Vous êtes sur la page 1sur 1

"KIDDE" FM200 FIRE SUPPRESSION SYSTEM

PRE-FABRICATED CONTAINER VAN POWER ROOM


FIRE ALARM CONTROL PANEL INPUT/OUTPUT MATRIX (CAUSE AND EFFECT)

ACTIVATE RELEASING (ARC) SOLENOID CIRCUIT

ACTIVATE PANEL TROUBLE LED INDICATORS


ACTIVATE PANEL NOTIFICATION STROBE

ACTIVATE HORN W/ FLASHING STROBES

ACTIVATE PANEL TROUBLE TONE ALERT


ACTIVATE PANEL ALARM TONE ALERT
SYSTEM OUTPUTS

START OF THE 30 SECS TIME DELAY

ACTIVATE PANEL TROUBLE RELAYS


ACTIVATE FIRE ALARM BELL
PANEL LED DISPLAY DEVICE
ALARM LED "RED"
SYSTEM INPUTS

ACTIVATION OF 1 NO. SMOKE DETECTOR (ZONE 1) X X X X

ACTIVATION OF 2 OR MORE SMOKE DETECTORS (ZONE 2) X X X X X X X

ACTIVATION OF MANUAL PULL STATION X X X X X X X

MANUAL ACTIVATION OF ELECTRIC CONTROL HEAD (ECH) X X X X X X X

EXPIRATION OF 30 SECONDS TIME DELAY X X X X X X X

OPEN CIRCUIT X X X X

GROUND FAULT X X X X

SYSTEM/DEVICE TROUBLE X X X X

NOTIFICATION APPLIANCE SHORT CIRCUIT X X X X

FIRE ALARM SYSTEM LOW BATTERY X X X X

LEGEND: X - Operation will Occur

Vous aimerez peut-être aussi