Vous êtes sur la page 1sur 6

GE Power Systems

COMPRESSOR WATER WASH SYSTEM

General Functional Description

Gas turbines can experience a loss of performance During the washing operation, water or wash solu-
during operation as result of deposits of contami- tion is delivered to the gas turbine in the proper mix
nants on internal components. The deposits of atmo- ratio and the proper pressure, temperature and flow
spheric contaminants on compressor parts occurs rate to wash the gas turbine compressor. Refer to
with the ingestion of air. Gas Turbine Compressor Cleaning GEI41042M,
Table 3 for proper pressures, temperatures, and flow
The ingested air may contain dirt, dust, insects and rates for this gas turbine.
hydrocarbon fumes. A large portion of these can be
removed before they get to the compressor by inlet System Requirements
air filtration. The dry contaminants that pass through
the filters as well as wet contaminants, such as hy- Water used for washing turbine parts should be rea-
drocarbon fumes, have to be removed from the com- sonably clean so that it does not cause fouling or cor-
pressor by washing with hot water or a rosion in itself. Distilled or deionized water is
waterdetergent solution followed by a water rinse. recommended. Water quality requirements are listed
in Table 1 of GEI41042M. Oily or varnished oil de-
posits on internal gas turbine parts require that a de-
Onbase Supplied Equipment tergent solution be used during the washing
operation. The detergent shall meet the require-
The onbase equipment supplied with this compres- ments in Table A1 of GEI41042M.
sor wash system consists of piping from the package
connection on the base, motor operated water injec- Compressor Washing Frequency
tion valves, and the appropriate spray manifolds. In
addition, there are package connections in the drain The frequency of compressor washing depends
lines from the inlet plenum, combustion area, ex- upon the severity and type of atmospheric contami-
haust frame and the exhaust plenum. nation which fouls the compressor and reduces per-
formance. The recommended method for
establishing the frequency is to monitor gas turbine
Offbase Equipment performance, comparing the routine performance
with the baseline performance to observe the trends.
The offbase equipment supplied is an enclosed wa- The comparison will show performance trends. If
ter wash skid containing a wash water tank, a deter- the performance has fallen significantly, and com-
gent tank and a centrifugal water pump and motor pressor fouling is suspected, it should be verified by
(88TW1) with a venturi eductor used to mix the de- visual inspection. This visual inspection should in-
tergent with the wash water. A needle valve used in clude inspection of the compressor inlet bellmouth,
conjunction with a flowmeter is used to set the deter- inlet guide vanes and the first and possibly the se-
gent flow to the level recommended by the detergent cond stage of the compressor blades. If the perfor-
manufacturer. The water tank is equipped with heat- mance loss is due to compressor fouling,
ers to bring the wash water to the proper temperature compressor cleaning should be initiated. For oily de-
and the skid itself is equipped with a heater, blower posits, a waterdetergent wash followed by a water
and vent fan to maintain the skid in the proper tem- rinse is required. If only dry deposits are found, wa-
perature range. ter alone may be sufficient.
A00215 1 COMPRESSOR WATER WASH SYSTEM
GE Power Systems

NOTE Mandatory Precautions


Inspection should be made for the source of the When doing an offline wash it is extremely impor-
oily deposits. If possible, corrective action tant that all water be drain from all piping and that all
should be taken. valving be returned to its normal running position.
Failure to do so may result in damage to the gas tur-
bine and/or its components. Refer to TIL 11792 for
CAUTION further information.
The differential temperature between the wash
Before water washing of the compressor begins, the
water and the interstage wheelspace tempera-
turbine blading temperature must be low enough so
ture must not be greater than 67C (120F) to
that the wash water does not cause thermal shock.
prevent thermal shock to the hot gas parts. For
wash water of 82C (180F), the maximum To reduce this difference, the wash water may be
wheelspace temperature must be no greater heated and the turbine kept on crank until the wheel-
than 149C (300F) as measured by the wheel- space temperatures drop to an acceptable level. The
space thermocouple readings on the turbine wheelspace temperatures are read at the control pan-
control panel. el.
WARNING
The water wash operation involves water un-
der high pressure. Caution must be exercised to
Washing System Operation ensure the proper positioning of all valves dur-
ing this operation. Since the water may also be
hot, necessary precautions should be taken in
handling valves, pipes, and potentially hot sur-
Online Washing
faces.

