Vous êtes sur la page 1sur 8

16 | Your questions answered

Earthing
By Geoff Cronshaw

The IET often receives questions on earthing. In


this article we look at the requirements of BS 7671
together with the advantages and disadvantages
of the various earthing systems.

IET Wiring Matters | Autumn 11


Your questions answered | 17

BS 7671 lists five types of


earthing system, TN-S,
TN-C-S, TT, TN-C and IT. Part
2 describes the systems and
Appendix 9 provides
descriptions of multiple-source
dc and other systems.

When designing an electrical


installation, one of the first
things to determine is the type
of earthing system. For an LV
supply the distributor will be
able to provide this
information. fig 1 Tn-s system

The system will either be TN-S,


TN-C-S (PME) or TT for a
low-voltage supply given in
accordance with the Electricity
Safety, Quality and Continuity
Regulations 2002 as
amended.

This is because TN-C requires


an exemption from the
Electricity Safety, Quality and
Continuity Regulations, and an
IT system is not permitted for a
low voltage public supply in
the UK because the source is
not directly earthed. Therefore
TN-C and IT systems are both
very uncommon in the UK.
fig 2 Cable sheath earth (Tn-s system). schematic of earthing and main equipotential bonding
OvErvIEW Of EarThIng arrangements. Based on 25mm2 tails and selection from Table 54.7. note: an isolator is not always
sysTEMs installed by the electricity distributor
Tn-s system earthing
A TN-S system, shown in practicable to the source, into the premises. main connected with earth at
Fig 1, has the neutral of and the consumers earthing source and at intervals along
the source of energy terminal is typically Tn-C-s system earthing its run. This is usually referred
connected with earth at connected to the metallic A TN-C-S system, shown in to as protective multiple
one point only, at or as sheath or armour of the Fig 3, has the supply neutral earthing (PME). With this
near as is reasonably distributors service cable conductor of a distribution arrangement the distributors

Autumn 11 | IET Wiring Matters


18 | Your questions answered

they make with the


surrounding material. Thus,
they should be driven into
virgin ground, not disturbed
(backfilled) ground.

Where it is necessary to drive


two or more rods and connect
them together to achieve a
satisfactory result, the
separation between rods
should be at least equal to
their combined driven depth to
obtain maximum advantage
from each rod.

In some locations low soil


resistivity is found to be
fig 3 Tn-C-s system concentrated in the topsoil
layer, beneath which there
may be rock or other
impervious strata which
prevents the deep driving of
rods, or a deep layer of high
resistivity. Only a test or known
information about the ground
can reveal this kind of
information. In such
circumstances, the installation
of copper earth tapes, or pipes
or plates, would be most likely
to provide a satisfactory earth
electrode resistance value.

Whatever form an earth


electrode takes, the possibility
of soil drying and freezing, and
of corrosion, must be taken
into account. Preferably,
testing of an earth electrode
should be carried out under
fig 4 PME supply (Tn-C-s system). schematic of earthing and main equipotential bonding arrangements. the least favorable conditions,
Based on 25mm2 tails and selection from Table 54.7. note: An isolator is not always installed by the i.e. after prolonged dry
electricity distributor weather. Further information
on earthing principles and
neutral conductor is also used energy connected as for TN-S, variety of types of earth practice can be found in BS
to return earth fault currents E but no facility is provided by electrode. Regulation 542.2.3 7430:1998 Code of Practice
arising in the consumers the distributor for the lists the types recognised for Earthing (which is current
installation safely to the consumers earthing. With TT, which include earth rods, earth but is being updated).
source. To achieve this, the the consumer must provide his plates and underground
distributor will provide a or her own connection to structural metal work. Earthing conductors
consumers earthing terminal earth, i.e. by installing a Earthing conductors which are
which is linked to the incoming suitable earth electrode local to The soil resistivity of the defined in BS 7671 as a
neutral conductor. the installation. ground is probably the single protective conductor
most important factor in the connecting the main earthing
TT system earthing REquIREMEnTs of Bs 7671 determination of the type of terminal of an installation to an
A TT system, shown overleaf, Earth electrodes earth electrode. Rods can only earth electrode or other means
has the neutral of the source of BS 7671 recognises a wide be as effective as the contact of earthing must be adequately

