A Slide No 1
Index

1. COFEM Presentation

2. Certifications and CE mark

3. Installation Design

4. CONVENTIONAL
Fire detection and Fire Alarm System
Conventional Systems
y features
CLVR and LONDON Modeles

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 2
Index

5. ANALOGUE & ADDRESSABLE


Fire detection and Fire Alarm System
Analogue and Addressable System Features
LYON, Compact-LYON and ZAFIR Models

6. CO Detection System COSENSOR


Control Panels
Detectors DCO and DNO2

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 3
COFEM Presentation

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 4
1 Cofem Presentation (1/9)
1.

- COFEM,
COFEM s.a,
s a is a Spanish Fire Protection
Manufacturer with more than 40 years at the market.

- We have a large variety of products, but the core of our activity is


manufacturing our Fire Detection and Fire Alarm Systems

Principal activity areas:


1. Fire Detectiona and Fire Alarm Systems
2. Carbon Monoxide (CO) Detection Systems for Parkings.
3. Fire Hose Cabinets.
4. Domestic combustible gas detection
(butane gas, town gas, etc).
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 5
1 Cofem Presentation (2/9)
1.

COFEM, s.a, is committed to the Fire Protection:

1) Takes part as member in TECNIFUEGO AESPI


Th
The Spanish
S i h Fire
Fi Protection
P t ti Association,
A i ti which
hi h
work close with the Spanish Ministery in the Fire protection regulation.

2) Hold the chairmanship of CTN23/SC3 of AENOR


Spanish Standard Body for Fire Detection and Fire Alarm
which allow managing standards as UNE 23007-14
23007 14 for
Spanish fire detection and fire alarm installation

3) COFEM is the Spanish representative at CEN/TC72.


European organization which develop the mandatory EN 54
Standards and CE mark under Construction Product Directive
(89/106/CEE)

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 6
1 Cofem Presentation (3/9)
1.

COFEM offers:
ff

- Experience of more than 40 years,

- Knowledge regarding international Standards,


EN 671
EN 54
EN 12094

- Expertice
p technical equipment
q p

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 7
1 Cofem Presentation (4/9)
1.

T our customers for:


To f

1) S
Support
t Assitance,
A it

2) Training courses,

3) Fire / CO Design Installations,

4) ON-LINE SW Configuration

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 8
1 Cofem Presentation (5/9)
1.

These allow us exportion of our products in more than


40 countries in 4 continents.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 9
1 Cofem Presentation (6/9)
1.

Some COFEM references:


Thermal Solar Power Plant Valle 1 and Valle 2 at Cadiz:
Installation of 2 Fire Control Panels with 4 loops, Fire detectors,
Hidrogen
g detectors, Flame detectors, Thermal p probes,
Extinguishing Control Panels, etc.

Ferrari Store at Las Rozas Madrid

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 10
1 Cofem Presentation (7/9)
1.

Some COFEM references ((Cont):


)
Heineken
Headquarter
at Madrid

Cala dOr
Camper
Camper Headquarter
Headquarter Hotel
at Mallorca at Mallorca
(Shoes Factory)

Hercules Towers
at Los Barrios Cadiz
(Offices buiding)
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 11
1 Cofem Presentation (8/9)
1.
Beatriz Atlantis SPA Hotel
Some COFEM references ((Cont):
) at Puerto de la Cruz - Canary Islands

Faculty of
Informatics
at Madrid

Caldea thermal-ludic
El Pozo Factory at Alama de Murcia
Hotel at Andorra la Vella
(Food Factory) Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 12
1 Cofem Presentation (9/9)
1.

Some COFEM references ((Cont):


)

Eroski Bernasud at Barcelona Kindergarten


(Shopping mall) Marco Aldany at Madrid El Bercial at Getafe
(hairdressing and aesthetic shop)
Sato Sport Ramon Llull University
at Sevilla att Barcelona
B l

Campana Refinery
In Argentina

Tvoli Theater
MRW Transports at Barcelona
at Coslada High Speed Train AVE Station at Zaragoza
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 13
Certifications and CE mark

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 14
2 Certification and CE mark
2.
2.1.- Main European Union Policies

- UE is
i establieshed
bli h d with
i h the
h purpose off allow:
ll

1) Free movement of goods,

2) Free movement of people,

3) Free movements of capitals,


capitals

4) Free establishment of services,

Erase/Delete:
- Phisical barriers,
barriers
- Tariffs or quotes
-Thecnical Standards diferences
-and Conformity Evaluation means

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 15
2 Certification and CE mark
2.
2.2.- European Union Directives

- Based on a Spacific purposes, UE establieshes a law tool to


harmonize all products.

The Directives
- Low
L V lt
Voltage
- Simple Pressure Vessels
- Safety
S f t off Toys
T
- Construction Product
- Electromagnetic
El t ti Compatiblity
C tiblit
- ()
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 16
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (1/4)

1) Application field:
- Any
ypproduct which is pproduced for incorporation
p in a
permanent manner in construction works, including both
buildings and civil engineering works

- Fire Detection and Fire Alarm Systems are included.

