIRE detect, turns off with completed system
reset.
L8 Supervisory Monitor Auto-generated by the system - may be
Points edited. Contains all Supervisory type
monitor points.
L9 Automatic Auto-generated by the system - may be
Suppression Release edited. When in fire state, causes L12 to
Points activate after automatic release delay timer
expires.
L10 Suppression Manual Auto-generated by the system - may be
Release Points edited. When in the fire state, causes L12 to
activate after manual release delay timer
expires.
L11 Suppression Release Auto-generated by the system - may be
Abort Points edited. When in the supervisory state, causes
the suppression release sequence to abort.
L12 Suppression Release Auto-generated by the system - may be
Output Points edited. Activated by the panel when the
suppression release algorithm completes.

4010 User Lists The user list pseudo card in the 4010 is at address 23. It has 25 points available
that may be filled by the user for specialized applications. The user lists may
have custom labels assigned to them.

Device Types/Point Types

A-31

Technical Manuals Online! - http://www.tech-man.com


This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com


Appendix B
Conversion Table

Conversion Table
Introduction This appendix contains the Base 10 to Base 36 Conversion Table. Use this table
to convert your Base 10 branch and job numbers to the Base 36 format required
by the Programmer (see Chapter 2).

How to Use the Table


Use the following procedure to convert your Base 10 number to the equivalent
Base 36 number:
1. Find the number in the Base 10 column of the table.
2. Look in the adjacent Base 36 column to see the corresponding Base 36
number.

B-1

Technical Manuals Online! - http://www.tech-man.com


Base 10 to Base 36 Conversion Table

Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
0 0 50 1E 100 2S 151 47 201 5L
1 1 51 1F 101 2T 152 48 202 5M
2 2 52 1G 102 2U 153 49 203 5N
3 3 53 1H 103 2V 154 4A 204 5O
4 4 54 1I 104 2W 155 4B 205 5P
5 5 55 1J 105 2X 156 4C 206 5Q
6 6 56 1K 106 2Y 157 4D 207 5R
7 7 57 1L 107 2Z 158 4E 208 5S
8 8 58 1M 108 30 159 4F 209 5T
9 9 59 1N 109 31 160 4G 210 5U
10 A 60 1O 110 32 161 4H 211 5V
11 B 61 1P 111 33 162 4I 212 5W
12 C 62 1Q 112 34 163 4J 213 5X
13 D 63 1R 113 35 164 4K 214 5Y
14 E 64 1S 114 36 165 4L 215 5Z
15 F 65 1T 115 37 166 4M 216 60
16 G 66 1U 116 38 167 4N 217 61
17 H 67 1V 117 39 168 4O 218 62
18 I 68 1W 118 3A 169 4P 219 63
19 J 69 1X 119 3B 170 4Q 220 64
20 K 70 1Y 120 3C 171 4R 221 65
21 L 71 1Z 121 3D 172 4S 222 66
22 M 72 20 122 3E 173 4T 223 67
23 N 73 21 123 3F 174 4U 224 68
24 O 74 22 124 3G 175 4V 225 69
25 P 75 23 125 3H 176 4W 226 6A
26 Q 76 24 126 3I 177 4X 227 6B
27 R 77 25 127 3J 178 4Y 228 6C
28 S 78 26 128 3K 179 4Z 229 6D
29 T 79 27 129 3L 180 50 230 6E
30 U 80 28 130 3M 181 51 231 6F
31 V 81 29 131 3N 182 52 232 6G
32 W 82 2A 132 3O 183 53 233 6H
33 X 83 2B 133 3P 184 54 234 6I
34 Y 84 2C 134 3Q 185 55 235 6J
35 Z 85 2D 135 3R 186 56 236 6K
36 10 86 2E 136 3S 187 57 237 6L
37 11 87 2F 137 3T 188 58 238 6M
38 12 88 2G 138 3U 189 59 239 6N
39 13 89 2H 139 3V 190 5A 240 6O
40 14 90 2I 140 3W 191 5B 241 6P
41 15 91 2J 141 3X 192 5C 242 6Q
42 16 92 2K 142 3Y 193 5D 243 6R
43 17 93 2L 143 3Z 194 5E 244 6S
44 18 94 2M 144 40 195 5F 245 6T
45 19 95 2N 145 41 196 5G 246 6U
46 1A 96 2O 146 42 197 5H 247 6V
47 1B 97 2P 147 43 198 5I 248 6W
48 1C 98 2Q 148 44 199 5J 249 6X
49 1D 99 2R 149 45 200 5K 250 6Y

