TOSHIBA PLANT SYSTEMS & SERVICES CORPORATION CAL-NC-XCSV2-0115 Rev.

2.3 STABILITY AND STRENGTH DESIGN


1 DIMENSION DATA

le
B = 5.310 m , footing width
L = 5.310 m , footing length
he = 5.745 m , height of equipment
x
B be = 4.512 m , width of equipment
le = 4.512 m , length of equipment
he d1 = 0.35 m
d2 = 2.00 m
z
d3 = 0.00 m
Q M h
L h = 3.00 m
H
d1
d2
d3

Rubble/LeanConcrete

1. DESIGN LOAD 4) SEISMIC CALCULATION


1) EQUIPMENT LOADING DATA Tank Seismic Force :
Empty Weight (Qe) = 6,691 kg = 65.57 KN Total Design Base Shear, He = 30.24 kN
Operation Weight (Qo) = 66,855 kg = 655.18 KN Ring Wall Overturning Moment, Mrw = 67.25 kN.m
Test Weight (Qt) = 73,580 kg = 721.08 KN Slab Overturning Moment, Ms = 85.92 kN.m
Total Design Moment about shell to
= Mrw + Ms
2) WEIGHT OF STRUCTURAL PROPER bottom of tank, Mt
3
Soil (s) = 18.0 KN/m = 153.17 kN.m
3
Reinforced concrete (rc) = 24.0 KN/m
Ground water (w) = 10.0 KN/m 3 Maximum Seismic Coefficient = 0.084
*) assumed ground water level GL-0.0m shall be considered on design
Foundation Seismic Force, Hef = 0.084 x (Wf+Wrc)
3) LOAD COMBINATION = 133.64 kN
For soil bearing capacity & stability check
Components A B C D E F 5) WIND CALCULATION
FDN Weight 1.0 1.0 0.9 1.0 0.9 1.0 Velocity Pressure (qz) = 1.28 kN/m 2
Empty 0.9 0.9 Total Wind Moment, Mwt = 77.34 kN.m
Operation 1.0 1.0 1.0 Wind Shear Force on Tank, Hw = 29.79 kN
Test 1.0 Hw < 0.7He, L/C B is neglective
Wind 1.0 1.0
Earthquake 0.70 0.70 6) FOUNDATION WEIGHT
Footing Weight (Wf) = 1591 kN
Rubble Concrete (Wrc) = 0 kN
2. SOIL BEARING CHECK
3.1 ALLOWABLE BEARING CAPACITY 7) BOUYANT FORCE
For fixed load Bouyant Force (Bf) = 564 kN
Qaf = 250.0 kN/m 2
For combined load
Qac = 250.0 kN/m 2 3. SLIDING CHECK

3.2 ACTUAL BEARING PRESSURE : Friction coefficient = 0.35


qmax : P/Af + Mx/Sfx + Mz/Sfz, Maximum soil reaction, kN/m 2 F : Actual safety ratio
qmin : P/Af - Mx/Sfx - Mz/Sfz, Minimum soil reaction, kN/m 2 N : Wf + Q - Bf
P : Q + Wf + Wrc, Total Vertical Load, kN Due to Load Case C:
Total Moment about X-Axis, kN-m : N 0.35 x 927
F = = = 10.89 > 1.5 OK
Case B & C Hw 29.8
Mx : M + H * ( d1 + d2) Due to Load Case E:
Case D & E N 0.35 x 927
F = = = 2.83 > 1.5 OK
Mx : M + (H*(d1 + d2))+ (Hef * (d1 + d2)/2)) 0.7*He 114.7

Af : 28.2 m 2 , B * L, Area of Footing 4. OVERTURNING CHECK


Sfx : 24.95 m 3 , (L * B2 ) / 6, Section Modulus of Footing about X-Axis MR : Resisting moment
MO : Overturning moment
N : Wf + Qo - Bf
CASE P (kN) Mx (kN) qmax qmin Ratio Judge Due to Load Case C:
A 2246 0 80 80 0.32 OK! B 5.310
MR = N = 927 x = 2461.0 kNm
B 2246 147 86 74 0.34 OK! 2 2
C 1491 147 59 47 0.24 OK!
Mo = 147 kNm
D 2246 267 90 69 0.36 OK!
E 1491 267 64 42 0.25 OK! MR 2461.0
F = = = 16.70 > 1.5 OK
F 2312 0 82 82 0.33 OK! Moe 147.3
5 RE-BAR ARRANGEMENT Due to Load Case E:
This foundation is a block foundation so re-bar requirement is only shrinkage B 5.310
MR = N = 927 x = 2461.0 kNm
requirement based on 300mm concrete layer at each face with 0.3% 2 2
reinforcement
Mo = 267 kNm

Closer Bar D16 @ 200 MR 2461.0


F = = = 9.22 > 1.5 OK
Bottom Bar D16 @ 200 Moe 267

Asc = 1005.3 mm 2 0.003Ac OK 5. UPLIFT CHECK


Asb = 1005.3 mm 2 0.003Ac OK P : Q + Wf + Wrc, Total Vertical Load, kN
BF : Bouyant Force
Due to Load Case Empty Condition:
P 1491
F = = = 2.64 > 1.1 OK
BF 564
Due to Load Case Operation Condition:
P 2246
F = = = 3.98 > 1.5 OK
BF 564

CLIENT: Cambodian Energy II Co., Ltd.

This documentation is CONFIDENTIAL and is INTELLECTUAL PROPERTY of TOSHIBA PLANT SYSTEMS & SERVICES
CORPORATION. It must not be copied, loaned or transferred, nor must be disclosed to any third party without their written permission.

5/5