2) Essential Requirements of the products:


- The essential requirements of the products which allow them
free movement inside the EU Countries will be introduced in
HARMONIZE STANDARDS

- CEN/TC72, The European Standarization Body, is in charge of


making these estandards =>

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 17
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (2/4)

3) Evaluation of Conformity:
- Define the means which assure that one product fulfill the

ms
essencial requirements

Alarm System
e Detection
Manufacture Approval Body Tasks

and
System CE Marking Documents
Tasks (Certification Based on:)

4 ITT N/A MDOC

Fire

Fire A
FPC

3 FPC ITT MDOC

2 ITT inicial FPC MDOC


FPC FPC Certification

2+ ITT FPC Initial Inspection MDOC


FPC FPC Periodic Inspection FPC Certification
Product Tests according to a Test Plan

1 FPC ITT MDOC


Product Tests according to a FPC Initial Inspection FPC Certification
Test Plan FPC Periodic Inspection

1+ FPC ITT MDOC


Product Tests according to a Test Plan FPC Initial Inspection FPC Certification
FPC Periodic Inspection
Factory or market product test

ITT: Initial Type Test


FPC: Factory Production Control
MDOC: Manufacturer Declaration of Conformity

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 18
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (3/4)
4) CE Mark:
- The products which incorporate the Essential Requirements
and Evaluation of Conformity shall affix the CE mark.

- EU Countries shall allow free moviment of product with


CE marking.

- Conformity Bodies: Results of Test shall be considered


independent of the country carried out.

MANDATORY

Voluntary

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 19
2 Certification and CE mark
2.
2.3.- Construction Product Directive CPD (4/4)
5) Mandatory Standards:

- EN 54-2:1997/A1:2006 -> Control and Indicating Equipment


- EN 54-4:1998/A2:2006 -> Power Supply Equipments

- EN 54-3:2001/A1:2002 -> Fire Alarm Devices- Sounders


- EN 54-5:2000/A1:2002 -> Heat Detectors- Point Detectors
- EN 54-7:2000/A1:2002 -> Smoke Detectors- Point detectors using
g , transmitted light
scattered light, g or ionization
- EN 54-11:2001/A1:2005 -> Manual Call Points
- EN 54-17:2005 -> Short circuit isolators
- EN 54-18:2005
54 18:2005 ->
> Input/Output Devices
...

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 20
2 Certification and CE mark
2.
2.5.- Construction Product REGULATION CPR

- In 2013 July => CPR supersedes CPD

CPR Vs CPD:
1)) Name of documents are changed.
g

2) CPR with Better explanations.

3) More flexibility for small companies at documentation issues.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 21
2 Certification and CE mark
2.
2.6.- Summary

Mark is mandatory in all Europe Union

Other Marks are ONLY voluntary in EU

Products must be certified under EN54 Standard


under the EU aproved
p bodies

Mandatory EN54 standards are in the

OJEC NANDO and web

CPR supersedes CPD


Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 22
Installation Design

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 23
3 Installation Design
3.
3.1.- Introduction

- The rules for Installation of equipments are not covered


by EU agreements.

- Each Country has its own design standard

- EU
U has
as pub
published
s ed TS54-14
S5 ((Technical
ec ca Spec
Specification
cat o as a
an European
u opea
recommendation)

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 24
3 Installation Design
3.
3.2.- Recommendation (1/14)

- Hereafter there are design recommendation for


the Fire detection and Fire Alarm System

SUMMARY
1. Detection Zones and Alarm Zones.
2. Fault efects limitations.
3. Detectors distribution
4. Manual Call Point distribution
5
5. Fire Alarm devices distribution
6. Cables

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 25
3 Installation Design
3.
3.2.- Recommendation (2/14)

1
1. D t ti
Detection and
d Al
Alarm Z
Zones
a. Detection Zones
The division of the premises/bilding in Detection Zones should
comply with:
- Floor Area 1600 m2
- Areas with more than 5 rooms:
Remote indicator above the doors or,
Room indication at the Control Panel.
- Zones with more than 1 fire compartment :
Zone limits should be the fire compartment, and
Zone Area 400 m2
- Zone should be limited to one floor, unless:
Stairwell,
St i ll lightwell,
li ht ll liftwell,
lift ll etc,
t but
b t inside
i id one fire
fi compartment.
t t
Building total Area 300 m2

b
b. Alarm Zones
According to Fire alarm response strategy.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 26
3 Installation Design
3.
3.2.- Recommendation (3/14)

2
2. Fault efect limitations
a. A single cable fault can afect only to one function by zone:
- Automatic detection,
- Manual Call points,
- Fire Alarm devices,
- Input/Output devices,
- Auxiliary devices,
- AND NOT more than 32 detectors or 10 Manual call points,
- Neither losing all Fire alarm devides in the building (At least one
device should work )

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 27
3 Installation Design
3.
3.2.- Recommendation (4/14)
One own output per zone for automatic detection and Manual call points
2 Fire Alarm device per each Zone and
1) 1) There
Zone <should
1600 mbe
Conventional 2) 2) Neither
AND it shouldZones losing
NOTwith
be lost
moteall
moreFirethan
than alarm
32 devides
1 Fire in or
detectors the10building
Compartement manual call points,
Area:
Zones Area should be Fire compartment, and Zone Area 400 m2
Example Up to 10 Up to 32

