The specified unit of the parameter for the Inverter should be 1r/min.
Frequency command setting/The motor pole number should be set as reference unit.
(3G3MV, CIMR-V7AZ:n035=2 to 39 / 3G3RV, CIMR - (F7Z,E7Z):o1-03=2 to 39)
The allocated size should be used 4 types by using 2 channels for both OUT and IN area.
(For using the standard remote I/O settings)
For using the FB, the remote I/O area first address of Slave unit allocated to DeviceNet Master Unit should
be required. For details, refer to the manual listed in the Related manuals below.
Function The speed command is operated for the Inverter specified by Master Unit No. (MasterUnitNo) and Inverter
description Slave Address (NodeNo).
The speed is specified using a frequency (r/min).
The poll number (4.6 etc) used in the parameter (MV:n35 RV:o1-03) of Inverter should be set and manage
the commands with r/min unit. The default setting for unit is Hz.
The operation command is written to the remote I/O area when Start (Execute) turns ON, or when Master
Unit No. (MasterUnitNo), Inverter Slave Address (NodeNo), and Direction (Direction) are changed while Start
(Exeute) remains ON.
Speed is written to the remote I/O area every cycle while Start (Execute) remains ON.
If Speed or Direction is set out of the range while Srart (Execute) remains ON, Aborted (CommandAborted)
will be turned ON.
If Start (Execute) is ON and the operation command is OFF, it will be assumed the FB of [Fixed Allocation]
Deceleration Stop (_INVDRT060_Stop) has been executed and Aborted (CommandAborted) will be turned
ON.
If Direction detects the reverse operation command while Start (Execute) remains ON, Aborted
(CommandAborted) will be turned ON.
FB Inverter uses 2 channels for both OUT and IN area, so 4 types should be used for the allocated size.
precautions If Frequency command is set over the frequency maximum (FMAX) (3G3MV, CIMR-V7AZ:n011 / 3G3RV,
CIMR - (F7Z,E7Z):E1-04), it will be operated ignoring Frequency at the execution. For this case,
Frequency that is executed before will be operated.
This Function Block is processed over several cycles.
Timechart
Start(Execute) ON
OFF
Inverter Speed
Application When bit A is turned ON, operation is started for Inverter 20 allocated to OUT area first address CIO100 and
example IN area first address CIO200, which connected to the DeviceNet Unit with a unit number of 10.
&10
CPU DRM
Unit No.:10
Inverter DRT2:20
OUT Area CIO100 to 101
IN Area CIO200 to 201
DRT2 20
Inverter
Always ON(P_ON)
_INVDRT035_MoveVelocityRPM_Free
(BOOL) (BOOL)
OUT Area ID EN ENO
(WORD) (BOOL) Speed agreement
P_CIO
OutAreaID InVelocity Bit B
OUT Area No
(INT) (BOOL) Aborted
&100
OutAreaNo CommandAborted Bit C
IN Area ID
(WORD) (BOOL) Error end
P_CIO
InAreaID Error Bit D
IN Area No
(INT) (WORD) Error number
&200
InAreaNo ErrorID
Start
(BOOL)
Bit A
Execute
Frequency
(REAL)
1200r/min +1200.00 Velocity
Rotation Direction (INT)
Reverse &1 Direction
Variable Tables
Input Variables
Name Variable name Data type Default Range Description
EN EN BOOL 1 (ON): FB started
0 (OFF): FB not started.
OUT Area ID AreaID WORD #0082 See P_CIO (#00B0): CIO Area
description P_WR (#00B1): Work Area
P_HR (#00B2): Holding Area
P_DM (#0082): DM Area
P_EM0 (#0050) to P_EMC (#005C):
EM Area bank 0 to 1C
OUT Area No AreaNo INT #0000 See The range depends on the value of the OUT
description Area ID (OutAreaID)
Specified CIO area: &0 to &6142
Specified WR area: &0 to &510
Specified HR area: &0 to &510
Specified DM area: &0 to &32766
Specified EM area: &0 to &32766
IN Area ID MSGAreaID WORD #0082 See Same as OUT Area ID (AreaID)
description
IN Area No. MSGAreaNo INT #0000 See Same as OUT Area No. (AreaNo)
description
Start Execute BOOL 0(OFF) 1 (ON): Operation started
0 (OFF): All of the following are turned OFF:
InVelocity, CommandAborted, Error, and
ErrorID.
Speed Velocity REAL +0.0 Over +0.0 Specify the integer value in units of Real.
Any digits below the setting unit (1r/min) are
truncated.
Direction Direction INT 0 &0&1 &0: Forward
&1: Reverse
Output Variables
Name Variable name Data type Range Description
ENO ENO BOOL 1 (ON): FB processed normally.
(May be omitted.) 0 (OFF): FB not processed or ended in an error.
Speed agreement InVelocity BOOL 1 (ON): Speed agreement
Aborted CommandAborted BOOL 1 (ON): Aborted
Error end Error BOOL 0 (OFF): Other status
1 (ON): Error in FB
Error number ErrorID WORD #0000: No error
(May be omitted.)
Version History
Version Date Contents
1.00 2005.7. Original production
Note
This manual is a reference that explains the function block functions.
It does not explain the operational limitations of Units, components, or combinations of Units and components. Always read
and understand the Operation Manuals for the systems Units and other components before using them.