Académique Documents
Professionnel Documents
Culture Documents
Volume of free air in CFM that will flow thru round holes from a receiver into the atmosphere. Cubic feet of
air per minute measured at absolute pressure of 14.7 lbs. per sq. in. and 70¼ F.
Table is based on 100% coefficient of flow. For well rounded entrance, multiply values by 0.97. For sharp
edge orifices, a multiplier of 0.65 may be used. This table will give approximate results only. The formula
Q=14.5 PD2, where Q is CFM, P is absolute pressure and D is orifice diameter in inches, may be used for
any points not given in table. (Applies only above 15 pounds gauge.)
1-
30 3/4 3/4 3/4 3/4 1 1 1 1/4 1-1/4
1- 1-
45 3/4 3/4 1 1 1 1 1/4 1/4 1-1/4
1- 1- 1- 1-
60 3/4 1 1 1 1/4 1/4 1/4 1/2 1-1/2
1- 1- 1- 1- 1- 1-
90 1 1 1/4 1/4 1/4 1/4 1/2 1/2 2
1- 1- 1- 1- 1- 1-
120 1 1/4 1/4 1/4 1/2 1/2 1/2 2 2
1- 1- 1- 1- 1-
150 1/4 1/4 1/4 1/2 1/2 2 2 2 2-1/2
1- 1- 1- 1- 2-
180 1/4 1/2 1/2 1/2 2 2 2 1/2 2-1/2
1- 1- 1- 2- 2-
240 1/4 1/2 1/2 2 2 2 1/2 1/2 3
1- 2- 2-
300 1/2 2 2 2 2 1/2 1/2 3 3
1- 2- 2- 2-
360 1/2 2 2 2 1/2 1/2 1/2 3 3
2- 2-
450 2 2 2 1/2 1/2 3 3 3 3-1/2
2- 2- 2- 3-
600 2 1/2 1/2 1/2 3 3 3 1/2 4
2- 2- 3- 3-
750 2 1/2 1/2 3 3 3 1/2 1/2 4
Valve Sizing
Valve Sizing With Cv = 1 Table
This method can be used if the required air flow is known or has been calculated with the formulas
as shown below:
Air Flow Q (SCFM) for Cv = 1 Example 2: Find Cv if air
flow Q (SCFM) is given.
Inlet Air Flow Q
Pressure (SCFM) To
(PSIG) 2 PSID 5 PSID 10 PSID 15 PSID 20 PSID Atmosphere
10 6.7 12
20 7.9 11.9 16.9 Flow through valve from
30 9 13.8 18.2 21.8 Table 28 for Cv = 1:30
40 9.9 15.4 20.6 23.8 26.6 SCFM
50 10.8 16.9 22.8 26.7 29.2 31.5
60 11.6 18.2 24.8 29.2 32.3 36.4 Cv = Air Flow Q (SCFM)
70 12.3 19.5 26.7 31.6 35.1 41.2
Air Flow at Cv = 1
(SCFM)
80 13 20.7 28.4 33.8 37.7 46.1
90 13.7 21.8 30 35.8 40.2 51
Cv = 60 SCFM
100 14.4 22.9 31.6 37.8 42.5 55.9
30 = 2.0
110 15 23.9 33.1 39.6 44.7 60.7
120 15.6 24.9 34.5 41.4 46.8 65.6
A valve with a Cv of
130 16.1 25.8 35.8 43.1 48.8 70.5 minimum 2 should be
140 16.7 26.7 37.1 44.7 50.7 75.3 selected.
150 17.2 27.6 38.4 46.3 52.5 80.2
160 17.7 28.4 39.6 47.8 54.3 85.1 Example 3: Find Cv if air
170 18.2 29.3 40.8 49.3 56 90 flow Q (SCFM) to
180 18.7 30.1 42 50.7 57.7 94.8 atmosphere is given.
190 19.2 30.9 43.1 52.1 59.4 99.7
200 19.6 31.6 44.2 53.4 60.9 104.6
Primary Pressure P1 = 90
PSIG
210 20.1 32.4 45.2 54.8 62.5 109.4
Air Flow to atmosphere Q =
220 20.5 33.1 46.3 56.1 64 114.3 100 SCFM
230 21 33.8 47.3 57.3 65.5 119.2
240 21.4 34.5 48.3 58.6 66.9 124 Flow to atmosphere through
250 21.8 35.2 49.3 59.8 68.3 128.9 valve from Table 28 for Cv =
1:51 SCFM
Cv = Air Flow to atmosphere
Example 1: Find an air flow Q(SCFM) if Cv is known. Q (SCFM)
Cv = 1.8 Air Flow to Atmosphere
at Cv = 1 (SCFM)
Flow through valve from Table 28 for Cv = 1:21.8 SCFM
Cv = 100
51
Example 4: Find Cv if
cylinder size and stroke
speed is known, using
Handy Rules Of Thumb For Estimating
Air Compressors:
1. Air compressors are normally rated to deliver 4 to 5 CFM per horsepower at 100 PSIG discharge
pressure.