FC: Fire Compartment

FC1 FC3
Zone 1

10 m

FC2

10 m
Zone2

20 m 20 m

Up to 10
Up to 32
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 28
3 Installation Design
3.
3.2.- Recommendation (5/14)

2
2. F l efect
Fault f limitations
li i i (Cont)
(C )

b. Two faults per circuit should not loss detector, manual call points and
alarm devices in:
- Area > 10 000 m2 .
- Area > 5 Fire compartments
compartments.
Fire compartments

Loop
p1

Loop 2

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 29
3 Installation Design
3.
3.2.- Recommendation (6/14)
- 32 elements between isolators
Addressable - Only one functionality between isolators
Example - At least 1 alarm device per Zone
- Area < 10000 m2 neither 5 Fire compartments FC: Fire Compartment

FC1 FC3

10 m

FC2
Zone 1 Zone 2
1m

20 m 20 m

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 30
3 Installation Design
3.
3.2.- Recommendation (7/14)
Smoke
3
3. D t t
Detectors distribution
di t ib ti
Detector
Premises Area (m2) Detector Type Premises Ceiling Slope 20 Ceiling Slope 20
Height (m) SV (m2) Dmx. (m) SV (m2) Dmx. (m)
SL 80 UNE-EN 54-7 12 80 6,3
, 80 6,3
,
SL 80 UNE-EN 54-7 6 60 5,5 90 6,7
6 h 12 80 6,3 110 7,4
SL 30 UNE-EN 54-5, Clase A1 7,5 30 3,9 30 3,9
UNE-EN 54-5, Clase A2, 6 30 3,9 30 3,9
B, C, D, E, F, G
SL 30 UNE-EN 54-5, Clase A1 7,5 20 3,2 40 4,5
UNE-EN 54-5, Clase A2, 6 20 3,2 40 4,5
B, C, D, E, F, G

Heat Detector

- In Extinguishing zones, protected area should be halving.


- Sited without obstacles 50 cm around.
- Room dividers with less than 30 cm to ceiling => diferent rooms.
rooms
- Air ducts, etc, with more than 25 cm to ceiling => Partitioning is not afected.
- Detection should be considered in false floors and false ceilings.
g
- Beam detector: Height 25 m; Separation between beams 7,5 m;

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 31
3 Installation Design
3.
3.2.- Recommendation (8/14)

4
4. M
Manual
lCCall
ll P
Points
i t

Each 25 m of evacuation route.


Height: Between 1,2 and 1,6 m. Considering people with disabilities: 0,9 1,2
m).

5. Fire alarm devices

Protected area should be divided in Alarm zones and be operated according


with the Fire Alarm Response Strategy (Evacuation plan).

Minimum sound level should be 65 dB(A) at any point (75 dB(A) if the objetive
is to wake up sleeping people) or 5 additional db(A) over the ambient noise.
Maximum sound level should be 120 dB(A).

If sound
d level
l l exceed
d 60 dB(A) because
b off noise
i ambiente,
bi t Fire
Fi alarm
l signal
i l
should be sound and light.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 32
3 Installation Design
3.
3.2.- Recommendation (9/14)

5
5. Fi Alarm
Fire Al device
d i (Cont)
(C t)

According with Fire Alarm Strategy, it should be installed acoustic-optical


outdoor sounder to signaling the entry of Fire brigade, or outside indication of
the Alarm status of the premises/building.

It should
h ld bbe a minimum
i i off 2 sounders
d in
i the
th building,
b ildi and
d att least
l t 1 per Fire
Fi
Compartment and Detection zone.
Sound Level Distance
(dB-(A)) (m)
It should not be more than 1 door between a
120 1
sounder and anyplace where it should be heard.
114 2
108 4
G
General
l acoustic
ti approuches:
h
102 8
Each time it is doubled the distance, you lose 6 dBs,
30 dBs are lost for every Fire door, 96 16
20 dBs are lost for every standard door
door. 90 32
84 64

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 33
3 Installation Design
3.
3.2.- Recommendation (10/14)
Minimum of 2 sounders in the building, and at least
1 per Fire Compartment and Detection zone.
Conventional
Example Up to 10 Up to 32

FC: Fire Compartment

FC1 FC3
Zone 1

10 m

FC2

10 m
Zone2

20 m 20 m

Up to 10
Up to 32
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 34
3 Installation Design
3.
3.2.- Recommendation (11/14)
Minimum of 2 sounders in the building, and at least
1 per Fire Compartment and Detection zone.
Addressable
Example
FC: Fire Compartment

FC1 FC3

10 m

FC2
Zone 1 Zone 2
1m

20 m 20 m

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 35
3 Installation Design
3.
3.2.- Recommendation (12/14)

6
6. C bl
Cables

Cables according with Manufacturer instructions (section, twist, shield, etc).