IET Wiring Matters | Autumn 11


Your questions answered | 19

sized particularly where buried An example would be a bare


partly in the ground, and be of (where permitted) or insulated
suitable material and copper conductor clipped to a
Partner Sponsor
adequately protected against surface, run on a cable tray or
corrosion and mechanical fixed to the outside of a wiring
damage. enclosure. Such a circuit
protective conductor must
The size of an earthing also be suitably protected if it
conductor is arrived at in is liable to suffer mechanical

Book your
basically the same way as for a damage or chemical
circuit protective conductor, deterioration or be damaged
except that Table 54.1 of BS by electro- dynamic effects
7671 must be applied to any
buried earthing conductor. For
a TN-C-S (PME) supply, it
produced by passing earth
fault current through it. If
mechanical protection is not
place today!
should be no smaller than the provided the minimum size is
London 4 Oct West Ham United FC, Upton Park
main bonding conductors. 4mm2 copper or equivalent. South 25 Oct Portsmouth FC, Fratton Park
East Anglia 1 Nov Newmarket Racecourse
Sizing of circuit protective BS 7671 provides two North West 23 Nov Wigan FC, DW Stadium
conductors methods for sizing protective Yorkshire 24 Nov York Racecourse
There are several factors which conductors including earthing Wales 6 Dec Cardiff City Football Stadium
may influence or determine conductors (see also Table Midlands 24 Jan Birmingham City FC, St. Andrews
Northern Ireland 1 Feb Everglades Hotel, Derry
the size required for a circuit 54.1). The easier method is to
South West 14 Feb National Marine Aquarium, Plymouth
protective conductor. A determine the protective
North East 6 Mar Sunderland FC, Stadium of Light
minimum cross-sectional area of conductor size from Table Scotland 17 Apr Livingston FC
2.5mm2 copper is required for 54.7 but this may produce a
Book online NOW at www.niceicdirect.com
any separate circuit protective larger size than is strictly
conductor, i.e. one which is necessary, since it employs a To find out more click or call
not part of a cable or formed by
a wiring enclosure or contained
simple relationship to the
cross-sectional area of the 0843 290 3468
techtalk@niceic.com
in such an enclosure. phase conductor(s).

Autumn 11 | IET Wiring Matters


Your questions answered | 21

k is a factor taking account of


the resistivity, temperature
coefcient and heat capacity of
the conductor material, and
the appropriate initial and nal
temperatures.

TYPE OF EARTHING
SYSTEMS, ADVANTAGES AND
DISADVANTAGES
Protective multiple earthing
(PME).
Such a supply system is
described in BS 7671 as
TN-C-S. The advantage of this
Fig 5 TT system system is that it provides an
effective and reliable method
of providing customers with an
earth connection. For example
the maximum Ze specied by
a distributor is 0.35 for
TN-C-S supplies compared to
0.8 for TN-S supplies.

However, under certain supply

Fig 6 No earth provided (TT system). Based on 25 mm2 tails and selection from Table 54.7. Note: An
isolator is not always installed by the electricity distributor. Manufacturers recommendations should
be sought with regards to connections to earth electrodes.

The second method involves a Regulation 543.1.3 states: which can ow through the
formula calculation. The The cross-sectional area, associated protective device,
formula is commonly referred where calculated, shall be not due account being taken of the
to as the adiabatic equation less than the value determined current limiting effect of the
and is the same as that used by the following formula or circuit impedances and the
for short-circuit current shall be obtained by reference limiting capability (I2t) of that
calculations (see Regulation to BS 7454. protective device.
434.5.2). It assumes that no ___
heat is dissipated from the S = ___
I 2t Account shall be taken of the
protective conductor during k effect, on the resistance of
an earth fault and therefore where: circuit conductors, of their
errs on the safe side. Even so, temperature rise as a result of
application of the formula S is the nominal cross overcurrent - see Regulation
will in many instances result sectional area of the conductor 413-02-05.
in a protective conductor in mm2.
having a smaller csa than that of t is the operating time of the
the live conductors of the I is the value in amperes (rms. disconnecting device in
associated circuit. This is quite for a.c.) of fault current for a seconds corresponding to the
acceptable. fault of negligible impedance, fault current I amperes.

