1 BASIS OF CALCULATION

Total External Static Pressure Loss is calculated based on highest pressure drop path.

Air Volume is referred from DD2 equipment schedule.

System Layout is extracted from coordinated shop drawing Model.

Duct pressure loss per meter is calculated based on ASHRAE Friction Chart for Round Ducts.

Equations used in the calculation to arrive pressure loss, based on ASHRAE Handbook Fundamentals 2009,
Chapter 21.

a. Equivalent Diameter of the duct

b. Hydraulic Diameter

c. Velocity Pressure

d. Reynolds number

Document Number: M006-GDB-MHV-RPT-00150 Rev 1 Page 19 of 37 23-Nov-2017


Uncontrolled if printed, refer to EDMS for current version
e. Friction Losses as per Darcy and Colebrook equations

a. Fitting loss coefficient

f. Duct Roughness Factor

Pressure drop for other duct components are referred from shortlisted vendor material approval submittal.
Refer section 5.3 backup documents.

Document Number: M006-GDB-MHV-RPT-00150 Rev 1 Page 20 of 37 23-Nov-2017


Uncontrolled if printed, refer to EDMS for current version