Cable should be Fire resistant when:


It crosses a zone which it has not fire detection and a fault here implies loses in:
the reception of fire detection signals
Actuation of the Fire System
Operation of Fire alarm devices
Communication with Repeaters Cables

Those cables that needs to work for


Standard
more than 1 minute after detection of a fire:
Sounders and its feed
Repeaters Fire
Resistant
Extinguishing

In Loops:
Cable should be fire protected when faults
could affect more than 1 detection zone => If cable installation is routed for
different ways, it is acceptable using standard cables.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 36
3 Installation Design
3.
3.2.- Recommendation (13/14)
Operation of the Fire Alarm Devices
Conventional
Example Up to 10 Up to 32

FC: Fire Compartment

FC1 FC3
Zone 1

10 m

FC2

10 m
Zone2

20 m 20 m

Up to 10
Up to 32
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 37
3 Installation Design
3.
3.2.- Recommendation (14/14)
If cable installation is routed for different ways, it is acceptable using standard cables.
Those cables that needs to work for more than 1 minute after detection of a fire: Sounders and its feed
Addresable
Example
p FC: Fire Compartment

FC1 FC3

10 m

FC2
Zone 1 Zone 2
1m

20 m 20 m

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 38
CONVENTIONAL
Fire Detection and Fire Alarm Systems
CLVR and
LONDON

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 39
4 Conventional System
4.
4.1.- Conventional System features (1/2)

C
Conventional
ti l features
f t
- Detector/Manual Call Point proccesses the Alarm Status
- Detector/Manual Call Point communicates with Control panel establishing voltage levels
i the
in th communication
i ti line.
li

- Open Circuit Status 22,5V a 24V


Example: Control panel processes - Quiescent Status ..... 19V a 22,5V
- Detector
D t t Alarm
Al St t
Status 7V a 16V
- Manual Call Point Alarm Status ... 3,5V a 7V
- Cross circuit Status .. 0V a 3,5V

Zone1 .
Zone 2

Control Panel doesnt know detector or Manual call point it is in Alarm status.
Need of divide area in detection ZONES.
ZONES
System limited to 32 elements by Zone.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 40
4 Conventional System
4.
4.1.- Conventional System features (2/2)

COFEM Offers
Off 2 kind
ki d off Conventional
C ti l Control
C t l Panels
P l

COFEM
Conventional Control Panels

2 to 12 Zones
2 to 128 Zones/Relays

Conventional Extinguishing
E ti i hi
CLVRxxZ CLVR02EXT

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 41
4 Conventional System
4.
4.2.- CLVR: Models

- 5 models available:
Conventional
Control Panels
CLVR02Z
CLVR04Z
CLVR08Z
CLVR12Z Extinguishing
Control Panel

CLVR02EXT

Z: Zone
Model EXT EXTinguishing
EXT: EXTi i hi
Zones N

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 42
4 Conventional System
4.
4.3.- CLVR: Technical Features (1/4)
Up to 32 elements (with detectors and manual call
points) per zone.

1 monitored general SOUNDER output


output, delayable from
0 to 10 minutes.

1 immediate ALARM output through a dry NO/NC


contact (Normally open/Normally Closed).

1 monitored FAULT output,


p , delayable
y from 0 to 10
minutes, and protected by a fuse (CLVR08Z/ 12Z).

1 FAULT output through a dry NO/NC contact


(Normally open/Normally Close), deleyable from 0 to 10
minutes (CLVR02Z/ 04Z).

Two 30 V/DC monitored auxiliary outputs protected by


a fuse for external power supply (sounders, relay units,
etc.).
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 43
4 Conventional System
4.
4.3.- CLVR: Technical Features (2/4)
/ Default
D f lt Thresholds
Th h ld

It has a test mode for quickly and easy checking of


detectors and manual call points.

It allows threshol Zones configuration for Open line,


Detector Alarm and Manual Call Point Alarm for
Note: Last zone monitoring adjusting
j g with other detectors.
a pressure switch
it h

It allows configuration of the last zone as a monitoring


input of an external fire warning device being signaling
as Open line fault.

Metalic chest with 4 frontal bolted door and 4 predrills


of 28 mm and 1 rectangular at the chest back of 140 x
40 mm for electric wiring.

Space
S f 2 batteries
for b tt i off 7 Ah.
Ah

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 44
4 Conventional System
4.
4.3.- CLVR: Technical Features (3/4)

MODBUS Protocol with RS485 on demand.

Possibility of ON
ON-LINE
LINE Software in a PC using the MODBUS
functionallity

Systems
Integration

EN 54 Contact ID on Demand.
Demand

Certification with EN 54-2, EN 54-4 and EN12094-1 Standards.

EN 12094
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 45
4 Conventional System
4.
4.3.- CLVR: Technical Features (4/4)
3 Operation Modes at Extinguihing :
1) Standard Mode: Advance Warning Extinguishing
Output (R1) is activated by Zone 1 or Zone 2 in Alarm
Status.
2) Consecutive Mode: R1 output is activated intermittently
(1 s with Zone 1 or Zone 2 in Alarm status, 0.5 s with
both Zone 1 and 2 in Alarm Status and continuosly when
the delay of the Extinguishing Output (R2) has finished)
finished).
3) Simultaneous Mode: R1 output is activated when Zone
1 and 2 are both in Alarm Status.

1 Stop Extinguishing key and 1 Release Extinguishing key at


the Control Panel.

It allows instalalltion of Manual Extinguishing Stop Device and


Manual Extinguishing Release Device near the flood zone.

