Vous êtes sur la page 1sur 3

JOB NO.

WKVECS-WE408-001
CALCULATION Fan Motor Detail
DATE November 27, 2017
SERVICES ACMV
JOB DESCRIBTION
REF. NO. WKVECS-WE408-ACMV-C-01

Input: Output:

Fan Air Flow Rate = 500 L/s Fan Absorbed Power = 0.08 kW

Fan Total Pressure = 100 Pa Motor Power Required = 0.09 kW

Fan Efficiency = 65 % Motor Rating = 0.1 kW @ Single Phase

VSD Drive = No Running Amp = 0.51 Amp

Safety Factor = 20 % Starting Amp = 2.56 Amp

Type of Supply = Single Phase

Notes: 1) Type of Starter - Motor Power less than 500W = No starter required
Motor Power 500W to 3.7kW = DOL
Motor Power 3.7kW to 15kW = Star Delta
Motor Power more than 15kW = Soft starter or Auto-Transformer

2) Type of Supply - Motor Power 700W or less = Single Phase


Motor Power more than 700W = Three Phase

3) Formula - Air flow rate(m3/s) x Fan total pressure(Pa)


Fan Absorbed Power, kW =
Fan efficiency(%)x10

file:///conversion/tmp/scratch/372819872.xlsx Page 1 of 3
Services Password To Unlock Cell
Hydraulic
Fire Protection Safety Factor
ACMV VSD No 20% Maximum
Natural Gas Yes 20% to 25%
LPG
Vertical Transportation Supply Single Phase
BAS Three Phase
Single Phase Motor Rating Three Phase Motor Rating
kW kW
0.07 0.1
0.07 0.1 0.1 0.12
0.1 0.12 0.12 0.18
0.12 0.18 0.18 0.25
0.18 0.25 0.25 0.37
0.25 0.37 0.37 0.56
0.37 0.56 0.56 0.75
0.56 0.75 0.75 1.1
1.1 1.5
1.5 2.2
2.2 3
3 3.7
3.7 4
4 5.5
5.5 7.5
7.5 9.3
9.3 10
10 11
11 15
15 18
18 22
22 30
30 37
37 45
45 55
55 75
75 90
90 110
110 130
130 150