Vous êtes sur la page 1sur 3

NO.

OF PUMPS RUNNING = 1 pump(s)

Total Curve points Pipes and fittinges inside pumping station Maine pipe and fittinges outide pumping station
DATA
flow total total loss local loss loss local loss
Qm l/s Qb l/s V m/s RE F dH m V m/s RE F dH m
NO. OF PUMPS 1 loss m head m m/m loss m m/m loss m
G. head (m) 14 0.1 0.00 14.00 0.1 0.0008 318.30989 0.0975478 8E-09 9E-08 1E-07 2E-07 0.00035 212.206591 0.114773 1.22E-09 1E-05 4E-08 1E-05
D. mm (inside) 400 20.0 0.10 14.10 20 0.1592 63661.977 0.0199101 6E-05 0.0008 0.0048 0.0055 0.07074 42441.3182 0.021658 9.21E-06 0.0892 0.00171 0.0909
K mm (inside) 0.01 40.0 0.34 14.34 40 0.3183 127324 0.0172688 0.0002 0.0027 0.0191 0.0218 0.14147 84882.6363 0.01862 3.17E-05 0.30676 0.00683 0.3136

inside pumping station


L. m (inside) 12 60.0 0.70 14.70 60 0.4775 190985.93 0.0159757 0.0005 0.0056 0.043 0.0486 0.21221 127323.954 0.017125 6.55E-05 0.63478 0.01538 0.6502
gate valve 0.2 1 80.0 1.18 15.18 80 0.6366 254647.91 0.0151553 0.0008 0.0094 0.0764 0.0858 0.28294 169765.273 0.016169 0.00011 1.0655 0.02734 1.0928
check valve 2.0 1 100.0 1.77 15.77 100 0.7958 318309.89 0.0145698 0.0012 0.0141 0.1194 0.1335 0.35368 212206.591 0.015481 0.00016 1.59404 0.04272 1.6368
elbow 90 d. 0.3 2 120.0 2.47 16.47 120 0.9549 381971.86 0.0141225 0.0016 0.0197 0.172 0.1917 0.42441 254647.909 0.014952 0.00023 2.21687 0.06151 2.2784
tee 0.9 1 140.0 3.28 17.28 140 1.1141 445633.84 0.013765 0.0022 0.0261 0.2341 0.2602 0.49515 297089.227 0.014525 0.0003 2.93126 0.08372 3.015
other 0 160.0 4.18 18.18 160 1.2732 509295.82 0.0134703 0.0028 0.0334 0.3057 0.3391 0.56588 339530.545 0.01417 0.00039 3.73503 0.10935 3.8444
total local factors 3.7 180.0 5.19 19.19 180 1.4324 572957.8 0.0132216 0.0035 0.0415 0.3869 0.4284 0.63662 381971.863 0.013868 0.00048 4.62635 0.1384 4.7648
D. mm (out) 600 200.0 6.30 20.30 200 1.5915 636619.77 0.0130077 0.0042 0.0504 0.4777 0.5281 0.70736 424413.182 0.013606 0.00058 5.60367 0.17086 5.7745
K mm (out) 0.0025 220.0 7.51 21.51 220 1.7507 700281.75 0.0128212 0.005 0.0601 0.578 0.6381 0.77809 466854.5 0.013375 0.00069 6.66564 0.20675 6.8724
outside pumping station

L. m (out) 9690 240.0 8.82 22.82 240 1.9099 763943.73 0.0126565 0.0059 0.0706 0.6879 0.7585 0.84883 509295.818 0.01317 0.00081 7.81108 0.24604 8.0571
gate valve 0.2 11 260.0 10.22 24.22 260 2.069 827605.7 0.0125097 0.0068 0.0819 0.8073 0.8892 0.91956 551737.136 0.012986 0.00093 9.03892 0.28876 9.3277
check valve 2.0 1 280.0 11.71 25.71 280 2.2282 891267.68 0.0123777 0.0078 0.094 0.9363 1.0302 0.9903 594178.454 0.012819 0.00107 10.3482 0.33489 10.683
elbow 90 d. 0.3 300.0 13.30 27.30 300 2.3873 954929.66 0.0122583 0.0089 0.1068 1.0748 1.1816 1.06103 636619.772 0.012667 0.00121 11.7381 0.38444 12.123
elbow 45 d. 0.1 16 320.0 14.99 28.99 320 2.5465 1018592 0.0121494 0.01 0.1205 1.2229 1.3433 1.13177 679061.091 0.012527 0.00136 13.2079 0.43741 13.645
Outlet 0.9 1 340.0 16.77 30.77 340 2.7056 1082254 0.0120497 0.0112 0.1349 1.3805 1.5154 1.2025 721502.409 0.012398 0.00152 14.7567 0.4938 15.251
total local factors 6.7 TABLE ( A ) CALCULATIONS USING COLBROOK formola

NO. OF PUMPS RUNNING = 2 pump(s)