1 monitored Extinguishing output (called R2), delayable from


0 to 60 s , protected by resettable fuse.
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 46
4. Conventional System
4.4.- Detectors / Manual Call Points / PIAL / Bases

A30XT PUCAR
- Conventional Heat detector. - Conventional Manual Call Point.
- Absolute temperature (64C). - Resettable.
- Protec cover.
- Red led Alarm.
A30XV
- Conventional Rate of Rise Heat
detector. PIAL
- Temperature rate of rise and
absolute temperature (64
(64C)
C). - Remote action indicator.
- Allows installation on switchgear
boxes.
A30XH - High reliability through 2 red leds.
- Optical
p Smoke detector.
- It includes heat sensor (64C).
HIGH/LOW Bases
A30XHS
- High: Allows 20 mm electrical tube.
tube
- Optical Smoke detector.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 47
4 Convencional System
4.
4.5.- CLVR: Wiring Diagrama (1/2)

- General connection

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 48
4 Convencional System
4.
4.5.- CLVR: Wiring Diagram (2/2)

- Conection Schemes with Flame detectors/ Thermal Probes

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 49
4 Conventional System
4.
4.6.- LONDON: Technical features

- Base Control panel configurable up to 12 modules


and expandible up to 32 in an additional box.
box

- 4 Zones/Relays Module =>128 outputs between zones y relays.

- It allows up to 10 Repeaters.

- Configurable throught EasyLONDON Software instaled in a PC (RS232).

- 32 detectors / manual call points per zone.

- EN 54-2 and EN 54-4 Certified

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 50
4 Sistema Convencional
4.
4.7.- LONDON: Wiring Diagram
Module / Zones Card
Module / Relay Card

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 51
ANALOGUE and ADDRESSABLE
Fire detection and Fire Alarm System
LYON model

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 52
5 Addressable Lyon System
5.
5.1.- Addressable System features (1/2)

Add
Addressable
bl System
S t f t
features
- Each detector sends the measured value to Control panel in digital format.
- Control panel establish th quescient or Alarm status.
Detector is only a sensor.
Control panel knows all elements System is allowed with more than 32
elements if instaled in loop
p format ((according
g with standard))
Digital communication greatly increases the functionality of the system.

ANALOGUE LOGARITHMIC ADDRESSABLE DIGITAL


Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 53
5 Addressable Lyon System
5.
5.1.- Addressable Cofem System (2/2)

COFEM offers
ff 3 kind
ki d off C
Control
t l Panels
P l (Full
(F ll compatible
tibl between
b t th )
them)

Device Elements

Zafir:
Up to 2 loops Lyon:
Up to 199 devices per loop Up to 20 loops
Up to 199 devices per loop

C-Lyon:
Up to 2 loops
Up to 99 devices per loop

Loops Number
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 54
5. Addressable Lyon System
5.2.- Lyon control panel Technical Features

- Base
B control
t l panell configurable
fi bl up to
t 8 loops
l (199 elements
l t by
b loop).
l )
- Expandible up to 20 loops, using an additional box.
- Capacity for up to 99 zones.
- File that stores up to 4095 events with date and time.
- Outputs:
1) Monitored delayable general sounder (between 0 and 10 min),
2) non monitored alarm (Voltage free relay)
3) Fault, Monitored and delayable.
- Evacuation button.
- Backlit LCD display of 4 lines and 40 characters.
- Incorporates 7 languages by default.
- Configurable and manageable through PC-EASYcoNET software.
- Allows connection of up to 15 repeaters.
- Allows connection of up to 15 network control panels.
- MODBUS interface.
- EN 54-2 and EN 54-4 certified.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 55
5. Addressable Lyon System
5.3.- Aditional technical features

- 3 sensibility levels for heat and smoke sensors.

- Dirty warning in optical sensors for indicationg of


maintenance tasks.

- Addressable sounders directly feed from the loop.

- Independent programmation of sounders and relays.

- Programmation of sensor flashing.


flashing

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 56
5. Addressable Lyon System
5.4.- Sensors / Manual Call Point / PIAL / Bases (1/2)
A30XTA PUCAY
- Addressable Heat sensor. - Addressable Manual call point with
-Temperature rate of rise and isolator.
absolute temperature (64C). - Resettable
- Protective cover
A30XHA - Red led flash/fix
- Addressable Optical Smoke sensor.
- It includes heat sensor (64C) PIAL
- Remote action indicator.
- Allows installation on switchgear
boxes.
A30XHAS - High reliability through 2 red leds.
- Addressable Optical Smoke sensor.
sensor

A30XHTCO HIGH/LOW Bases


- Addressable Multisensor. - High: Allows 20 mm electrical tube.
Optical Smoke sensor.
Heat Sensor (64C).
CO sensor.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 57
5. Addressable Lyon System
5.4.- Detectores / Pulsador / PIAL / Zcalo (2/2)

