Académique Documents
Professionnel Documents
Culture Documents
Earthing
By Geoff Cronshaw
Book your
basically the same way as for a damage or chemical
circuit protective conductor, deterioration or be damaged
except that Table 54.1 of BS by electro- dynamic effects
7671 must be applied to any
buried earthing conductor. For
a TN-C-S (PME) supply, it
produced by passing earth
fault current through it. If
mechanical protection is not
place today!
should be no smaller than the provided the minimum size is
London 4 Oct West Ham United FC, Upton Park
main bonding conductors. 4mm2 copper or equivalent. South 25 Oct Portsmouth FC, Fratton Park
East Anglia 1 Nov Newmarket Racecourse
Sizing of circuit protective BS 7671 provides two North West 23 Nov Wigan FC, DW Stadium
conductors methods for sizing protective Yorkshire 24 Nov York Racecourse
There are several factors which conductors including earthing Wales 6 Dec Cardiff City Football Stadium
may influence or determine conductors (see also Table Midlands 24 Jan Birmingham City FC, St. Andrews
Northern Ireland 1 Feb Everglades Hotel, Derry
the size required for a circuit 54.1). The easier method is to
South West 14 Feb National Marine Aquarium, Plymouth
protective conductor. A determine the protective
North East 6 Mar Sunderland FC, Stadium of Light
minimum cross-sectional area of conductor size from Table Scotland 17 Apr Livingston FC
2.5mm2 copper is required for 54.7 but this may produce a
Book online NOW at www.niceicdirect.com
any separate circuit protective larger size than is strictly
conductor, i.e. one which is necessary, since it employs a To find out more click or call
not part of a cable or formed by
a wiring enclosure or contained
simple relationship to the
cross-sectional area of the 0843 290 3468
techtalk@niceic.com
in such an enclosure. phase conductor(s).
TYPE OF EARTHING
SYSTEMS, ADVANTAGES AND
DISADVANTAGES
Protective multiple earthing
(PME).
Such a supply system is
described in BS 7671 as
TN-C-S. The advantage of this
Fig 5 TT system system is that it provides an
effective and reliable method
of providing customers with an
earth connection. For example
the maximum Ze specied by
a distributor is 0.35 for
TN-C-S supplies compared to
0.8 for TN-S supplies.
Fig 6 No earth provided (TT system). Based on 25 mm2 tails and selection from Table 54.7. Note: An
isolator is not always installed by the electricity distributor. Manufacturers recommendations should
be sought with regards to connections to earth electrodes.
The second method involves a Regulation 543.1.3 states: which can ow through the
formula calculation. The The cross-sectional area, associated protective device,
formula is commonly referred where calculated, shall be not due account being taken of the
to as the adiabatic equation less than the value determined current limiting effect of the
and is the same as that used by the following formula or circuit impedances and the
for short-circuit current shall be obtained by reference limiting capability (I2t) of that
calculations (see Regulation to BS 7454. protective device.
434.5.2). It assumes that no ___
heat is dissipated from the S = ___
I 2t Account shall be taken of the
protective conductor during k effect, on the resistance of
an earth fault and therefore where: circuit conductors, of their
errs on the safe side. Even so, temperature rise as a result of
application of the formula S is the nominal cross overcurrent - see Regulation
will in many instances result sectional area of the conductor 413-02-05.
in a protective conductor in mm2.
having a smaller csa than that of t is the operating time of the
the live conductors of the I is the value in amperes (rms. disconnecting device in
associated circuit. This is quite for a.c.) of fault current for a seconds corresponding to the
acceptable. fault of negligible impedance, fault current I amperes.
fixed building
distribution
pitch
socket-outlets
c.p.c. of
distribution cable
distribution board segregated from
pitch supply 30 mA
earthing RCDs
Fig 7 Typical site distribution for a PME supply, separation from PME earth at pitch supply point
fixed building
distribution
100 mA or pitch
greater RCD to socket-outlets
discriminate with
pitch socket-outlet
RCDs
main pitch
distribution board distribution board 30 mA
RCDs
Fig 8 Typical site distribution for a PME supply, separation from PME earth at main distribution board
Neutral Current (DNC). Values in guarantee the earth conductor for connection to distributors service cable into
excess of 100 mA to be subject to connection back to the source, the consumers earth terminal, the premises or to a separate
greater investigation with possible e.g. a low voltage overhead unless inappropriate for protective conductor of, for
recommendation for removal and supply, where there is the reasons of safety (Reg 24 of instance, an overhead supply.
replacement with a TT or isolated
likelihood of the earth wire ESQCR). Construction site,
TN-S system.
either becoming somehow farm or swimming pool Large consumers may have
Also, mines and quarries are disconnected or even stolen. installations might be one or more HV/LV
another area. A supply taken inappropriate unless additional transformers dedicated to their
to an underground shaft, or for A distributor also might not precautions are taken, such as installation and installed
use in the production side of a provide means of earthing for an additional earth electrode. adjacent to or within their
quarry, must have an earthing certain outdoor installations, premises. In such situations
system which is segregated e.g. a construction site TN-S system the usual form of system
from any system bonded to the temporary installation, leaving A TN-S system has the neutral earthing is TN-S. L
PME terminal. it to the consumer to make of the source of energy
suitable and safe connected with earth at one More information on earthing
Finally, because of the arrangements for which they point only, at or as near as is and bonding is available in IEE
practical difficulties in bonding are fully responsible. reasonably practicable to the Guidance Note 5 and 8. Also
all accessible extraneous source and the consumers more information on special
conductive-parts electricity The electricity distributor is earthing terminal is typically locations is available in IEE
distribution companies might required to make available his connected to the metallic Guidance Note 7.
not provide a PME earth to supply neutral or protective sheath or armour of the
construction sites and
agricultural and horticultural
installations.
In addition, Regulation
704.411.3.1 does not allow a
PME earthing facility to be
used as a means of earthing
unless all extraneous
conductive-parts are reliably
connected to the main
earthing terminal in
accordance with Regulation
411.3.1.2.
Furthermore, Regulation
705.415.2.1 includes a note
which states: Unless a metal
grid is laid in the floor, the use
of a PME earthing facility as a
means of earthing for the
electrical installation is not
recommended.
TT system
With TT, the consumer must
provide his or her own
connection to earth, i.e. by
installing a suitable earth
electrode local to the
installation.