Bilal, Muhammad

From: Stavropoulos Steve [Steve.Stavropoulos@transgrid.com.au]


Sent: Tuesday, 17 May 2011 8:52 AM
To: Brown, Colin
Subject: RE: UNITED COLLIERY PROJECT-CLIENT REQUEST ON BLASTING PROCEDIURES
NEAR OVERHEAD STEEL TOWER LINES.

Col,

Below is an extract of TG blasting policy. In summary the limit we specify is PPV of 50mm/sec. Hope this is what you are
after.

Cheers
Steve

The limits for transmission lines is based on the observation that (generally) transmission
lattice towers are very resistant to vibration damage Therefore: PPV below 25mm/sec: no
interest. Between 25 and 50mm/sec: we would like to see some evidence (from monitoring) that
50mm/sec will not be exceeded. Between 50 and 100mm/sec. Probably OK, but requires some
investigation and review (eg monitoring). Above 100mm/sec: Only in exceptional
circumstances. It is assumed precautions will be taken to avoid fly rock and dust becoming
an problem.

We suspect that substations are far more prone to damage from strong vibration and that the
limits for building damage in the relevant Australian Standard should be applied.

From: Brown, Colin [mailto:Colin.Brown@aecom.com]


Sent: Monday, 16 May 2011 12:40 PM
To: Stavropoulos Steve
Subject: UNITED COLLIERY PROJECT-CLIENT REQUEST ON BLASTING PROCEDIURES NEAR OVERHEAD STEEL TOWER
LINES.

Steve,

I have received a request from an Xstrata Client located in the Hunter Valley who has asked for and I quote:

Transgrid standard design guidelines which will outline blasting restrictions etc, which need to be taken into account
when mining adjacent to their infrastructure

The line in question is Feeder 81 a steel tower 330kV transmission line that is being planned to be relocated around the
extensions to the existing Xstrata United Colliery near the Gold Highway.

Is there anything in this area that you have available that can be provided to the client.

I did discuss issues such as particle velocity limits (footings) and appropriate safety procedures (blast mats etc) however
he is wanting to obtain some broad brush TransGrid guidelines or constraints.

Is there anything in this area that you can provide to assist the client?

Hear from you soon.

1
Regards

Colin Brown
Technical Director - Energy
D +61 2 8295 1134 M +61 409 012 376
Colin.Brown@aecom.com

AECOM
Level 11, 44 Market Street, Sydney, NSW 2000
Q410, QVB Post Office, Sydney, NSW, 1230
T +61 2 8295 3600 F +61 2 9262 5060
www.aecom.com
Please consider the environment before printing this email.
.-. -.. -

This electronic communication, which includes any files or attachments thereto, contains proprietary or confidential information and may be privileged and
otherwise protected under copyright or other applicable intellectual property laws. All information contained in this electronic communication is solely for the use of
the individual(s) or entity to which it was addressed. If you are not the intended recipient(s), you are hereby notified that distributing, copying, or in any way
disclosing any of the information in this e-mail is strictly prohibited. If you have received this e-mail in error, please notify the sender immediately, and destroy the
communication and any files or attachments in their entirety, whether in electronic or hard copy format. Since data stored on electronic media can deteriorate, be
translated or modified, AECOM, its subsidiaries, and/or affiliates will not be liable for the completeness, correctness or readability of the electronic data. The
electronic data should be verified against the hard copy.

Disclaimer:
This e-mail may contain privileged and confidential information intended only for the addressees named above. If you are not the intended recipient please delete
this e-mail and advise the sender. Any use, dissemination, distribution, reproduction of this email is prohibited. Unless explicitly attributed, the opinions expressed
in this e-mail are those of the author only and do not represent the official view of TransGrid. E-mail communications with TransGrid may be subject to automated
e-mail filtering, which could result in the delay or deletion of a legitimate e-mail before it is read by its intended recipient. TransGrid does not accept liability for any
corruption or viruses that arise as a result of this e-mail. Please consider the environment before printing this e-mail.

Vous aimerez peut-être aussi