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 58
5. Addressable Lyon System
5.5.- Modules / SIRAY / FAE /Repeater
KMAY MYOA
- Addressable Master module with isolator. - Addressable Relay and Technical
- Allows connection of conventional detectors and signal module with isolator.
manual call point (20 heat/ratre of rise or - R1 Relay monitored.
15 smoke/manual call points). - IN2 Closed contact as ALARM.
MDA1Y KABY
- Addressable 1 relay module with isolator.
- Loop isolator.
- 2 relays of simultaneous action from
- Inside High base..
Control p
panel.
- Maximum 70 per loop.
loop
- R1 Relay monitored.
- R2 Relay is NO/NC not monitorized. SIRAY
- Addressable sounder with isolator.
MDA2Y - Equivalence
E i l off 10 elements.
l t
- Addressable 2 relays module with isolator. - Programmed from Control panel.
- Relays programmed independently from - Maximum 6 or 10 per loop.
control panel. FAE 03 / 05
- Inside a chest.
MSTAY - FAE03: 3 A / FAE05: 5 A
- Addressable Thechnical signal module Repeater
with isolator.
isolator
- Up to 15.
- 2 NO/NC input signals monitored..
- Direct actions on the Control panel
- IN1 Closed contact as ALARM
(Alarm resets, faults, and general).
- IN2 Closed contact as FAULT. Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 59
5. Addressable Lyon System
5.6.- Wiring diagram (1/2)

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 60
5. Addressable Lyon System
5.6.- Wiring diagram (2/2) Manual Call Points
Zone

External Power Supply ONLY


for feeding the connected
external devices

Monitored outputs for sounders,


Ventilation, elevator actions,
etc

NOT Monitored outputs for


electromagnets, Detectors Zone
etc Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 61
5. Addressable Lyon
y System
y
5.7.- System capacity

Devices limit per Control Panel

Control Equivalence
Loop Element Logical
Reference Description Panel with loop
limit equivalence Relays
Limit Isolator

A30XHA Addressable optical-heat sensor 199 --- 1 --- ---


A30XHAS Addressable optical sensor 199 --- 1 --- ---
A30XTA Addressable heat sensor 199 --- 1 --- ---
Add
Addressable
bl optical-heat-monoxide
ti l h t id 1 --- ---
A30XHTCO 199 ---
multi-sensor
PUCAY Addressable Manual Call Point 70 --- 1 --- 1
KMAY Conventional zone master module 39 --- 5 --- 1
MDA2Y 2 Rela
Relayss module
mod le 16 99 5 2 1

MDA1Y 1 Relay module 32 199 5 1 1

MYOA Relay and Technical Signal module 32 199 5 1 1


MSTAY Technical signal module 70 --- 2 --- 1
KABY Loop Isolator module 70 --- --- --- 1
SIRAY/ SIRAYL Addressable sounder 10 99 10 1 1

Control Panel Limits:


a) 199 elements
elements, 32 logic relays and 70 isolators per loop.
loop
b) 20 loops, 199 logic relays per Control panel.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 62
5. Addressable Lyon
y System
y
5.8.- Configuration (1/7)

- Control panel knows all installed elements in the loop by their


programming number.

- Control panel doesnt know where are the elements located=>


=> Control panel needs to be configured.
configured

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 63
5. Addressable Lyon
y System
y
5.8.- Configuration (2/7)

A) Steps for Control panel configuration


1. Locate the elements. :
Loop Number, Element Number, and label (optional)
Bucle: 01

Element Programming Number Label Type Notes


Number

1 12757 ROOM 101 A30XHA

2 12432 ROOM 102 A30XHA

3 4767 HALL 1 FLOR PUCAY Drawing details


4 6982 CORRIDOR 2 FLOOR KMAY

Elements list

2. Configure Zones list and Element list that active relays (optional).

3. Configure general output Control panel parameters


a) Day/Night Mode
b) General Sounder Output
c) Fault Output
d) Autoevacuation
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 64
5. Addressable Lyon
y System
y
5.8.- Configuration (3/7)

B) Control panel Configuration


1) On the Control panel (with or without external keyboard)

2) EASY conNET (Basic version)

Easy Control panel programming from a PC in a windows environment.


PC-Control Panel conection through USB
Allows
All managementt off allll instalations
i t l ti
Avoid direct programming on the Control panel.
USB Software
port conexin
se(Basic version)
entregag en un CD con la central Lyon.
y

NOTE 1:Maximum USB wiring lengh 3 m

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 65
5. Addressable Lyon
y System
y
5.8.- Configuration (4/7)

Configuration advantages with the N of programming


1. Installer activities
A- Elements with MicroSwitch B- Elements with N
N of programming
1- Receive Installation drawing 1- Receive Installation drawing

2- Identification of N
2 N element insde the 2- Identifyy p
programming
g g number and p
place
loop of installation
3- Insert N element in binary codeinside 3- Physical installation
the device

4- Physical installation 4- Send information


(N of programming and place installed)
=> less
l execution
i error probability
b bili
=> Easier modifications/ expansions during the works and after it.
=> Responsibility transferred almost entirely to the programmer of the configuration
=> Eaisier to make start connections
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 66
5. Addressable Lyon
y System
y
5.8.- Configuration (5/7)

B) Control panel configuration


2) EASY coNET (Basic version) -Cont-
2.1 Configure Control panel
Number of Loop
Day/Night Mode
General Sounder output
Fault output
Autoevacuation

