How to remove and replace a System Board Battery in an X4270

M2

Goal
How to rmove and replace a System Board Battery in an X4270 M2

Fix
DISPATCH INSTRUCTIONS

WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)


X4270 M2 Server Training

TIME ESTIMATE: 30 minutes

FIELD ENGINEER INSTRUCTIONS

WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE


RESOLUTION ACTIVITY? :

1. Prepare the server for service.


a. Power off the server and disconnect the power cord (or cords) from the power supply (or
supplies).
b. Remove the server from the rack.
c. Attach an antistatic wrist strap.
d. Remove the top cover.

WHAT ACTION DOES THE ENGINEER NEED TO TAKE:


Removing the Battery.
2. Remove the battery.
a. Place you finger between the battery and side wall of the server chassis and push the
battery away from the side wall.
b. Twist the battery (either clockwise or counter-clockwise) and lift it out.
Installing the Battery.
1. Unpack the replacement battery and place it on an antistatic mat.
2. Press the new battery into the battery holder with the positive side (+) facing the server
chassis side wall.
3. If the service processor is configured to synchronize with a network time server using the
Network Time Protocol (NTP), the ILOM clock will be reset as soon as the server is powered
on and connected to the network. Otherwise, proceed to the next step.
4. If the service processor is not configured to use NTP, you must reset the ILOM clock using
the ILOM CLI or the web interface.
5. Return the server to operation.
a. Install the top cover.
b. Return the server to the normal rack position.
c. Reconnect the power cord(s) to the power supply (or supplies) and power on the server.
Verify that the AC Present LED is lit.