Académique Documents
Professionnel Documents
Culture Documents
Riga 10
2993 LW Barendrecht
The Netherlands
Tel.: +31 (0)180 531027 (office)
Fax: +31 (0)180 531848 (office)
E-mail: info@cts-netherlands.com
Website: www.cts-netherlands.com
Dome Venting Calculation according to API 2000 7th edition - ISO 28300
General project data
Project number : 3495
Tank number : 2007
Stored Product : Gasoil
Customer : Zenith Energy Amsterdam Terminal
Revision : A
Date : 4-8-2016
By : OB
Input
Tank data
Tank inside dia D : 70.00 m
Tank heigth H : 17.70 m
Design pressure Pp : 0.00 mbar
Design vacuum Pv : 0.00 mbar
Operating temperature To : < 25 C
Roof design data
Roof type : dome
Cone roof slope 1 : x : 0
Dome height : 12.99 m
Dome radius : 54.55 m
Flashing choke height : 0.00 mm (0 for solid CF or cone roof)
Shoe width : 230.00 mm
Shoe qty : 42.00 pcs
Frangible roof-to-shell : yes (yes for dome roof)
Insulation
Insulated area of shell Ain,s : 0 %
Insulated area of roof Ain,r : 0 %
Insulation thickness lin : 0 mm
Thermal conductivity lin : 0 W/m.K
2
Inside heat-transfer coefficient h : 0 W/m K
Factors
Reduction factor for insulation Ri : 1.00
Latitude of tank location Y : between 42 and 58 y= 0.25
Environmental factor F : Bare metal tank F = 1.00
Vapour pressure C : Hexane or similar C = 3.00
Process data
3
Maximum filling rate Vpf : 10,000 m /hour
3
Maximum emptying rate Vpe : 10,000 m /hour
Outlet nozzle dia : 24 inch
2
Wetted surface area Atws : 2,011 m
3
Total tank volume Vtk : 94,740 m
Stored product data
Product : Gasoil
Vapour pressure : 0.06 kPa @ 20C
Specific weigth rho : 0.83
Latent heat of vapourization L : 250,000.00 J/kg (for hexane use 334.900)
Boiling point temperature T : 473.00 K
Relative molecur mass of vapour M : 130.00 (for hexane use 86,17)
Containing more volatile components of dissolved : no
gasses
Dome Venting Calculation according to API 2000 7th edition - ISO 28300
General project data
Project number : 3495
Tank number : 2007
Stored Product : Gasoil
Customer : Zenith Energy Amsterdam Terminal
Revison : A
Date : 4-8-2016
By : OB
Output
1.0 Normal vacuum relief
3
1.1 Inbreathing :
1.1 Inbreathing 10,000 Nm /hour
3
1.2 Thermal inbreathing : 18 Nm /hour
3
1.3 Normal total vacuum relief : 10,055 Nm /hour
2.0 Normal pressure relief
3
2.1 Outbreathing : 10,000 Nm /hour
3
2.2 Thermal out-breathing : 7,530 Nm /hour
3
2.3 Total normal out-breathing : 17,530 Nm /hour
3.0 Emergency relief
3
3.1 Fire exposure : 0 Nm /hour due to frangible roof-to-shell
3
3.2 Gravity flow due process failures : 55 Nm /hour
3
Venting requirement = 7,530 Nm /h (According to API 2000 3.3.2.3.2)
Heat input from fire exposure Q = 4,129,700 watts (According to API 2000, table 3)
Environmental factor F = 1 (According to API 2000, table 9)
Latent heat of vaporization L = 250,000 J/kg
Absolute temperature of vapor T = 473 K
Relative mocular mass of vapor M = 130.00
3
Venting Requirement = 0 Nm /h due to frangible roof-to-shell (According to API 2000 3.3.3.3)
1
g .h1 (t ) = v 2 (t )
2
3.2 Gravity flow due process failures (For information only, not a design consideration acc. API)
2
Tank height H = 17.70 m
Velocity V = 16.98 m/s
Outlet nozzle area = 24 " 0.292 m2
= 4.956 m3/s
Max. gravity flow Q = 17,840 Nm3/h