2.2 Configure elements

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 67
5. Addressable Lyon
y System
y
5.8.- Configuration (6/7)

B) Configuracin de la central (Cont)


2) EASY coNET (Basic version) -Cont-
2 3 Configure Realys
2.3
Type of performance (Sounder, Maneuvre, Relay)
Phisical situation
Delays (With delay/Immediate/Inactive)
Detector Day / Detector Night
Manual call p
point Day
y / Manual call p
point Night
g
Relay activation (General / Activation list (Up to 8 independent lists)/ Per Zones)

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 68
5. Addressable Lyon
y System
y
5.8.- Configuration (7/7)

B) Configuracin de la central (Cont)


2) EASY coNET (Basic version) -Cont-
2 4 Configure Zones (Up to 8 independent lists)
2.4

2.5 Send Configuration to Control panel


General configuration / Especific configuration

2 6 It is allowed receiving Control panel information


2.6
Partial/Total Configuration
Reading of detected Programming numbers
Full history

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 69
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (1/4)

Characteristics
- ON-LINE management in Windows environment
(monitoring test mode,
(monitoring, mode situation maps,
maps null or rearm zones,
zones etc)

- Separation up to 1200 m with RS232/RS485 converters

- TCP/IP protocol posibility

- Licence by Installation
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 70
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (2/4)

Example in Fiber Optics connection

Fiber Optic Fiber Optic


O
Conversor Conversor

NOTE
Fiber Optic Line 1 Line 2
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 71
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (3/4)

1) Continuous connection with Control panel


Inmediate action buttons
Configuration of:
a. Relays

b Null/Rearm elements/zones
b.

c. Test (General/Zones)

d. Sensitivity

e. Monitoring (reaing and information of the elements)

f. General Rearm

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 72
5. Addressable Lyon
y System
y
5.9.-EASY coNET Online (Extended version) (4/4)

2) Events (Alarm,
(Alarm Fault,
Fault etc)
Information Window

Situation drawing with los


the related elements

3) Graphical Presentation
Allows up-load drawing in
.BMP, JPG, WMF or GIF format

Presents the detection elements related with


the events
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 73
5. Addressable Lyon System
5.10.- Derived Control panels (1/3)
Compact Lyon
C-Lyon

- COMPACT version of LYON Control panel

- Installation totally compatible with LYON Control panel

- 1 or 2 loops
l (99 elements
l t per loop).
l )

- Reduced Chest coming


g from CLVR

- Control panel NETWORK, Repeaters, ON-LINE, etc.


Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 74
5. Addressable Lyon System
5.10.- Derived Control panels (2/3)

1 or 2 loops with 199 elements/loop.

Full compatible installation with LYON

Reduced Chest coming from CLVR

Control panel NETWORK, Repeaters, ON-LINE, etc.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 75
5. Addressable Lyon System
5.10.- Derived Control panels (3/3)

D i
Devices li
limit
it per C
Control
t lP Panell
Control Element Logical
Loop Loop Control Control
Panel Loop limit equivalence Relays
Reference Description limit limit Panel limit Panel limit
limit
LYON Control panel ZAFIR Control panel C-LYON Control panel
Addressable optical-heat
A30XHA 199 --- 199 398 99 198 1 --- ---
sensor
Addressable optical
A30XHAS 199 --- 199 398 99 198 1 --- ---
sensor
A30XTA Addressable heat sensor 199 --- 199 398 99 198 1 --- ---
Addressable optical-heat-
A30XHTCO 199 --- 199 398 99 198 1 --- ---
monxide Multisensor
Add
Addressable
bl Manual
M l Call
C ll
PUCAY 70 --- 70 140 70 140 1 --- 1
Point
Conventional Zone master
KMAY 39 --- 39 78 19 38 5 --- 1
detection module
MDA2Y 2 Relays module 16 99 16 32 16 32 5 2 1
MDA1Y 1 Relay module 32 199 32 64 19 38 5 1 1
R l and
Relay dT
Technical
h i l
MYOA 32 199 32 64 19 38 5 1 1
signal module
MSTAY Technical signal module 70 --- 70 140 49 98 2 --- 1
KABY Loop isolator module 70 --- 70 140 70 140 --- --- 1
SIRAY/
Addressable sounder 10 99 10 20 6 12 10 1 1
SIRAYL
Control panel limits:
LYON Control Panel ZAFIR Control panel Central C-LYON
a) 199 elements, 32 logic relays and 70 isolators a) 199 elements, 32 logic relays and 70 isolators per a) 99 elements, 32 logic relays and 70 isolators per
per loop. loop. loop.
b) 20 loops with 199 logic relays b) 2 loops with 199 logic relays b) 2 loops with 199 logic relays
per control panel. per control panel. per control panel.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 76
CO Detection system for parking

COsensor Model

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 77
6 CO Detection System COsensor
6. COsensor
6.1.- Design recommendations

1) Certification
It is certified according with the UNE 23.300
23 300 standard and agreed with CE Directives
(CE mark).

