Disusun oleh :
FERNANDO RAFLYANDI (1602069)
3. Lampu :
A. Jenis TL : 8 Lampu
B. Tegangan : 18 watt
`
1. Beban eksternal
a) Dinding
b) Atap
c) Kaca
d) Solar radiasi
2. Beban Internal
a) Konduksi melalui struktur internal
Partisi
Langit langit
Lantai
b) Penghuni/ orang
Beban sensible
Beban Laten
c) Peralatan
Terminal
Infocus
Komputer
CPU
d) Lampu
3. Beban Infiltran dan Ventilasi heat loss
MENGHITUNG BEBAN COOLING LOAD
1. Perhitungan Eksternal \
B. Atap
( Edward G. Pita hal 123 )
= 78 + (-4.4 ) + ( -8.1 )
= 65.5
Q = U x A x CLTDc
= 2936.8 BTU
C. Kaca
Q = U x A x CLTDc
= 1.04 x 137.05 x 13
= 1853
D. Solar Radiasi
Q = SHGF x A x SC x CLF
= 44 x 137.05 x 0.94 x 1
= 5668.388 BTU
2. Perhitungan Internal
A. Konduksi Melalui Struktur Internal
a. Langit langit
Q = U x A x TD
= 0.23 x 210.5 x 9.4
= 455.101
b. Lantai
Q = U x A x TD
= 0.59 x 210.5
= 1167.433
c. Partisi ( Tabel A.7 Edward G. Pita )
1. Dinding Utara
Q = U x A x TD
= 423.47 BTU
2. Dinding Selatan
Q = U x A x TD
= 0.25 x 180.2 x 9.4
= 423.47 BTU
3. Dinding Barat
Q = U x A x TD
= 0.25 x 148.2 x 9.4
= 348.27 BTU
B. Penghuni ( 6.13 Edward G. Pita )
a. Beban Sensibel
QS = qs x n x CLF
= 225 x 29 x 0.58
= 3784.5
b. Beban Laten
QL = ql x n
= 105 x 29
= 3045
C. Peralatan
a. Terminal (ASHRAE)
QL = Cl x ql
= 0.17 x 270
= 45.9 BTU
~ 45.9 x 31 = 1422.9 BTU
QS = Cs x qs x CLF
= 0.33 x 270 x 0.58
= 51.678 BTU
~ 51.678 x 31 = 1602.018 BTU
b. Infocus
QL = Cl x ql
= 0.17 x 853
= 145.01 BTU
QS = Cs x qs x CLF
= 163.2642 BTU
= 1 x 0.45
= 0.45
~ QS = 1.1 x CFM x TC
= 1.1 x 0.45 x 14.4
= 7.128