Autumn 11 | IET Wiring Matters


22 | Your questions answered

pitch supply pillar


overcurrent
protective devices

fixed building
distribution
pitch
socket-outlets

c.p.c. of
distribution cable
distribution board segregated from
pitch supply 30 mA
earthing RCDs

PME supply pitch


supply earthing

Fig 7 Typical site distribution for a PME supply, separation from PME earth at pitch supply point

pitch supply pillar


overcurrent
protective devices

fixed building
distribution
100 mA or pitch
greater RCD to socket-outlets
discriminate with
pitch socket-outlet
RCDs
main pitch
distribution board distribution board 30 mA
RCDs

pitch supply earthing


PME supply (resistance area separated from
supply earthing)

Fig 8 Typical site distribution for a PME supply, separation from PME earth at main distribution board

IET Wiring Matters | Autumn 11

24 | Your questions answered

system fault conditions (PEN conductor to be connected


conductor of the supply electrically to any metalwork in
becoming open circuit external a caravan or boat. This
to the installation) a potential prevents PME terminals being
can develop between the used for caravans or boat
conductive parts connected to mooring supplies, although
the PME earth terminal and they may be used for fixed
the general mass of earth. premises on the sites, such as
However, since there are the site owners living premises
multiple earthing points on the and any bars or shops, etc.
supply network and bonding is
provided within the building Filling stations are another area
complying with BS 7671, the where precautions need to be
risk is considered to be small. taken. The reference publication is
the 3rd edition Design,
Special Locations construction, modification,
The Energy Networks maintenance and de-commissioning
Association publications of filling stations published by the
Association for Petroleum and
provides guidance on PME
Explosive Administration (APEA) and
systems. Whilst PME systems
the Energy Institute (EI) which for
provide an effective and
new sites and sites undergoing
reliable earth connection
refurbishment then a TT or a TN-S
precautions need to be taken
system are used where the TN-S is
when dealing with special
exclusive to the filling station and
locations. not shared with any other electricity
consumers. APEA and the Energy
For example Regulation 9(4) of Institute (EI) advise that for existing
the Electricity Safety, Quality sites where TN-C-S or a TN-S supply
and Continuity Regulations shared with consumers is utilised
does not allow the combined these must be risk assessed with
neutral and protective regards the value of the Diverted

IET Wiring Matters | Autumn 11


26 | Your questions answered

Neutral Current (DNC). Values in guarantee the earth conductor for connection to distributors service cable into
excess of 100 mA to be subject to connection back to the source, the consumers earth terminal, the premises or to a separate
greater investigation with possible e.g. a low voltage overhead unless inappropriate for protective conductor of, for
recommendation for removal and supply, where there is the reasons of safety (Reg 24 of instance, an overhead supply.
replacement with a TT or isolated
likelihood of the earth wire ESQCR). Construction site,
TN-S system.
either becoming somehow farm or swimming pool Large consumers may have
Also, mines and quarries are disconnected or even stolen. installations might be one or more HV/LV
another area. A supply taken inappropriate unless additional transformers dedicated to their
to an underground shaft, or for A distributor also might not precautions are taken, such as installation and installed
use in the production side of a provide means of earthing for an additional earth electrode. adjacent to or within their
quarry, must have an earthing certain outdoor installations, premises. In such situations
system which is segregated e.g. a construction site TN-S system the usual form of system
from any system bonded to the temporary installation, leaving A TN-S system has the neutral earthing is TN-S. L
PME terminal. it to the consumer to make of the source of energy
suitable and safe connected with earth at one More information on earthing
Finally, because of the arrangements for which they point only, at or as near as is and bonding is available in IEE
practical difficulties in bonding are fully responsible. reasonably practicable to the Guidance Note 5 and 8. Also
all accessible extraneous source and the consumers more information on special
conductive-parts electricity The electricity distributor is earthing terminal is typically locations is available in IEE
distribution companies might required to make available his connected to the metallic Guidance Note 7.
not provide a PME earth to supply neutral or protective sheath or armour of the
construction sites and
agricultural and horticultural
installations.

In addition, Regulation
704.411.3.1 does not allow a
PME earthing facility to be
used as a means of earthing
unless all extraneous
conductive-parts are reliably
connected to the main
earthing terminal in
accordance with Regulation
411.3.1.2.

Furthermore, Regulation
705.415.2.1 includes a note
which states: Unless a metal
grid is laid in the floor, the use
of a PME earthing facility as a
means of earthing for the
electrical installation is not
recommended.

TT system
With TT, the consumer must
provide his or her own
connection to earth, i.e. by
installing a suitable earth
electrode local to the
installation.

The circumstances in which a


distributor will not provide a
means of earthing for the
consumer are usually where
the distributor cannot

IET Wiring Matters | Autumn 11

Vous aimerez peut-être aussi