Continued on next page

B-2
Technical Manuals Online! - http://www.tech-man.com
Base 10 to Base 36 Conversion Table, Continued

Conversion Table
Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
251 6Z 301 8D 351 9R 401 B5 451 CJ
252 70 302 8E 352 9S 402 B6 452 CK
253 71 303 8F 353 9T 403 B7 453 CL
254 72 304 8G 354 9U 404 B8 454 CM
255 73 305 8H 355 9V 405 B9 455 CN
256 74 306 8I 356 9W 406 BA 456 CO
257 75 307 8J 357 9X 407 BB 457 CP
258 76 308 8K 358 9Y 408 BC 458 CQ
259 77 309 8L 359 9Z 409 BD 459 CR
260 78 310 8M 360 A0 410 BE 460 CS
261 79 311 8N 361 A1 411 BF 461 CT
262 7A 312 8O 362 A2 412 BG 462 CU
263 7B 313 8P 363 A3 413 BH 463 CV
264 7C 314 8Q 364 A4 414 BI 464 CW
265 7D 315 8R 365 A5 415 BJ 465 CX
266 7E 316 8S 366 A6 416 BK 466 CY
267 7F 317 8T 367 A7 417 BL 467 CZ
268 7G 318 8U 368 A8 418 BM 468 D0
269 7H 319 8V 369 A9 419 BN 469 D1
270 7I 320 8W 370 AA 420 BO 470 D2
271 7J 321 8X 371 AB 421 BP 471 D3
272 7K 322 8Y 372 AC 422 BQ 472 D4
273 7L 323 8Z 373 AD 423 BR 473 D5
274 7M 324 90 374 AE 424 BS 474 D6
275 7N 325 91 375 AF 425 BT 475 D7
276 7O 326 92 376 AG 426 BU 476 D8
277 7P 327 93 377 AH 427 BV 477 D9
278 7Q 328 94 378 AI 428 BW 478 DA
279 7R 329 95 379 AJ 429 BX 479 DB
280 7S 330 96 380 AK 430 BY 480 DC
281 7T 331 97 381 AL 431 BZ 481 DD
282 7U 332 98 382 AM 432 C0 482 DE
283 7V 333 99 383 AN 433 C1 483 DF
284 7W 334 9A 384 AO 434 C2 484 DG
285 7X 335 9B 385 AP 435 C3 485 DH
286 7Y 336 9C 386 AQ 436 C4 486 DI
287 7Z 337 9D 387 AR 437 C5 487 DJ
288 80 338 9E 388 AS 438 C6 488 DK
289 81 339 9F 389 AT 439 C7 489 DL
290 82 340 9G 390 AU 440 C8 490 DM
291 83 341 9H 391 AV 441 C9 491 DN
292 84 342 9I 392 AW 442 CA 492 DO
293 85 343 9J 393 AX 443 CB 493 DP
294 86 344 9K 394 AY 444 CC 494 DQ
295 87 345 9L 395 AZ 445 CD 495 DR
296 88 346 9M 396 B0 446 CE 496 DS
297 89 347 9N 397 B1 447 CF 497 DT
298 8A 348 9O 398 B2 448 CG 498 DU
299 8B 349 9P 399 B3 449 CH 499 DV
300 8C 350 9Q 400 B4 450 CI 500 DW

Continued on next page

B-3
Technical Manuals Online! - http://www.tech-man.com
Base 10 to Base 36 Conversion Table, Continued

Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
501 DX 551 FB 601 GP
502 DY 552 FC 602 GQ
503 DZ 553 FD 603 GR
504 E0 554 FE 604 GS
505 E1 555 FF 605 GT
506 E2 556 FG 606 GU
507 E3 557 FH 607 GV
508 E4 558 FI 608 GW
509 E5 559 FJ 609 GX
510 E6 560 FK 610 GY
511 E7 561 FL 611 GZ
512 E8 562 FM 612 H0
513 E9 563 FN 613 H1
514 EA 564 FO 614 H2
515 EB 565 FP 615 H3
516 EC 566 FQ 616 H4
517 ED 567 FR 617 H5
518 EE 568 FS 618 H6
519 EF 569 FT 619 H7
520 EG 570 FU 620 H8
521 EH 571 FV 621 H9
522 EI 572 FW 622 HA
523 EJ 573 FX 623 HB
524 EK 574 FY 624 HC
525 EL 575 FZ 625 HD
526 EM 576 G0 626 HE
527 EN 577 G1 627 HF
528 EO 578 G2 628 HG
529 EP 579 G3 629 HH
530 EQ 580 G4 630 HI
531 ER 581 G5 631 HJ
532 ES 582 G6 632 HK
533 ET 583 G7 633 HL
534 EU 584 G8 634 HM
535 EV 585 G9 635 HN
536 EW 586 GA 636 HO
537 EX 587 GB 637 HP
538 EY 588 GC 638 HQ
539 EZ 589 GD 639 HR
540 F0 590 GE 640 HS
541 F1 591 GF 641 HT
542 F2 592 GG 642 HU
543 F3 593 GH 643 HV
544 F4 594 GI 644 HW
545 F5 595 GJ 645 HX
546 F6 596 GK 646 HY
547 F7 597 GL 647 HZ
548 F8 598 GM 648 I0
549 F9 599 GN 649 I1
550 FA 600 GO 650 I2

B-4
Technical Manuals Online! - http://www.tech-man.com
Index

programming, 6-1
programming 24 point I/O, 6-32
Misc. programming AUX relay, 6-11
24 point I/O card, 6-32 programming IDNet, 6-13
24 point I/O cards programming master controller, 6-5
output points, 6-36 programming NAC card, 6-9
4009 IDNet NAC Extender, 1-6 programming pseudo point cards, 6-16
4120 network card CD-ROM
programming, 6-29 installing on a system without, 2-4
installing programmer from CD-ROM, 2-7
CFIG
A building, 11-2
access levels, 5-9 downloading to panel, 11-3
active status reminder system option, 5-7 class A NACs, 6-9
adding cards, 6-4 class B NACs, 6-9
AHJ alarm city circuit programming, 1-7 communication parameters
AHU stagger start system option, 5-5 setting, 3-2
alarm cutout timer system option, 5-4 custom control
alarm pseudo point, 6-18 adding an equation, 10-6
alarm silence/inhibit system option, 5-4 adding inputs and outputs, 10-7
analog system pseudos, 6-18 editing input properties, 10-8
analog user pseudos, 6-19 editing output properties, 10-19
point types for, 6-20 input opcodes, 10-10
AND operator, 10-4 output opcodes, 10-19
archiving jobs, 4-13 overview of equation, 10-4
AutoFill custom control tab, 1-3
and card tab, 6-3 overview, 10-2
and point tab, 7-3 custom labels, 7-11
AUX relay for AUX relays, 6-12
custom labels for, 6-12 for NACs, 6-10
point types for, 6-12 spell check for, 7-3
programming, 6-11
D
B day/night programming, 1-6
backing up jobs, 4-13 deleting cards, 6-4
Base 36 conversion, 4-6 depleted battery system option, 5-4
battery charger trouble, 1-6 and suppression release, 5-6
baud rate, 3-3 device types, 7-5
BIN file, 3-1 for IDNet points, 6-14
connecting download cable, 3-2 NAC, 6-9
default directory for, 3-6 summary of, 1
downloading to panel, 3-1 digital system pseudos, 6-16
required download components, 3-1 door drop on AC fail system option, 5-5
when to download. See door drop on alarm system option, 5-5
building a job, 11-2 download
and warm start, 3-8
BIN file, 3-1
C communication parameters, 3-2
connecting cable, 3-2
card tab, 1-3
connecting cable for, 11-4
and AutoFill, 6-3
enabling on panel, 11-4
overview, 6-2
enabling panel for, 3-4
cards
procedure for, 3-6
4120 network, 6-29
required cable, 3-2
adding and deleting, 6-4
warning about backup and archive, 3-5
dual RS-232 card, 6-22
downloading a CFIG
LCD annunciator, 6-37

