Académique Documents
Professionnel Documents
Culture Documents
In the previous post about Directional Overcurrent relay (67) testing (Finding the Direction in
Directional Overcurrent Relays), we reviewed Directional Overcurrent protection from a system
perspective to enhance the descriptions in The Relay Testing Handbook: Principles and Practice
or The Relay Testing Handbook #1: Electrical Fundamentals for Relay Testing. Well be looking
at Directional Overcurrent relays from a testing perspective in this post.
A traditional relay tester, or automated testing software, will often apply a test scenario like the
following:
This test plan may work depending on the sophistication of the relay, but theres a pretty good
chance that the pickup tests will work, and the timing test will fail. In this scenario, you might
get frustrated and start disabling the directional function, or start looking for the non-directional
relay definitions so you can map them to a test output. Lets take a closer look at your test plan
before you, or your test software, head down that path.
Based on the drawing of your test plan, it looks like youve met the first two criteria for a
successful Directional Overcurrent test:
Directional relays need a reference to work correctly, and that reference is called the polarizing
signal. The Directional Overcurrent element needs a polarizing signal to operate reliably;
otherwise anything could happen depending of the sophistication of the relay.
Most electro-mechanical relays, and GE relays like the one from The Relay Testing Handbook
example, use the phase-phase voltage from the two un-faulted phases as a polarizing signal. You
could drive yourself crazy trying to figure out how to apply the test and phasor diagrams from
older relay manuals to modern test-sets.
Or you can test all relays that use the un-faulted voltages as a polarizing signal by simply
applying three-phase balanced voltages as shown in this phasor diagram from the previous post.
We added the B-C phase-phase voltage to the drawing, which is the polarizing voltage this style
of relay uses.
If we rotate the standard phasor diagram by 90 and add the same labeling used by the relay
bulletin drawings, we can see that simply adding voltage will allow us to successfully test every
relay of this type.
You can tell by graphically adding the three voltages together, or with the negative sequence
formula.
The negative sequence, or unbalance voltage, is zero in a balanced system. Therefore, our
previous test plan will not have a polarizing signal on relays that use negative sequence
polarizing.
We can fix this problem by thinking about what happens during a phase-to-ground fault.
What happens to the faulted voltage? The faulted voltage will drop; how much it drops
depends on the severity of the fault. The worst possible fault would drop the fault voltage
to near zero, but most faults wont be that severe. We can cut the faulted voltage in half
to simulate a phase-to-ground fault.
What happens to the faulted current? The faulted currents will jump to a higher value,
and we know from the relay settings how much current we need for the relay to detect a
fault. Set the fault current at least 110% of the relays pickup setting.
What happens to the other voltages and currents that arent faulted? They would
change slightly during a real fault, but you would need some modelling software to figure
out how much. We can assume that they dont move, like textbooks do, for testing
purposes.
If we alter our test plan to better simulate a fault, it would look like the revised plan below.
These drawings look at the same test plan for a Directional Overcurrent (67) element that uses
negative sequence voltage. We start with the raw currents and voltages, then calculate the
negative sequence voltage, and then plot the operating current and polarizing signal (V2). This
test plan has a good chance of being successful because we have an operating signal and a
polarizing signal.
We appear to be in good shape for most Directional Overcurrent (67) applications. However,
there will be times when this test plan will not work. What are the odds that a phase-to-
ground fault will be 100% resistive? The answer is never. Actually, there are almost no purely
resistive systems as we discussed in the previous article, so our test current at zero degrees can
cause problems, especially near generation systems like wind farms that can have crazy
characteristics or very high voltage (>115kV) applications. Some relays have an operating
characteristic like the following picture:
Notice that our test current is right on the edge of the reverse direction. This means that it is a
coin toss whether the relay will operate or not. We can ensure the relay always operates by
setting the faulted current to a fault angle that would happen in the system. You can choose a
good fault angle using one of these methods:
Most modern relays have a positive sequence angle setting that defines the expected fault
angle. Set the fault angle to that setting.
If you have a good understanding of fault characteristics, you could guess the fault
angles.
o A very high voltage system (>115kV) will have a characteristic near 90 degrees,
so you could safely choose a fault angle of 87.
o A high voltage system (>69kV) will have a fault angle closer to 75.
o A distribution system (>34kv) will have a fault angle closer to 60.
o A medium voltage system will have a fault angle closer to 45.
You can never go wrong with a fault angle of 60 or 75. This is what electro-mechanical
relays used because their options were limited and they needed a good average.
Our test will work for all common characteristic angles if we modify it to include the phase angle
during a fault.
Modern testing equipment makes this easy, which means you can spend more time
understanding the application so you can become a true relay testing craftsman.
Please like and share this post if you found it useful. It helps us get noticed, which means we can
post more free content.