2) Installation recomendation
Parking cars mechanically ventilated with site for more than 5 cars or 100 m2
Ventilation activation with 100 ppm CO concentration (50 ppm if there are workers)
CO detector coverture: 200 m2
Installation high: Between 1,5 and 2 m from floor.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 78
6 CO Detection
6. D t ti S t
System CO
COsensor

6.2.- CCO-1 Control Panel (1/2)

1) Models available:
CCO110: 1 Zone and up to 10 detectors
CCO115: 1 Zone and up to 15 detectors
CCO115 DVB: 1 Zone, Up to 15 detectors, Doble Ventilation and Batteries.

2) F
Funcionamiento
i i t (CCO110/115)
Alarm Alarm
[CO]
Delay Stop

Alarm
Al
Parameter Value Margin
level
Postventilation
Delay Alarm Ventilacin Level: 50 ppm Programable (30 150 ppm)

Ventilation Ventiltion Actived


Ventilacin Delay: 4 min Programable (1 9 min)
Delay Stop
Postventilation Delay: 4 min Fix
Ventilation
Level Alarm Level: 300 ppm Fix

Ventilation Ventilation Alarm Delay: 15 min Fix


Actived Actived

Time
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 79
6 CO Detection System COsensor
6. COsensor
6.2.- CCO-1 Control Panel (2/2)
Alarma
3) Operation CCO115 DVB Level
Ventilation 2
Parameter Value Margin Level
Ventilation level 1: 50 pp
ppm Fix Ventilation 1
Ventilation Delay 1: 4 min Programable (1 9 min) Level
Postventilation Dalay 1: 4 min Fix

Ventilation level 2: 100 ppm Fix


Ventilation Delay 2: 0 min Fix

Postventilation Delay 2: 0 min Fix

Alarm Level : 200 ppm Fix

Alarm Delay : 0 min Fix

DRY CONTACT

4) Installation
LIMIT 2A

C NA

Detectors in serial or parallel with polarity


Alarm

Ventilacin Output: Dry contact 2 A. Ventilation

Alarm Output: 22 Vdc,


Vdc 0,8
08A

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 80
6 CO Detection
6. D t ti S t
System CO
COsensor

6.3.- CCO1-4 Control Panel(1/2)
1) Models available:
CCO122 / CCO222 / CCO322 / CCO422: X Zones and up to 22 detectors
All model acept DBV opcion (Doble Ventilation and Batteries)

2) Operation (CCO1-4)
Each Zone is configured independently.
Alarm Alarm
[CO]
Delay Stop

Alarm
Al
level
Postventilation Parameter Value Margin
Delay Alarm Ventilacin Level: 50 ppm Programable (20 150 ppm)
Ventilation Ventiltion Actived Ventilacin Delay:
y 4 min Programable
g ( 9 min))
(1
Delay Stop
Postventilation Delay: 4 min Fix

Ventilation Alarm Level: 300 ppm Fix

Level Alarm Delay: 15 min Programable (10 30 min)

Ventilation Ventilation
Actived Actived

Time
Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 81
6 CO Detection System COsensor
6. COsensor
6.3.- CCO1-4 Control Panel (2/2)
Alarma
3) Operation CCO1-4
CCO1 4 Level
Ventilation 2
Level
Parmetro Valor Margen
Ventilation 1
Ventilation level 1: 50 ppm Programable (20 150 ppm)
Level
Ventilation Delay 1: 4 min Programable (1 9 min)

Postventilation Dalay 1: 4 min Fix

Ventilation level 2: 200 ppm Programable (20 300 ppm) +


+ > Ventilation level 1

Ventilation Delay 2: 10 min Programable (1 30 min) +


+ > Ventilation Delay 2
Zone Power Supply
Postventilation Delay 2: 4 min Fix

Alarm Level : 300 ppm Fix

Alarm Delay : 15 min Programable (10 30 min) Zone 2 Zone 1

Fuse
4) Installation
Detectors in serial or parallel with polarity
Ventilation Output:
p Dryy contact 2 A.

Detectors (up to 22 per Zone) Detectors (up to 22 per Zone)

Alarm Output: 22 Vdc, 0,8 A

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 82
6 CO Detection System COsensor
6.
6.4.- CO Detector

- Green Led: Correct Operation

- Red Led: Sensor reading more than 50 ppm CO.

- According to UNE 23300, it is recommened changing CO sensor


each 5 years.

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 83
6 CO Detection System COsensor
6. COsensor
6.5.- NO2 Detector

- Gas CO -> Gasoline Engines DCO Detector


- Gas NOx -> Diesel Engines

DNO2 Detector
DNO2 Detector
Internal Algorithm to indicate NO2 ppm in CO ppm equivalent:
+ 2 ppm of NO2 are equivalent to 50 ppm of CO
+ 14 pp
ppm of NO2 are equivalent
q to 300 pp
ppm of CO

(Note: Control Panel shows only CO ppm concentration)


CO Control Panels with DCO and DNO2 in the same zone lines.
Installation DNO2 recomendation: The same as for DCO
NO2 Detector coverture: 200 m2.
I t ll ti high:
Installation hi h Between
B t 1 5 and
1,5 d 2 m from
f fl
floor.

It is recommended changing detector each 4 years.


Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 84
The End

Fire Detection and Fire Alarm System V3.1, COFEM S.A Slide No 85