Total Curve points Pipes and fittinges inside pumping station Maine pipe and fittinges outide pumping station
DATA
flow total total loss local loss loss local loss
Qm l/s Qb l/s V m/s RE F dH m V m/s RE F dH m
NO. OF PUMPS 2 loss m head m m/m loss m m/m loss m
G. head (m) 14 0.1 0.00 14.00 0.05 0.0004 159.15494 0.1331562 3E-09 3E-08 3E-08 6E-08 0.00035 212.206591 0.117799 1.25E-09 1E-05 4E-08 1E-05
D. mm (inside) 400 30.0 0.19 14.19 15 0.1194 47746.483 0.0211943 4E-05 0.0005 0.0027 0.0031 0.1061 63661.9772 0.019844 1.9E-05 0.18389 0.00384 0.1877
K mm (inside) 0.01 60.0 0.66 14.66 30 0.2387 95492.966 0.0182938 0.0001 0.0016 0.0107 0.0123 0.21221 127323.954 0.017154 6.56E-05 0.63587 0.01538 0.6512
inside pumping station

L. m (inside) 12 90.0 1.38 15.38 45 0.3581 143239.45 0.0168757 0.0003 0.0033 0.0242 0.0275 0.31831 190985.932 0.015824 0.00014 1.31976 0.0346 1.3544
gate valve 0.2 1 120.0 2.33 16.33 60 0.4775 190985.93 0.0159757 0.0005 0.0056 0.043 0.0486 0.42441 254647.909 0.014972 0.00023 2.21985 0.06151 2.2814
check valve 2.0 1 150.0 3.50 17.50 75 0.5968 238732.41 0.0153328 0.0007 0.0084 0.0672 0.0755 0.53052 318309.886 0.014358 0.00034 3.32621 0.09611 3.4223
elbow 90 d. 0.3 2 180.0 4.88 18.88 90 0.7162 286478.9 0.0148409 0.001 0.0116 0.0967 0.1084 0.63662 381971.863 0.013884 0.00048 4.6317 0.1384 4.7701
tee 0.9 1 210.0 6.47 20.47 105 0.8356 334225.38 0.0144474 0.0013 0.0154 0.1317 0.1471 0.74272 445633.841 0.013502 0.00063 6.13081 0.18838 6.3192
other 0.9 0 240.0 8.26 22.26 120 0.9549 381971.86 0.0141225 0.0016 0.0197 0.172 0.1917 0.84883 509295.818 0.013184 0.00081 7.81912 0.24604 8.0652
total local factors 3.7 270.0 10.25 24.25 135 1.0743 429718.35 0.0138477 0.002 0.0244 0.2176 0.2421 0.95493 572957.795 0.012913 0.001 9.69293 0.3114 10.004
D. mm (out) 0.9 600 300.0 12.43 26.43 150 1.1937 477464.83 0.0136111 0.0025 0.0297 0.2687 0.2984 1.06103 636619.772 0.012679 0.00121 11.7491 0.38444 12.134
K mm (out) 0.9 0.0025 330.0 14.81 28.81 165 1.313 525211.31 0.0134044 0.0029 0.0353 0.3251 0.3605 1.16714 700281.75 0.012472 0.00144 13.9849 0.46518 14.45
outside pumping station

L. m (out) 0.9 9690 360.0 17.38 31.38 180 1.4324 572957.8 0.0132216 0.0035 0.0415 0.3869 0.4284 1.27324 763943.727 0.012288 0.00169 16.3981 0.5536 16.952
gate valve 0.2 11 390.0 20.14 34.14 195 1.5518 620704.28 0.0130584 0.004 0.0481 0.4541 0.5022 1.37934 827605.704 0.012123 0.00196 18.9863 0.64971 19.636
check valve 2.0 1 420.0 23.08 37.08 210 1.6711 668450.76 0.0129114 0.0046 0.0551 0.5266 0.5818 1.48545 891267.681 0.011974 0.00224 21.7478 0.75351 22.501
elbow 90 d. 0.3 0 450.0 26.21 40.21 225 1.7905 716197.24 0.0127781 0.0052 0.0626 0.6046 0.6672 1.59155 954929.659 0.011837 0.00255 24.6809 0.865 25.546
outside pumping station

elbow 45 d. 0.1 16 480.0 29.53 43.53 240 1.9099 763943.73 0.0126565 0.0059 0.0706 0.6879 0.7585 1.69765 1018591.64 0.011712 0.00287 27.7839 0.98418 28.768
elbow 45 d. 0.9 1 510.0 33.02 47.02 255 2.0292 811690.21 0.0125449 0.0066 0.079 0.7765 0.8555 1.80376 1082253.61 0.011596 0.0032 31.0554 1.11104 32.166
total local factors 6.7 TABLE ( A ) CALCULATIONS USING COLBROOK formola
Pumps operation curves with system curves for force main pipe 1 pump system curve

including the losses inside the station ( studied by LAMAH EST.) 2 pumps system curve

PUMP MODEL : GRUNDFOS/SARLIN S2-1004 AM1 1 pump curve


2 pumps curve
60

50

40
Head (m)

30

20

10

0
0 50 100 150 200 250 300 350 400 450 500
Flow rate (l/s)

Vous aimerez peut-être aussi