NOTE
Online washing is done with the unit at full speed
and the load at or less than 95% rated load. Certain Before water washing the compressor, inspect
precautions must be taken when performing an on the inlet plenum and gas turbine bellmouth for
line wash during low ambient temperature condi- large accumulations of atmospheric contami-
tions; see Gas Turbine Compressor Cleaning nants which could be washed into the compres-
GEI41042M and TIL 11533 for further informa- sor. The deposits can be removed by washing
tion. with a garden hose.

Offline Washing
Water Wash Procedures
To perform cleaning designed for this particular
unit, refer to the system schematic and the device
Offline water washing should be scheduled during summary to verify the wash system equipment fur-
a normal shutdown, if possible. This will allow nished. Follow the steps outlined in the appropriate
enough time for the internal machine temperatures section(s) below.
to drop to the required levels for the washing. The
time required to cool the machine can be shortened Offline Compressor Wash Procedure
by maintaining the unit at crank speed. During this
cooling of the turbine, the wash water is to be heated On the water wash skid, in the Annunciator/Control
to the proper level. Panel, the following settings must be initiated:
COMPRESSOR WATER WASH SYSTEM 2 A00215
GE Power Systems

1. Water Temperature Setpoint switch to HOT. 2. Close the hand valves on the flame detectors.
2. Operation Selector switch to MANUAL. 3. Arrange any valves in the exhaust plenum drain
piping to divert effluent from the sludge tank to
NOTE the waste water tank. Open the main wash water
It will take approximately 915 hours for the drain valve at the bottom of the exhaust plenum.
water to heat up to the proper washing tempera-
4. Open the inlet plenum drain valve.
ture.
5. If a valve is installed in the line supplying com-
Make certain the turbine is shut down. pressor discharge air to the false start drain
valve, close it.
Select the Water Wash On/Off Line control dis-
play on the turbine control primary operator inter- 6. Switch the motor controller for the turbine ex-
face and click on the OFFLINE WW ON target. At haust frame cooling fan motors, 88TK1 and
this time, the turbine is prohibited from firing. 88TK2 in the manual ON position (if pro-
vided).
Select CRANK at the Master Select of the Main Dis- NOTE
play at the operator interface for the SPEEDTRON-
IC Mark V control. This step is necessary to prevent water wash
from entering the exhaust frame cooling sys-
Initiate a turbine START signal. tem during the wash cycle.
The turbine will accelerate to full continuous crank
The atomizing air system (if provided) is isolated in
speed. The cranking motor will maintain the unit on
the following manner:
crank until the stop signal is given.
1. Close butterfly valve on inlet side of atomizing
The cooldown procedure must be continued until air system from AD8 line.
the wheelspace temperatures are within 67C
(120F) of the wash water temperature. 2. Open all low point drains in the atomizing air
lines.
NOTE
3. Open the atomizing air separator drain valve (if
The turbine may be allowed to cool down on provided).
slow roll if time permits.
4. Open vent valve on suction side of CA2, booster
atomizing air compressor.
During the crank cycle, manually place the follow-
ing in the positions indicated and in the order listed: 5. Open vent valve on pressure side of CA1, main
atomizing air compressor.
1. The flow through false start drain valves must be
diverted from the sludge tank to a wash water ef- 6. Open the breaker at the motor control center for
fluent tank. 88AB, the drive motor for the booster atomizing
air compressor, CA2.
NOTE
The false start drain flow or any flow that goes Using the schematic for the cooling and sealing air
normally to the sludge tank must be diverted system, the cooling and sealing air circuitry should
from its normal path into the sludge tank, to a be isolated in the following manner:
wash water effluent drain to prevent an over- 1. Close the valves in the fifthstage compressor
flow of the sludge tank. Additionally, the false extraction air lines.
start drain effluent should be visible to evaluate
1. Close the valves in the eleventhstage compres-
the effectiveness of the wash cycle.
sor extraction air lines.
A00215 3 COMPRESSOR WATER WASH SYSTEM
GE Power Systems