2. Depending on the the size of the system, compressed air costs about 25 to 42 cents per
thousand cubic feet of free air ingested by the compressor (including operating and maintenance
costs).
3. A 50 horsepower compressor rejects approximately 126,000 BTU per hour for heat recovery.
Air Receivers:
1. Size air receiver tanks for about 1 gallon capacity for each CFM of rotary compressor capacity.
Standard receiver tank sizes are listed below:
Gal. Dimensions Gal. Dimensions
30 16" x 38" 400 36" x 96"
60 20" x 48" 660 42" x 117"
80 20" x 63" 1060 48" x 144"
120 24" x 68" 1600 54" x 170"
200 30" x 72" 220 60" x 190"
240 30" x 84" 2560 60" x 220"
Water Content:
1. The water vapor content at 100¼ F of saturated compressed air is about two gallons per hour for
each 100 CFM of compressor capacity.
2. Every 20¼ F temperature drop in saturated compressed air at constant pressure, 50% of the
water vapor condenses to liquid.
Water-Cooled Aftercoolers:
1. Most water-cooled aftercoolers will require about 3 GPM per 100 CFM of compressed air at
Discharge Air Tempera- ture at 100 psig.
3. 10¢/ KWH Electric Power Rate = $806/ Year for 1 HP/3 shift Constant Run.
4. KW = HP x 0.7457
Ventilation Required
The following formula will estimate the required ventilation air in cfm to adequately control ambient
heat rejection from an air compressor Ð BE SURE TO USE FULL ABSORBED HORSEPOWER!
EXAMPLE:
WHEN
TOTAL BHP = 110 CFM = 110 HP x 2546
Start Temp. (T1) = 80F (1.08)(20¼)Temp. Rise =
280,060
Max. Allow Temp. (T2) = 100F
21.60
Determine the Water Volume
The following chart was created to simplify the procedure necessary to determine the amount of
water vapor that is present in a cubic foot of air at various temperature and humidity conditions. The
design conditions are based on sea level (14.7 PSIA), and 35¼ pressure dew point.
Percentage Of Saturation
Temp º F 40 50 60 70 80 90 100
35 0.001 0.0012 0.0015 0.0017 0.002 0.0022 0.0024
40 0.0012 0.0015 0.0017 0.0021 0.0024 0.0026 0.0029
45 0.0014 0.0018 0.0021 0.0025 0.0028 0.0032 0.0035
50 0.0017 0.0021 0.0025 0.003 0.0034 0.0038 0.0042
55 0.002 0.0025 0.003 0.0035 0.004 0.0045 0.005
60 0.0024 0.003 0.0036 0.0042 0.0048 0.0054 0.006
65 0.0028 0.0035 0.0042 0.0049 0.0056 0.0063 0.007
70 0.003 0.0041 0.005 0.0058 0.0066 0.0075 0.0083
75 0.0039 0.0049 0.0058 0.0068 0.0078 0.0088 0.0097
80 0.0045 0.0057 0.0068 0.008 0.0091 0.0102 0.0114
85 0.0053 0.0066 0.0079 0.0093 0.0106 0.0119 0.0132
90 0.0061 0.0077 0.0092 0.0108 0.0123 0.0138 0.0154
95 0.0071 0.0089 0.0107 0.0125 0.0142 0.016 0.0178
100 0.0082 0.0103 0.0123 0.0144 0.0164 0.0185 0.0205
105 0.0095 0.0118 0.0142 0.0166 0.0189 0.0213 0.0236
110 0.0108 0.0136 0.0163 0.019 0.0217 0.0244 0.0271
115 0.0124 0.0155 0.0186 0.0217 0.0248 0.0279 0.031
120 0.0142 0.0177 0.0212 0.0248 0.0283 0.0319 0.0354
To use this chart, determine your maximum temperature and humidity condition. (In the event you
are between ratings, please round up to the next number present.) Locate the factor that is at the
intersection point of these two conditions. Take the CFM rating of the air compressor system that
you intend to dehydrate. Multiply the CFM by the factor at the intersection of the proper conditions.
The answer you get is the total amount of water in gallons per hour that would be condensed when
chilled to 35¼ F