Ca = 0.2709901
Pa = 1434.8923 Kg/m 0.300 Ksf
Ha = 2152.3385 Kg/m 1.475 K/ft of Wall
Ha acts at h/3 from the base = 1 m 3.281 ft
hs = 0.5439093 m 1.785 ft
Ps = 260.15045 Kg/m 0.054 Ksf
Hs = 780.45136 Kg/m 0.535 K/ft of Wall
Hs acts at h/2 from the base = 1.5 m 4.9215 ft
In the preceding calculations, it is assumed that the backfill is dry, but it is necessary to investigate
the presence of water pressure behind the wall. The maximum water pressure occures when the whole
height of the basement wall is subjected to water pressure, and:
w = w h = 3000 Kg/m 0.626566 Ksf
The maximum pressure may not be present continuously behind the wall. Therefore, if the ground is
intermittently wet, a percentage of the preceding pressure may be adopted, say 50%:
Hw' acts at h/3 from the base = 1 m 3.281 ft water may be prevented from
collecting against the wall by providing drains at the lower end of the wall.
In addition to drain, a waterproofing or damp-proofing membrane must be laid or applied to the external
face of the wall. The ACI Code, Section 14.5, specifies that the minimum thickness of an exterior
basement wall and its foundation is 7.5 in. In general, the minimum thickness of bearing walls is 1/25
of the supported height or length, whichever is shorter, nor less than 100mm.
Page 1 of 4
Project Name
Subject Basement Walls Design
Element Number
Done By
YOUR LOGO
Date 11/14/2017 4:38
A A A
Ma = wL/8 Ma = wL/7.5 Pa Pw Ps
Page 2 of 4
Project Name
Subject Basement Walls Design
Element Number
Done By
YOUR LOGO
Date 11/14/2017 4:38
Maximum positive bending moment within the span occures at the section of zero shear
Vu = RB - 1.7(Ps x) - 1.7[(Pa+Pw)x / h]
x = 0.9701441 m 3.183043 ft
Longitudinal Reinforcement
Use minimum steel ratio, = 0.002 for deformed bars not larger than No.16 (ACI Code, Section 14.3)
As = 360 mm /m 0.17 in /ft
Page 3 of 4
Project Name
Subject Basement Walls Design
Element Number
Done By
YOUR LOGO
Date 11/14/2017 4:38
Then bar diameter = 11.63 mm
Use 4 of Bar No. 12 Spacing = 25 cm on each side of the wall.
Note:
If the bending moment at the base of the wall is quite high, it may require a thick wall slab, for example
12 in. (30cm) or more. A hunch may be adopted which will reduce the thickness of the wall, because it
will be desinged for the moment at the section exactly above the haunch.
The basement slab may have a thickness greater than the wall thickness and may be extended outside
the wall by about 10in. (25cm) or more, as required.
Hunch
10-20"
15.5cm 10-15"
Extension of base
Y12/25cm
3m 18cm
Y12/25cm
Y14/20cm
20.5cm
0.3m
Page 4 of 4