Location Bagri
District Rajgarh
18 m
Nagar palika , Rajrah
1.0 GENERAL
1.1 Scope
This document covers the analysis and design of 3000 kL ESR AT Bagri, District Rajgarh with 18
m staging height for Nagar palika , Rajrah.
1) IS: 456 -2000 Code of practice for plain and reinforced concrete
2) IS: 3370 (Part-1)-2009 Concrete Structures for Storage of Liquids Code of Practice Part-1
General Requirements
3) IS: 3370 (Part-2)-2009 Concrete Structures for Storage of Liquids Code of Practice Part-2
Reinforced Concrete Structures
4) IS: 875 (Part-3) -1987 - Code of practice for Design Loads (Other than Earthquake) for Building
and Structures. Part-3 Wind Loads
5) IS: 11682-1985 Criteria for design of RCC staging for overhead water tanks.
6) IS: 1893-2002 - Criteria for Earthquake Resistant design of structures. Part-1 General Provisions
of buildings
7) IS: 1893-2014 - Criteria for Earthquake Resistant design of structures. Part-2 Liquid Retaining
Tanks
8) IS 13920:2016 Ductile detailing of reinforced concrete structures subjected to seismic force
code of practice.
9) SP: 16 Design Aids for Reinforced Concrete
2000 kL ESR AT jagira with 20.5 m staging height will be a Reinforced concrete Circular Elevated
water tank, supported on column/beam staging (height of 20.50 m) resting on solid circular
raft. The internal diameter of the tank is 19.1 m and is supported on grid of orthogonal beams
and a ring beam, which are supported on columns resting on circular raft. Top roof of the tank
consists of a slab supported on beams with a maximum span of 4.57 m spanning between the
circular columns submerged inside the tank. Total Height of tank is 6.55 m which consists of a
liquid depth of 6.0 m, free board of 0.3 m below the soffit of lowest beam, and web depth of
top cover slab beam (0.25 m). The Tank Floor slab level of tank is at EL (+) 18.0 m and
Maximum Water Level at EL (+) 24.52 m. Bottom floor slab is spanning between beam column
arrangements. For the maintenance purpose tank is provided with an access through separate
RCC staircase.
4 STRUCTURAL ANALYSIS
4.1 Modelling
ESR walls, is modelled as Plate element in STAAD-PRO with staging. Bottom of columns are
considered fixed at foundation level. Staging is modelled with beam element. Stiffness of the
staging for seismic base shear calculation is obtained through a separate load of 100kN. Wall
has been modelled separately for base Hinged and 50% base fixity.
The structure is analyzed using STAAD-PRO. Walls, Cover Slab, Base Slab & Foundation are
designed using in-house developed Spread sheets. All RCC members like Walls, Roof Slabs &
beams, base slab & beams, submerged Columns etc. of the container are designed as un-
cracked sections as per IS: 3370 (Part 2). However, staging columns are designed by limit state
method, Tie beams, plinth beams and foundation is designed using limit state method as per
IS: 456-2000. Column and beams are detailed as per IS 13920:2016.
d) Wind load
Various design parameters for calculation of wind loads on structures are determined on the
basis of IS: 875 (Part III). Following parameters has been considered for the wind load
calculation.
Height Vb K1 K2 K3 Vz Pz
0-10m 39 1.06 0.98 1 40.51 0.98
10-15m 39 1.06 1.02 1 42.17 1.07
15-20m 39 1.06 1.05 1 43.41 1.13
20-30m 39 1.06 1.1 1 45.47 1.24
e) Seismic load
The seismic analysis of the ESR will be carried out as per IS: 1893 (Part-II) -2014.
The design horizontal seismic coefficient Ah for the structure will be determined using the
following parameters
Seismic zone = IV
Zone Factor (Z) = 0.10
Ah = [(Z/2) (I/R) (Sa/g)]
Response reduction factor R = 2.5
Importance factor, I =1.5
Damping = 5%
Value of Sa/g is taken from Fig.2 (For Rock )
Loads Calculation
d) Wind load
Various design parameters for calculation of wind loads on structures are determined on the
basis of IS: 875 (Part III). Following parameters has been considered for the wind load
calculation.
Height Vb K1 K2 K3 Vz Pz
0-10m 44 1.06 1 1 46.64 1.31
10-15m 44 1.06 1.05 1 48.97 1.44
15-20m 44 1.06 1.07 1 49.90 1.49
20-30m 44 1.06 1.12 1 52.24 1.64
e) Seismic load
The seismic analysis of the ESR will be carried out as per IS: 1893 (Part-II) -2014.
The design horizontal seismic coefficient Ah for the structure will be determined using the
following parameters
Seismic zone = II
Zone Factor (Z) = 0.10
Ah = [(Z/2) (I/R) (Sa/g)]
Response reduction factor R = 2.5
Importance factor, I =1.5
Damping = 5%