IN-1
Technical Manuals Online! - http://www.tech-man.com
downloading to panel, 11-3 defined, 9-3
list tab, 1-3
overview, 8-2
E sorting points within, 8-3
Earth ground detect lists
user-defined LED example, 6-7 adding/deleting points, 8-4
EXEC. See BIN file naming, 8-4
existing jobs
opening, 4-7 M
master controller card, 6-5
F menu structure, 1-4
F4 key, 6-3 menus, 1-2
firmware
and compatibility, 1-8 N
floppy disks, 2-4
installing programmer from, 2-7 NACs
function keys and signal operation system option, 5-7
programming user-defined, 6-7 custom labels for, 6-10
device types for, 6-9
point types for, 6-10
G programming NAC card, 6-9
general information
setting, 5-2 O
OR operator, 10-5
I oswitch point type, 6-32
icons, 1-2 overview, 1-1
summary of functions, 1-4 programmer components, 1-2
IDNet card
device types for, 6-14 P
point types for, 6-15
programming, 6-13 panel
installation, 2-1 and Quick CFIG, 4-2
creating floppy disks, 2-4 setting baud rate, 3-3
installing programmer from CD-ROM, 2-7 panel tab, 1-3
required components, 2-1 and general information, 5-3
system requirements, 2-2 and system options, 5-3
passcodes, 5-9
point addresses
J summary of, 1
job number format, 4-6 point tab, 1-3
jobs overview of, 7-2
and older SFIO components, 1-9 point types
archiving, 4-13 24 point I/O input types, 6-32
backing up, 4-13 24 point I/O output types, 6-36
building and downloading, 11-2 defined, 7-8
creating a new job, 4-5 for 24 point I/O, 6-32
downloading to panel, 11-3 for analog user pseudos, 6-20
format of job number, 4-6 for AUX relay, 6-12
opening an existing, 4-7 for IDNet points, 6-15
restoring, 4-13 for user digital pseudos, 6-18
saving, 4-13 NAC, 6-10
uploading from panel, 4-8 summary of, 1
programmer
features of each version, 1-8
L starting, 4-4
LCD annunciator, 6-37 warning about suppression point types, 5-6
leaf pseudo points, 6-16
defined, 9-3 analog system pseudos, 6-18
level analog user pseudos, 6-19

IN-2
Technical Manuals Online! - http://www.tech-man.com
digital system pseudos, 6-16 system defined list pseudos, 6-20
system defined list pseudos, 6-20 system options, 5-3
user digital pseudos, 6-17 active status reminder, 5-7
user-defined list pseudo points, 6-21 AHU stagger start, 5-5
alarm cutout timer, 5-4
alarm silence inhibit, 5-4
Q depleted battery, 5-4
QALERT device type, 1-7 door drop on AC fail, 5-5
Quick CFIG, 1-7 door drop on alarm, 5-5
procedure for new panels, 4-2 signal operation, 5-7
TrueAlert Non-Addressable NAC devices, 1-7 suppression release, 5-6
alarm operation, 1-7 time format, 5-3
and Quick CFIG, 1-7
and signal operation system option, 5-7 T
horn operation for, 1-7
SMPL programming of, 1-7 tabs, 1-2
overview of, 1-3
time format system option, 5-3
R trouble pseudo point, 6-18
related documents, 1-1 tswitch point type, 6-32
restoring jobs, 4-13
RS-232 card U
configuring, 6-22
RS-232 service modem card upgrade, 2-1, 2-7
programming, 6-24 compatibility, 1-8
service modem commands for, 6-26 uploading jobs, 4-8
and baud rate, 4-8
communication parameters, 4-8
S procedure for, 4-8
saving jobs, 4-13 user digital pseudos, 6-17
setting baud rate, 3-3 point types for, 6-18
SFIO board user-defined function keys, 6-7
and compatibility, 1-8 user-defined LED
SFIO card, 6-5 Earth ground detect example, 6-7
programming user-defined function keys, 6-7 waterflow indicator example, 6-6
programming user-defined LEDs on, 6-5 user-defined LEDs, 6-5
signal operation system option, 5-7 user-defined list pseudos, 6-21
single station uswitch point type, 6-32
setting, 6-15 utility pseudo point, 6-18
site tab, 1-3 utility temperature sensing, 1-6
overview, 9-3
site tree V
building, 9-5
overview, 9-2 Version 2.x features, 1-6
SMPL programming
QALERT device type, 1-7
software key, 2-3
W
SQALERT device type, 1-7 warm start
sswitch point type, 6-32 and download, 3-8
stagger start system option, 5-5 waterflow indicator
starting the programmer, 4-4 user-defined LED example, 6-6
supervisory pseudo point, 6-18
suppression release system option, 5-6

IN-3
Technical Manuals Online! - http://www.tech-man.com
This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com


This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com


Rev. C Simplex Time Recorder Co., Simplex Plaza Westminster, Massachusetts 01441-0001 U.S.A. 574-187
Simplex International Time Equipment, Co., LTD. Mississauga, Ontario, Canada

Technical Manuals Online! - http://www.tech-man.com

Vous aimerez peut-être aussi