1 Run Mode Display will show present status of the A/C parameters & fault messages for live faults one by one in RUN Mode SR.NO. Display Description Message 1 t- C Room Temperature 2 VoLt Voltage 3 BAL- Balance Cycle Time 4 AC1h AC1 Run Hour 5 AC2h AC2 Run Hour 6 r-Hi High Temp Alarm 7 r-Lo Low Temp Alarm 8 oV Over Voltage 9 uV AC1 Under Voltage 10 SnFL Sensor Fail 2 Key Operation Salient Features: SR.NO. Display Description 1] It Controls two air conditioners. Message 2] Separate Phase Supply for each A/C. 3] Bright Red 4 Digit LED Display. 1 Function To enter into FUNCTION SET 4] Accurate Temperature sensing by precise temperature sensor. mode / To save the changes. 5] Time Sharing for Compressors to share load equally. 2 ENTER To save the changes & to come 6] Voltage protections for each compressor. out of FUNCTION SET Mode. 7] Separate alarm relay contacts for Room High. 3 Up Arrow To Increment the value. 8] Separate alarm relay contacts for Sensor Fail. Key 9] Separate alarm relay contacts for OV/UV. 4 Down To Decrement the value. 10] Hour counters for Compressor ON Period to check its reliability. Arrow 11] Display of all the A/C parameters & fault messages Key continuously in a Scrolling manner. 3 FUNCTION SET User can view/change the Set 12] Display Hold Feature by using ENTER Key. Press it again to Mode points in this Mode release the hold. SR.NO Display Description 13] Various set points are settable through function mode categories Menu 14] It has Password Protection. Passwords User can enter into menus by 15] Sensor Fail Mode to keep ON & OFF cycle of one of the A/C entering their respective through sensor fail ON/OFF time settings. passwords 16] LED Indications to observe the status. Display Password Menu Technical Specifications: 1 Function Factory Set :- 11 Set Mode 1] Supply Voltage: 230 V AC, 50 Hz 15% separate for each Display Description A/C. SR.NO. Set point 2] Contact Rating: 30 A at 230 V AC for Compressor Live Message Outputs & 5 A at 250 V AC for Alarm Potential Free Outputs (C, 1 CYCL Cycle Time to swap AC1 & N/O). AC2 & AC3 Temperature set 3] Temperature Sensor: Thermistor Sensor NTC 10K@25C points Default: 240 minutes. Metal body with clamp. Sensor Cable Length: 2.75 meters. Range:- 5 to 600 minutes 4] Temperature Sensing Range: 0.0C to 55.0 C. 2 AC-1 AC1 Cut In Set point Default 5] Resolution: 1V for Voltage, 0.1 A for Current & 0.1C for -on- Value: 24.0C temperature. Range:- 20.0 C to 40.0C 6] Indications: 3 AC-2 AC2 Cut In Set point Default 1] Supply ON for A/C1 & A/C2.Colour: Yellow. -on- Value: 25.0C 2] OV/UV Fault Colour: Red. Range:- 20.0 C to 40.0C 3] Sensor Fail fault Colour: Red. 4 OFF- Cut Off Set point 4] Room High fault Colour: Red. Hyst Default Value: -3.0C i.e. cut 5] Healthy Colour: Green. off at 24.0C 6] Keys: 4 key keypad for settings. Range:- 0.5 C to 10.0C 1] SET Key : To enter into FUNCTION SET Mode/To view 5 r-Hi Room High Cut In Set point the next set point. -on- Default Value: 32.0C 2] Up Arrow Key: To increment the set point. Range:- 25.0 C to 37.0C 3] Down Arrow Key: To decrement the set point. 6 r-Hi Room High Cut Off Set point 4] ENTER Key: To come out of FUNCTION SET mode/To -OFF- Default Value: -1.0C enter into menu/To accept the password. i.e. cut off at 25.0C 7] Mounting: Wall mounting. Range:- 0.5 C to 5.0C 8] Size: 235 mm (H) X 190 mm (W) X 63 mm (D). 7 r-Lo Room Low Cut In Set point -on- Default Value: 15.0C 1 USER MANUAL PROTON POWER CONTROL PVT. LTD., PUNE
Range:- 10.0 C to 20.0C Working:
8 r-Lo Room Low Cut Off Set point -OFF- Default Value: +1.0C i.e. cut 1. After power on delay over if Room Temperature demands with off at 16.0C respect to AC1 ON Setpt &AC2 ON Setpt Which of the AC Range:- 0.5 C to 5.0C becomes ON first, after Inter AC ON Delay Over other will be 9 uV Under Voltage Set point allowed to ON. Default: 160 V 2. AC1 will be ON after its ON Delay of 180 sec (Default). Cut off at (Set point + 10 ) i.e. 3.AC2 will be ON after its settable delay at 170V Range:- 100V to 200V 4.If Room Temp reduces below 10 oV Over Voltage Set point [AC1 ON Setpt OFF Hyst Setpt],AC1 will be OFF. Default: 250 V 5. If Room Temp reduces below [AC2 ON Setpt OFF Hyst Cut off at (Set point - 10 ) i.e. at Setpt], AC2 will be OFF. 260V Range:- 240V to 300V 6. AC1 ON Setpt & AC2 ON Setpt will get interchanged after 11 SET- Set Password---- This set point Cycle Time for the purpose of load sharing. PASS is not displayed in View 7. If any fault occurs (OV/UV) & Room low that time all machine Menu Range:- 000 to 999 will be OFF. 12 AC-1 Strt AC1 restart delay 8. Room High fault occurs that time all machine will be ON. Default:-180 sec. 9. After temperature cut in/fault recovery, A/C will be ON after Range:- 100 to 600 seconds their Restart delays. 10. In Sensor Fail condition, Half AC will remain ON for sensor 13 AC-2 Strt AC2 restart delay fail on time & will remain off for remaining half AC sensor fail Default:-190 sec. off time. Range:- 100 to 600 seconds 14 SnFL Sensor Fail ON Delay -on- Default:- 60 minutes Range:- 5 to 995 minutes Terminal Layout: 15 SnFL Sensor Fail OFF Delay OFF- Default:- 15 minutes SUPPLY A/C1 A/C2 ALARM Range:- 5 to 995 minutes 230V AC 16 rt-P Room Temperature + offset N/O L N E C N/O C N/O C Default:- 0.0 C Range:- 0.0 C to 5.0 C 17 rt-- Room Temperature - offset Default:- 0.0 C Range:- 0.0 C to 5.0 C 18 V1-P AC1 Voltage + offset Default:- 0V Range:- 0 V to 50 V 19 V1-- AC1 Voltage - offset Default:- 0V Range:- 0 V to 50 V 20 rSEt Reset AC1 & AC2 & AC3 & Hour AC4 & AC5 &AC6 Hour Counter Default:- -no- If YES- message is selected, Hour Counters will reset.