2. Close any and all compressor discharge extrac- by using the respective pushbuttons in the motor
tion valving (ADn). control panel:
3. Open the drain valve on the bearing sealing air 1. Start the main wash pump
separator. 2. Open detergent isolation valve on line between
4. Open needle valve (low point drain on AD3) the venturi and detergent tank.
upstream of WW9 connection for drainage dur- 3. While monitoring the flow meter, adjust the
ing the wash cycle, (if provided). flow metering valve as necessary until the prop-
5. Open low point drain on bearing sealing air line, er detergent/water mix ratio is obtained. Refer to
(if provided). detergent manufacturers recommendations.
6. If the turbine has a selfcleaning inlet filter, 4. Wash/detergent solution should run into the
close the block valve and open the drain valve on compressor for approximately 35 minutes . Al-
the supply line to the selfcleaning filters. low enough flow time to displace water in the
lines between the wash skid and the compressor
The water wash skid should now be checked for op- wash manifold nozzles.
erational readiness. Determine if the following
5. Initiate the turbine STOP signal and close
conditions exist:
20TW1 using the pushbutton station.
1. The water tank is full. 6. Close detergent isolation valve. (This valve
2. The detergent tank is full. should be closed at all times, except when being
used to add detergent.)
3. The water temperature is at the required level.
7. Shut off the main wash pump.
4. The valve on the main wash pump suction side is
open. During the coastdown and immediately afterward,
allow the turbine to soak for approximately 20 min-
5. The shutoff isolation valve in the water supply utes. After the soak time is complete initiate a tur-
line to the skid is closed. This is done to prevent bine START signal.
unheated water from entering the water tank
once a wash is initiated. Open the water wash shutoff valve, 20TW1, using
the pushbutton station 20TW1/PB at the turbine.
To minimize thermal shock to the hot gas path parts Allow the turbine to reach full continuous crank
the operator must verify that all turbine wheelspace speed.
temperatures have cooled to within 67C (120F)
[149C (300F) maximum] of the wash water tem- Start the water pump on the skid. Rinse the compres-
perature. sor by pumping clear water from the skid with the
main wash pump. Rinse the compressor for 1520
When doing a water/detergent wash, refer to the de- minutes or until the rinse water runs clear.
tergent manufacturers instructions for the proper
detergent/wash ratio. After washing is complete, initiate a turbine STOP
signal and shut off the water pump. Allow the tur-
Open the water wash valve at the compressor using bine to dry while coasting down.
the pushbutton 20TW1/PB. This pushbutton is lo-
NOTE
cated near the 20TW1 valve near the inlet plenum.
Experience will determine the proper time in-
Allow the turbine to reach crank speed. tervals for the various wash operations or
whether repetition of the above procedure is
Initiate the appropriate devices on the water wash necessary to restore lost performance.
skid. The following devices can be manually started
COMPRESSOR WATER WASH SYSTEM 4 A00215
GE Power Systems

Return all valves on the skid to their normal position.


CAUTION
Close wash water injection solenoid valve, It is important that the line that allows waste
20TW1, using the pushbutton station. fuel to drain to the sludge tank be kept open af-
ter water washing and during normal turbine
After the turbine has stopped, initiate a turbine startup and operation, so that fuel or water
START signal with the master operation selector which may accumulate in the exhaust plenum
switch in the CRANK position. can continuously drain out of the plenum. Ac-
cumulation of waste fuel in the exhaust plenum
Allow the turbine to accelerate to crank speed. is potentially hazardous.
Allow the turbine to dry for 20 minutes at crank
speed. Switch the motor controller for the turbine exhaust
frame cooling fan motors 88TK1 and 88TK2, into
Initiate a turbine STOP signal. the AUTO mode (if provided).

Click on the OFFLINE WW OFF target on the Select OFF at the Master Select of the Main Display
Water Wash On/Off Line control display. at the operator interface for the SPEEDTRONIC
Mark V control.
NOTE In the annunciator/control panel on the skid, set wa-
When OFFLINE WW OFF is selected, the ter temperature setpoint to COLD and the Opera-
permissive is in place to allow the turbine to tion Selector switch to AUTO.
fire and the permissive is removed to allow the
Initiate a turbine START signal within 24 hours after
20TW1 valve to be opened.
completion of the DRY cycle and allow it to acceler-
ate to, and remain at, full speed for a minimum of
Return all valving to their previous fullspeed op- five minutes.
eration positions. The gas turbine is now available for commercial ser-
vice and may be loaded.
NOTE
NOTE
Allow the water to drain from the lines while
the above restorations are being performed. Check for air leakage from all drains.

A00215 5 COMPRESSOR WATER WASH SYSTEM


GE Power Systems

GE Power Systems Training


General Electric Company
One River Road
Schenectady, NY 12345

COMPRESSOR WATER WASH SYSTEM 6 A00215

Vous aimerez peut-être aussi